eltherm ELTC-MV2 User manual

www.eltherm.com
OPERATION-
MANUAL
ELTC-MV2
Handling, operation and adjustment
ELTC-MV2 Moduvise
eltherm GmbH
Ernst-Heinkel-Straße 6 -10
57299 Burbach, Germany
T.: +49 2736 4413-0
F.: +49 2736 4413-0
BU 123
P
1 2 3 4
www.eltherm.com

www.eltherm.com
2
operation manual
temperature contoller ELTC-MV2
BU 123
Revision 1
CONTENT
OPERATION
GENERAL
MESSAGES
PARAMETER
STRUCTURE SWITCH
MODBUS INTERFACES
FUNCTIONAL DESCRIPTIONS
SETPOINT CONTROLLER W1
RAMP MODE
EXTERNAL SETPOINT
SLIDING SETPOINT
LIMITER
DOWNLOADS
Particularly important points in these instructions are marked by symbols:
important information and instructions for safe, eecti-
ve and environmentally compatible use.
NOTE
i
indicates an potential dangerous situation. If it is
not avoided, there is a risk of damage or malefunction.
CAUTION
WARNING
indicates a dangerous situation. If it is not avoided,
there is a risk of injury or at least a high risk of damage.
DANGER
indicates an extremely dangerous situation. If it is
not avoided, there is a danger to life or at least a high risk of serious injury.
3
3
3
4
5
5
5
5
5
5
DESCRIPTION AND TECHNICAL DATA
DESCRIPTION
TECHNICAL SPECIFICATIONS
CONNECTION AND CONTROL PANEL
SPECIAL CONDITIONS
INSTALLATION AND SAFETY INSTRUCTIONS
GOODS RECEIPT
STORAGE
DISPOSAL
DECLARATION OF CONFORMITY
6
6
7
7
10
11
12
12
16
21
24
27
27
eltherm GmbH
Ernst-Heinkel-Str. 6-10
57299 Burbach
T.: +49 2736 4413-0
F.: +49 2736 4413-50
Document:
008MV02
BU - 123
operation manual
temperature controller ELTC-MV2
Autor Peter Schmidt
Revision: 1 27.10.2022_je 07.06.2021
Reservation
We reserve the right to make technical changes. Changes, errors and misprints do not justify any no claim for compensation. For
safety components and systems, the installation instructions and the relevant standards and regulations must be observed.

3
www.eltherm.com 3
www.eltherm.com
DESCRIPTION AND TECHNICAL DATA
DESCRIPTION
Temperature controller for heating applications such as
heating cables in industrial plants, with additional alarm relay.
Design for DIN rail mounting. Temperature sensor Pt100 in
3- or 2-wire technology, thermocouples type J, thermocouple
type K or standard signals (0/2V - 10V, 0/4mA - 20mA). Many
dierent control functions.
Operating status LEDs
LED 1 = operation (heating on)
LED 2 = ramp mode
LED 3 = signaling relay (alarm 2)
LED 4 = alarm relay (alarm 1)
Soft start
When using the internal hybrid relay as a switching output, a
soft start phase is initiated for 20 seconds before each cold start
of the load relay (with 14% power via triac output) in order to
reduce the starting current.
Digital inputs
DigIn1 is used with structure switch position S07 – 2 (external
controller release) and serves as an external release of the load
output.
DigIn2 is used with the structure switch position S04 - 5 (limiter
function) and serves as an external unlocking.
DigIn3 is used with structure switch position S03 – 6 (W1/W2
switchover) and is used to switch between W1 and W2.
Dimensions ELTC-MV2
TECHNICAL SPECIFICATIONS
contoller type ELTC-MV2
operating voltage 100V..277VAC, +/-10%,
50/60Hz, 24VDC, +/-5%
power consumption max. 5,5 W
Relay K1 20A res./ max 277 VAC
Relay K2 and K3 8A res. / max. 250 VAC
1A res. / 24 VDC
operating temperature -25...+55°C
storage temperature -30...+60°C
adjustment range -50…+950°C, congurable
display range/ resolution -50...+999°C
accuracy ± 1K, ± 2 Digits (-50..400°C)
Display / relay indicator LED, rot, 11mm, three digits
terminals
sensor: 0,2…1,5mm²
copper line
others: 0,1…2,5mm²
solid copper,
stripping length 5…6mm
sensor connection
Pt100 2- or 3-wire,
thermocouples J or K, stan-
dard signal;
meets requirements for
operation with
ELTF PTEx sensors
interface RS485
attachment TS35
Protection class IP20
P
1 2 3 4
ELTC-MV2
www.eltherm.com
153 mm (6.02 in)
47 mm (1.85 in)
63 mm (2.48 in)
93 mm (3.66 in)

www.eltherm.com
4
operation manual
temperature contoller ELTC-MV2
BU 123
Revision 1
CONNECTION / CONTROL PANEL
control panel
LEDs in the display
"1" = control relay ON
"2" = two-point operation
"3" = proportional operation
"4" = alarm relay activated (=de-energized)
Flashing of the LEDs indicates a functional delay.
connection (example)
buttons
" " = increase values
" " = decrease values
"P" = programming button
ELTC-MV2
Input
24VDC
(-) (+)
Digital
Input
(D3)(D2)(D1)(Us)
Output U/I 1
(GND)(U)(I)
Output U/I 2
(GND)(U)(I) SCADA
ModBus
(12V)(S)(GND)(A)(B)
System
ModBus
(GND)(A)(B)
Input
external U/I 1
(I)(GND)(U)
Input U/I
(I)(GND)(U)
Sensor 2 Sensor 1
X10 X9 X8 X7 X6 X5 X4 X3 X2 X1
2 1 4 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1
5 4 3 2 1
X11 X12 X13 X14 X15
1 2 3 1 2 3 1 2 3 1 2 3
1 2 3 4
N-Terminal
(N)(N)(N)
PE-Terminal
(PE)(PE)(PE)
Power supply input
A + heating cable output
(L(A))(L1)(L1)(L(heca))
Alarm relay
(Com)(NC)(NO)
OT-Relay
(Com)(NC)(NO)
ϑϑ
when using same phase
bridge X13.2 to X13.1
( )
K1 K2 K3
N
PE
L
P
1 2 3 4
ELTC-MV2
www.eltherm.com
X10 X9 X8 X7 X6 X5 X4 X3 X2 X1
2 1 4 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1
5 4 3 2 1
X11 X12 X13 X14 X15
1 2 3 1 2 3 1 2 3 1 2 3
1 2 3 4

5
www.eltherm.com 5
www.eltherm.com
INSTALLATION AND SAFETY INSTRUCTIONS
SPECIAL CONDITIONS
GOODS RECEIPT
STORAGE
i
i
i
DISPOSAL
DECLARATION OF CONFORMITY
•Electrical connection / commissioning must be carried
out by a qualied electrician.
•The relevant local safety regulations must be observed.
•Observe the connection values according to the rating
plate.
•Avoid tensile stress and torsion of the connected
cables
CAUTION
WARNING
Before starting work on
heating or connection cables or connection
terminals is to ensure that the corresponding circuit is
switched o and is secured against unintentional
restart
CAUTION
The sensor lines must be shielded
when extended, the shielding must be grounded on
one side close to the controller. The line must not be
laid parallel to lines carrying mains voltage. The total
line resistance must not exceed 10 ohms.
After switching on the controller, the
display shows the current actual value.
NOTE
Storage should be in a dry place at an
ambient temperature of 0°C to 50°C.
NOTE
The WEEE logo (shown above) indicates
that this product should not be disposed of with your
household waste.
You can obtain more information on disposal and
restoration of electrical and electronic
old devices and collection points from your local was-
te disposal company or from the manufacturer where
you purchased the product.
NOTE
Upon receipt of the goods, check the controllers and accesso-
ries and compare the data on the nameplate with the data on
the delivery note to ensure that the correct material has been
supplied.
We declare that the product described fully complies with
the directives 2014/35/EU, 2014/30/EU and 2011/65/EU. If you
need a detailed declaration of conformity, please contact us.

www.eltherm.com
6
operation manual
temperature contoller ELTC-MV2
BU 123
Revision 1
GENERAL
After switching on, the type number ("CU2") and software ver-
sion of the device appear and after approx. three seconds the
measured actual value. By pressing the arrow keys / you
can scroll through the parameters P01 – P08 (purely display
parameters). After approx. 60 seconds the display jumps back
to the actual value. If the„P“ button is pressed for approx. 3
seconds, you get to the parameter list ("P10" is shown on the
display). Holding the„P“ button down for another 3 seconds
will display "C" for degrees Celsius (°C) or "F" for degrees Fah-
renheit (°F). If the„P“ button is pressed longer, the device type,
software version and build state are displayed. By pressing„ “
and„ “ simultaneously for approx. 3 seconds, you can access
the structure switch list via the parameter list.
Call up and change parameters
In order to reach the parameter list, „P“ must be pressed for
approx. 3 seconds until“P10” appears on the display.
Press „P“ for 3 seconds
Parameter no. appears
Press „ / “
select parameters
Press „P“
parameter value appears
Press „ / “
change parameters
Press „P“
New value saved, back to parameter no.
Press „ / “ until „P01“ or T > 1 minute
Exit input mode
Call up and change structure switches
In order to reach the structure switch list, the „ “ and„ “
keys must be pressed simultaneously in the parameter list for
approx. 3 seconds until "S01" appears on the display.
Press „P“ for 3 seconds
Parameter no. appears
Press „“ and„ “ simultaneously for 3 seconds
Structure switch S01 appears
Press „ / “
Select structure switch
Press „P“
switch position appears
Press „ / “
change switch position
Press „P“
New value saved, back to structure switch.
Press „“ and„ “ simultaneously for 3 seconds
Return to the parameter list
Press „ / “ until „P01“ or T > 1 minute
Exit input mode
Protection against unauthorized operation
In principle, the control setpoints can be set freely, provided
they are not limited by "P13/P14" or "P23/P24". All other para-
meters are protected by a code.
If a code is required, the display shows "C00". The required
code number "C42" is set with the arrow keys„ / “ and
conrmed with„P“.
After about 1 minute without pressing a button, the code is
requested again.
Autoscrolling
If you hold down the arrow keys„ / “ the values continue
to run automatically.
Factory reset
To restore the factory settings, you rst need to enter the code
"C42". To do this, any parameter simply has to be selected and
changed. After entering the code, the factory settings can be
restored by pressing all buttons simultaneously for approx. 5
seconds.
OPERATION

7
www.eltherm.com 7
www.eltherm.com
MESSAGES
Error messages
In the event of an error, the display shows an error code. Sen-
sor errors are displayed with a delay of approx. 10 seconds.
Error codes
• E01 = AE1: Sensor short circuit (Pt100 only)
or temperature < -60°C
• E02 = AE1: sensor interruption
• E03 = AE1: 3rd wire missing or R ≥ 10Ω (thermocouple only),
• E04 = AE2: Sensor short circuit (only Pt100)
or temperature < -60°C
• E05 = AE2: sensor interruption
• E06 = AE2: 3rd wire missing or R ≥ 10Ω (thermocouple only)
• E07 = AE3: short circuit current/voltage input, interruption
current/voltage input
• E08 = AE4: short circuit current/voltage input, interruption
current/voltage input
• E09 = Hybrid relay open error
• E10 = Error hybrid relay short circuit.
• E11 = limiter active
• E12 = no mains supply (heating)
• E19 = internal error
Warning codes
• C00 = Protected parameter Code entry required (Set "C42"
with the arrow keys„ / “„C42“ and conrm with "P".)
• AL1 = over/under temperature input 1
• AL2 = over/under temperature input 2
• AL3 = Alarm current monitoring output, load current < 0.3A
• SP2 = second set value via digital input active
• oFF = external controller release -> device blocked
Ramp status messages
• rF0 = ramp ended correctly
• rF1 = ramp aborted and ramped down in a controlled man-
ner
• rF2 = band alarm occurred during operation
• rF3 = ramp aborted
The ramp status is indicated by a ashing display alternating
with parameter "P01" (3 seconds "P01", 1 second "rFx"). You
can return to the normal display by pressing the "P" key.
PARAMETERS AND THEIR MEANING
The factory settings are specied in [..].
Parameter meaning and range
P01
Input variable X1
Display only, resolution: °C
P02
Input variable X2
Display only, resolution: °C
P03
Reference variable
Display only, resolution: °C
P04
Current display
Only display, resolution: 0.1A
P05
Output level on the propor-
tional controller / continuous
controller
Only display, resolution: %
P06
Time unit on the proportional
controller
Display only, resolution: sec.
P07
Display of the current
Ramp phase
Display only, resolution:
without unit
P08
Display of the remaining time
of the current ramp phase /
PWM phase
Display only, resolution: 0.1
min.
P10
Control setpoint W1 [°C] Range P13...P14, [5°C]
P11
Switching hysteresis Range 0...10K, [2K]
P12
min standstill time hybrid
Relay range 0...30 min,
[0 min], resolution: 0.1 min
P13
Highest settable setpoint 1 Range P14...950°C, [950°C]
P14
Smallest adjustable setpoint 1 Range -50°C...P13, [-50°C]
P15
Sensor correction X1 Range -30...10K, [0K]
P16
Overtemperature alarm 1 Range P17...999°C, [999°C]
P17
Low temperature alarm 1 Range -99°C...P16, [-99°C]
P18
Lower analog scaling value
(0/2V, 0/4mA)
Range -50°C...P19, [0°C]

www.eltherm.com
8
operation manual
temperature contoller ELTC-MV2
BU 123
Revision 1
Parameter meaning and range
P19
Upper analog scaling value
(10V, 20mA)
Range P18...999°C, [100°C]
P20
Control setpoint W2 [°C] Range P23...P24, [5°C]
P23
Highest settable setpoint 2 Range P24...950°C, [950°C]
P24
Smallest adjustable setpoint 2 Range -50°C...P23, [-50°C]
P25
Sensor correction X2 Range -30...10K, [0K]
P26
Over temperature alarm 2 Range P27...999°C, [999°C]
P27
Low temperature alarm 2 Range -99°C...P16, [-99°C]
P28
Current monitoring load output Range oFF (=0)...1, [oFF]
P32
Low temperature alarm delay
during operation
Range 0...99 min., [0 min]
P33
Delay under temperature alarm
after switching on
Range 0...500 min., [0 min.]
P40
Power correction Range 65...130%, [100%]
P41
Minimum ambient temperature Range -70°C...P10, [-30°C]
P42
Material selection
[1] = metal
2 = plastic
P43
Insulation material range
Range 1...15, [6] see table
on page 9
P44
Thickness of insulation material
Range 1...59, [6] see table
on page 9
P45
Medium selection
Range 1...5, [2] see table on
page 10
P46
Geometry
[0] = pipe
1 = container
P47
Metal pipe outer diameter
Range 1...32, [11] see table
on page 10
P48
Plastic pipe outer diameter
Range 1...17, [3] see table
on page 10
Parameter meaning and range
P49
Cooling times
[0] = calculated by para-
meters P41…P48
1 = TU 30 seconds
2 = TU 60 seconds
3 = TU 120 seconds
P50
Start value setpoint ramp
Range noP (=-1)...950°C,
[100°C]
P51
Ramp 1 duration
Range 1...999 min., [30
min.]
P52
Ramp 1 setpoint
Range noP (=-1)...950°C,
[100°C]
P53
Ramp 2 duration
Range 1...999 min., [30
min.]
P54
Ramp 2 setpoint
Range noP (=-1)...950°C,
[100°C]
P55
Ramp 3 duration
Range 1...999 min., [30
min.]
P56
Ramp 3 setpoint
Range noP (=-1)...950°C,
[100°C]
P57
Ramp 4 duration
Range 1...999 min., [30
min.]
P58
Ramp 4 setpoint
Range noP (=-1)...950°C,
[100°C]
P59
Ramp 5 duration
Range 1...999 min., [30
min.]
P60
Ramp 5 setpoint
Range noP (=-1)...950°C,
[100°C]
P61
Ramp 6 duration
Range 1...999 min., [30
min.]
P62
Ramp 6 setpoint
Range noP (=-1)...950°C,
[100°C]
P63
Ramp 7 duration
Range 1...999 min., [30
min.]
P64
Ramp 7 setpoint
Range noP (=-1)...950°C,
[100°C]
P65
Ramp 8 duration
Range 1...999 min., [30
min.]
P66
Ramp 9 setpoint
Range noP (=-1)...950°C,
[100°C]
P67
Ramp 9 duration
Range 1...999 min., [30
min.]

9
www.eltherm.com 9
www.eltherm.com
Parameter meaning and range
P68
Ramp setpoint 9 (nal value)
Range noP (=-1)...950°C,
[100°C]
P69
Band alarm hysteresis Range P11...11K, [5]
P75
Switching 0/4-20mA or 0/2-10V
0 = 0...20mA, 0...10V
[1] = 4...20mA, 2...10V
P76
min. output signal analogue
output
Range 0%...P77, [0%]
P77
max. output signal analogue
output
Range P76...100%, [100%]
P80
Baud rate (SCADA interface)
1 = 9600 baud
[2] = 19200 baud
3 = 38400 baud
P81
Device address (SCADA and
system interface)
Range 0 (=disabled)...247,
[1]
P82
Status network (SCADA inter-
face)
Range 0...999 sec.,
display of the last telegram
P83
SCADA mode N / A
P84
SCADA setting N / A
P44: Thickness insulation material
1 4,76 mm 3/16" 31 45 mm 1 3/4"
2 5 mm 1/5" 32 50 mm -
3 6,25 mm 1/4" 33 51 mm 2"
4 7 mm - 34 57 mm 2 1/4"
5 8 mm 5/16" 35 60 mm -
6 9 mm 5/16" 36 64 mm 2 1/2"
7 9,5 mm 3/8" 37 70 mm 2 3/4"
8 10 mm 2/5" 38 76 mm 3"
9 11 mm 7/16" 39 80 mm 3 1/4"
10 12 mm - 40 83 mm -
11 12,7 mm 1/2" 41 89 mm 3 1/2"
12 13 mm - 42 90 mm -
13 14 mm - 43 95 mm 3 3/4"
14 14,3 mm 9/16" 44 100 mm 4"
15 15 mm 3/5" 45 110 mm -
16 16 mm 5/8" 46 114 mm 4 1/2"
17 17 mm - 47 120 mm -
18 17,5 mm 11/16" 48 127 mm 5"
19 18 mm - 49 130 mm -
20 19 mm 3/4" 50 140 mm 5 1/2"
21 20 mm - 51 150 mm -
22 23,32 mm 4/5" 52 153 mm 6"
23 22 mm 7/8" 53 160 mm -
24 24 mm 15/16" 54 165 mm 6 1/2"
25 25 mm 1" 55 170 mm -
26 30 mm - 56 178 mm 7"
27 32 mm 1 1/4" 57 180 mm -
28 35 mm - 58 190 mm 7 1/2"
29 38 mm 1 1/2" 59 200 mm 8"
Parameter content for refined control according to
ambient temperature
P43: Insulating material W/(m²*K) at 20°C
1 Calcium silicate, low density 0,08
2 Calcium silicate moldings 0,21
3 Elastomeric foam 0,033
4 Elastomeric foam high temp. 0,038
5 Foam glass 0,038
6 Foam glass ASTM C552-88 0,052
7 Mineral wool 035 0,035
8 Mineral wool 040 0,04
P43: Insulating material W/(m²*K) at 20°C
9 Mineral wool ASTM C547-77 0,035
10 Mineral wool ASTM C553-70 0,04
11 Mineral wool BS3958 0,036
12 Perlite expanded ASTM C610-
85 0,067
13 Perlite 0,067
14 PIR-hard foam 0,027
15 PUR-hard foam 0,023

www.eltherm.com
10
operation manual
temperature contoller ELTC-MV2
BU 123
Revision 1
STRUCTURE SWITCHES AND THEIR MEANING
There are 9 structure switches (S01 to S09) with a dierent
number of switch positions. Each structure switch is assigned
a function with at least two or more alternatives, which are
selected using only one possible switch position per structure
switch.
P45: Medium-selection
1 Water, brine, caustic soda
2 Water-based liquid, acids, alkalis
3 Liquid hydrocarbons, vegetable oils
4 Gases
5 Other
P47: Metal pipe size
1 3 mm 1/8" 17 200 mm 8"
2 6 mm 1/4" 18 225 mm 9"
3 10 mm 3/8" 19 250 mm 10"
4 15 mm 1/2" 20 300 mm 12"
5 20 mm 3/4" 21 350 mm 14"
6 25 mm 1" 22 400 mm 16"
7 32 mm 1 1/4" 23 450 mm 18"
8 40 mm 1 1/2" 24 500 mm 20"
9 50 mm 2" 25 550 mm 22"
10 65 mm 2 1/2" 26 600 mm 24"
11 80 mm 3" 27 650 mm 26"
12 90 mm 3 1/2" 28 700 mm 28"
13 100 mm 4" 29 750 mm 30"
14 125 mm 5" 30 800 mm 32"
15 150 mm 6" 31 850 mm 34"
16 175 mm 7" 32 900 mm 36"
P48: Plastic pipe size
1 10 mm 3/8" 10 75 mm 2 7/8"
2 12 mm 3/8+" 11 100 mm 4"
3 15 mm 1/2" 12 125 mm 5"
4 20 mm 3/4" 13 150 mm 6"
5 25 mm 1" 14 200 mm 8"
6 32 mm 1 1/4" 15 250 mm 10"
7 40 mm 1 1/2" 16 300 mm 12"
8 50 mm 2" 17 400 mm 16"
9 65 mm 2 1/2"
no. meaning
S01
Selection actual value
X1
[1] = Pt100, 3-wire (AE1)
2 = Pt100, 2-wire (AE1)
3 = Thermocouple type J (AE1)
4 = Thermocouple type K (AE1)
5 = Voltage input (AE3)
6 = Current input (AE3)
S02
Selection actual value
X2
[0] = Input disabled
1 = Pt100, 3-wire (AE2)
2 = Pt100, 2-wire (AE2)
3 = Thermocouple type J (AE2)
4 = Thermocouple type K (AE2)
5 = Voltage input (AE4)
6 = Current input (AE4)
S03
Select setpoint W
[1] = Fixed value W1
2 = Fixed value W2
3 = Ramp function
4 = Sliding setpoint (W2+X2)
5 = External setpoint (AE4)
6 = Changeover W1/W2 (DigIn 3)
S04
Selection of output
function controller
[1] = two-point control
2 = pulse width modulation (PWM)
3 = proportional control
4 = continuous control
5 = limiter
S05
Selection switching
output
[1] = internal hybrid relay with soft
start
2 = external power contactor
3 = analog output clocked
S06
Alarm selection:
temperature absolute
– relative
[1] = absolute
2 = relative
S07
Select controller
release (DigIn1)
[1] = continuously
2 = external
S08
Alarm relay mode
1 = alarm relay on in case of error
[2] = alarm relay o on error
3 = enable relay mode
4 = like 0, but heating on
5 = like 1, but heating on
6 = like 2, but heating on
S09
Selection of display
format
[1] = °C
2 = °F

11
www.eltherm.com 11
www.eltherm.com
MODBUS INTERFACES
System interface
Type: RS485 (Physical Layer)
Baud rate: 19200 Baud
Protocol: N,8,2 / ModBus
number of devices: max. 32
SCADA interface
Type: RS485 (Physical Layer)
Baud rate: max. 38400 Baud
Protocol: N,8,2 / ModBus
number of devices: max. 1
Read discrete inputs
Function = 0x02
Address = 0
QTY = 48
Read device ID
Function = 0x2B Object ID 00: eltherm GmbH
Address = 0x0E Object ID 01: ELTC-52
ID Code = 0x01 Object ID 02: Rev01, Bxxx
Object ID = 0x00
ModBus parameters
Bit 0 Bit 1 Bit 2
Hybrid relay Alarm relay OT relay
Bit 3 Bit 4 Bit 5
softstart U/I output 1 Digit In 1
Bit 6 Bit 7 Bit 8
Digit In 2 Digit In 3 Alarm: X1 High-
temp.
Bit 9 Bit 10 Bit 11
Alarm: X1 Low-
temp.
Alarm: X2 High-
temp.
Alarm: X2 Low-
temp.
Bit 12 Bit 13 Bit 14
Alarm: Heating-
cable - -
Bit 15 Bit 16 Bit 17
-State: X1 Pre High-
temp.
State: X1 Pre Low-
temp.
Bit 18 Bit 19 Bit 20
State: X2 Pre High-
temp.
State: X2 Pre Low-
temp
State: External o
mode
Bit 21 Bit 22 Bit 23
State: External SP2
mode - -
Bit 24 Bit 25 Bit 26
E01: AE1 short E02: AE1 open E03: AE1 3wire
Bit 27 Bit 28 Bit 29
E04: AE2 short E05: AE2 open E06: AE2 3wire
Bit 30 Bit 31 Bit 32
E07: AE3 input E08: AE4 input E09: Hybrid open
Bit 33 Bit 34 Bit 35
E10: Hybrid short E11: Limiter active E12: Mains supply
Bit 36 Bit 37 Bit 38
---
Bit 39 Bit 40 Bit 41
E19: internal Ramp: started Ramp: pause
Bit 42 Bit 43 Bit 44
Ramp: powerdown - Ramp: Cycle na-
lized
Bit 45 Bit 46 Bit 47
Ramp: Controlled
stopped Ramp: Temp. Alarm Ramp: Uncontrol-
led stopped

www.eltherm.com
12
operation manual
temperature contoller ELTC-MV2
BU 123
Revision 1
SETPOINT CONTROLLER W1
Setpoint controller (W1) 2-point
The actual value x is recorded via a temperature sensor or a
standard signal and converted into a digital signal. Before this
signal is sent to the controller, the actual value is corrected.
The corrected actual value is shown on the display.
The setpoint w is set on the controller and shown on the
display.
A hysteresis h can be set on the controller.
The control dierence xd= (w - h) -x is formed in the control-
ler.
Hybrid relay K1 (2-point)
If the control dierence is xd< 0 , the hybrid relay opens.
If the control dierence is xd ≥ 0 , the hybrid relay closes.
Control of an external SSR relay (2-point)
The external SSR relay is switched via a voltage signal from the
controller.
If the control dierence is xd< 0 , a 0/2V signal is sent to the
output and the SSR relay switches o.
If the control dierence is xd ≥ 0 , a 10V signal is given to the
output and the SSR relay switches on.
Control of an external power contactor (2-point)
The external power contactor is switched via the controller's
safety relay.
A hysteresis h can be set on the controller.
If the control dierence is xd< 0 , the safety relay opens and
the external power contactor switches o.
If the control dierence is xd ≥ 0 , the safety relay closes and
the external power contactor switches on.
Structure switch settings
No. description selection option
S01 Selection actual
value X1
[1] = Pt100, 3-wire (AE1)
2 = Pt100, 2-wire (AE1)
3 = thermocouple type J (AE1)
4 = thermocouple type K (AE1)
5 = voltage input (AE3)
6 = current input (AE3)
S03 Select setpoint W [1] = Fixed value W1
S04 Selection of output
function controller [1] = two-point control
S05 Selection swit-
ching output
[1] = internal hybrid relay with
soft start
2 = external power contactor
3 = analog output clocked
Parameters used
No. description factory set-
ting
Own
setting
P01 Input variable X1 Display only
P03
Reference variable W
Display only
P04 Current display Display only
P10 Control setpoint 1 (=W1) 5
P11 Switching hysteresis 2
P12 min. standstill time K1 0
P13 largest adjustable setpo-
int 1 950
P14 smallest adjustable
setpoint 1 -50
P15 sensor correction 1 0
P16 Over temperature alarm 1 999
P17 low temperature alarm 1 -99
P18 Lower analog scaling
value 0
P19 Upper analog scaling
value 100
P28 power monitoring
load output 0
P75 Low level mode analog
inputs/outputs 0
FUNCTIONAL DESCRIPTIONS

13
www.eltherm.com 13
www.eltherm.com
Setpoint controller (W1) PWM
The actual value x is recorded via a temperature sensor or a
standard signal and converted into a digital signal. Before this
signal is sent to the controller, the actual value is corrected.
The corrected actual value is shown on the display.
The setpoint w is set on the controller and shown on the
display.
The hysteresis h is set on the controller and indicates the
range in which the controller clocks.
The control dierence xd= w - x is formed in the controller.
Hybrid relay K1 (PWM)
If the control dierence is xd ≤ h , the hybrid relay clocks.
If the control dierence is xd > h , the hybrid relay remains
permanently closed.
If the control dierence is xd < 0 , the hybrid relay remains
open.
Control of an external SSR relay (PWM)
The external SSR relay is switched via a voltage signal from the
controller.
If the control dierence is xd ≤ h , the analogue output and the
SSR relay clocks.
If the control dierence is xd > h , a 10V signal is sent to the
output and the SSR relay switches on.
If the control dierence is xd < 0 , a signal with 0/2V is sent to
the output and the SSR relay switches o.
Control of an external power contactor (PWM)
The external power contactor is switched via the controller's
safety relay.
If the control dierence is xd ≤ h , the safety relay clocks.
If the control dierence is xd > h , the safety relay remains
permanently closed.
If the control dierence is xd < 0 , the safety relay remains
open.
Structure switch settings
No. description selection option
S01 Selection actual
value X1
[1] = Pt100, 3-wire (AE1)
2 = Pt100, 2-wire (AE1)
3 = thermocouple type J (AE1)
4 = thermocouple type K (AE1)
5 = voltage input (AE3)
6 = current input (AE3)
S03 Select setpoint W [1] = Fixed value W1
S04 Selection of output
function controller 2 = PWM
S05 Selection swit-
ching output
[1] = internal hybrid relay with
soft start
2 = external power contactor
3 = analog output clocked
Parameters used
No. description factory
setting
Own
setting
P01 Input variable X1 Display only
P03
Reference variable W
Display only
P04 Current display Display only
P10 Control setpoint 1 (=W1) 5
P11 Switching hysteresis 2
P12 min. standstill time K1 0
P13 largest adjustable setpoint 1 950
P14 smallest adjustable setpoint 1 -50
P15 sensor correction 1 0
P16 Over temperature alarm 1 999
P17 low temperature alarm 1 -99
P18 Lower analog scaling value 0
P19 Upper analog scaling value 100
Parameters used
No. description factory
setting
Own
setting
P28 power monitoring
load output 0
P75 Low level mode analog inputs/
outputs 0

www.eltherm.com
14
operation manual
temperature contoller ELTC-MV2
BU 123
Revision 1
Setpoint controller (W1) proportional control accor-
ding to ambient temperature
The actual value x is recorded via a temperature sensor or a
standard signal and converted into a digital signal. Before this
signal is sent to the controller, the actual value is corrected.
The corrected actual value is shown on the display.
The setpoint w is set on the controller and shown on the
display.
At ambient temperatures in between, the controller runs in
cycle mode.
The time unit is dened via P49, with the parameters P42 to
P48 being included in the calculation in the rened operating
mode. During operation, the TU is continuously calculated
and adjusted to the current eviromental conditions.
Parameters used
No. description factory
setting
Own
setting
P16 Over temperature alarm 1 999
P17 low temperature alarm 1 -99
P18 Lower analog scaling value 0
P19 Upper analog scaling value 100
P28 power monitoring
load output 0
P40 power correction [%] 10
P41 min. ambient temperature -30
P42 material selection 1
P43 insulation material 6
P44 thickness insulation material 6
P45 medium selection 2
P46 geometry 0
P47 pipe outer diameter metal 11
P48 pipe outer diameter plastic 3
P49 cooling times 0
P75 Low Level mode analog inputs/
outputs 0
Hybrid relay K1 (proportional control)
The load contact is open at ambient temperatures above the
setpoint (P10).
At ambient tempatures below the entered minimum ambient
temperature (P41) + 1/6 of the dierence between the set-
point (maintaining temperature) and the minimum ambient
temperature, the load contact is closed.
Control of an external SSR relay (proportional control)
The external SSR relay is switched via a voltage signal from the
controller.
If the ambient temperature is above the set setpoint (P10), the
analogue output emits a signal of 0/2V.
At ambient temperature below the entered minimum
ambient temperature (P41) + 1/6 of the dierence between
the setpoint (maintaining temperature) and the minimum
ambient temoerature, the analog output emits a signal of 10V.
Control of an external power contactor (proportional
control)
The load contact is open at ambient temperatures above the
setpoint (P10)
At ambient tempatures below the entered minimum ambient
temperature (P41) + 1/6 of the dierence between the set-
point (maintaining temperature) and the minimum ambient
temperature, the load contact is closed.
Structure switch settings
No. description selection option
S01 Selection actual
value X1
[1] = Pt100, 3-wire (AE1)
2 = Pt100, 2-wire (AE1)
3 = thermocouple type J (AE1)
4 = thermocouple type K (AE1)
5 = voltage input (AE3)
6 = current input (AE3)
S03 Select setpoint W [1] = Fixed value W1
S04 Selection of output
function controller
3 = Proportional control after
ambient temperature
S05 Selection switching
output
[1] = internal hybrid relay with
soft start
2 = external power contactor
3 = analog output clocked
Parameters used
No. description factory
setting
Own
setting
P01 Input variable X1 Display only
P03
Reference variable W
Display only
P04 Current display Display only
P05 output level at the proportional
controller/ steady controller Display only
P06 time unit on the proportional
controller Display only
P10 Control setpoint 1 (=W1) 5
P12 min. standstill time K1 0
P13 largest adjustable setpoint 1 950
P14 smallest adjustable setpoint 1 -50
P15 sensor correction 1 0

15
www.eltherm.com 15
www.eltherm.com
Setpoint controller (W1) with continuous output
The actual value x is recorded via a temperature sensor or a
standard signal and converted into a digital signal. Before this
signal is sent to the controller, the actual value is corrected.
The corrected actual value is shown on the display.
The setpoint w is set on the controller and shown on the
display.
The size of the output signal can be limited by a minimum
and maximum value on the controller.
The hysteresis h is set on the controller. When controlling with
a continuous output, the hysteresis indicates the range in
which the output signal varies between 0/4mA and 20mA or
0/2V and 10V.
The control dierence xd= w - x is formed in the controller..
If the control dierence is xd < h, the output emits a signal up
to 20mA or 10V.
If the control dierence is xd ≥ h, the output emits a signal of
20mA or 10V.
If the control dierence is xd < 0, the output emits a signal of
0/4mA or 0/2V.
Structure switch settings
No. description selection option
S01 Selection actual
value X1
[1] = Pt100, 3-wire (AE1)
2 = Pt100, 2-wire (AE1)
3 = thermocouple type J (AE1)
4 = thermocouple type K (AE1)
5 = voltage input (AE3)
6 = current input (AE3)
S03 Select setpoint W [1] = Fixed value W1
S04 Selection of output
function controller 4 = continuous control
S05 Selection swit-
ching output 3 = analog output clocked
Parameters used
No. description factory
setting
Own
setting
P01 Input variable X1 Display only
P03
Reference variable W
Display only
P04 Current display Display only
P05 output level at the proportional
controller/ steady controller Display only
P10 Control setpoint 1 (=W1) 5
P11 Switching hysteresis 2
P12 min. standstill time K1 0
P13 largest adjustable setpoint 1 950
P14 smallest adjustable setpoint 1 -50
P15 sensor correction 1 0
P16 Over temperature alarm 1 999
P17 low temperature alarm 1 -99
P18 Lower analog scaling value 0
P19 Upper analog scaling value 100
P28 power monitoring
load output 0
P75 Low Level mode analog in-
puts/ outputs 0
P76 min. output signal analogue
output 0
P77 max. output signal analogue
output 100

www.eltherm.com
16
operation manual
temperature contoller ELTC-MV2
BU 123
Revision 1
RAMP MODE
Ramp start
Press button„ “ for >5 seconds, LED„2“ lights up continuous-
ly.
If the actual value is below the value stored for P50 (= start
value), this value (P50) is initially heated up (in two-point con-
trol). After reaching the start value, the stored ramp function
(P51 to P68) is started.
If the actual value is abovw the start value stored for P50, the
stored ramp function starts immediately.
After reaching the lsat stored ram value, LED "2" goes out and
the set temperature setpoint "P10" is approached (in two-po-
int control) and maintained permanently.
Pause
Press button„ “ for >5 seconds, LED„2“ ashes at a regular
rate. Current temperature is maintained permanently. By pres-
sing the button„ “ again for >5 seconds the ramp continues.
Abort the ramp in a controlled manner
Press button„ “ and„ “ simultaneously for >5 seconds, LED
„2“ ashes alternately long / short. Starting from the current
temperature, the ramp is ramped down with the next smaller
ramp value. After reaching the smallest ramp value, LED "2"
goes out. The set temperature setpoint "P10" is then appro-
ached and maintained permanently.
Cancel ram immediately
Press button„ “ and„ “ simultaneously for >5 seconds, LED
„2“ ashes alternately long / short. Press button„ “ and„ “
simultaneously again for >5 seconds, LED„2“ goes out.
The ramp function is now inactive, the set temperature setpo-
int "P10" is then approached and maintained permanently.
Ramp mode 2-point
The actual value x is recorded via a temperature sensor or a
standard signal and converted into a digital signal.
Before this signal is sent to the controller, the actual value is
corrected. The corrected actual value is shown on the display.
The setpoints w1 to w9 and the associated running times t1
to t9 are set on the controller. The current ramp phase, the
current setpoint and the remaining run time of the ramp
section can be shown on the display.
A hysteresis h can be set on the controller.
In the controller, the control dierence is formed with the
current setpoint xdi = (wi- h) - x
Structure switch settings
No. description selection option
S01 Selection actual
value X1
[1] = Pt100, 3-wire (AE1)
2 = Pt100, 2-wire (AE1)
3 = thermocouple type J (AE1)
4 = thermocouple type K (AE1)
5 = voltage input (AE3)
6 = current input (AE3)
S03 Select setpoint W 3 = ramp function
S04 Selection of output
function controller [1] = two-point control
S05 Selection swit-
ching output
[1] = internal hybrid relay with
soft start
2 = external power contactor
3 = analog output clocked

17
www.eltherm.com 17
www.eltherm.com
Parameters used
No. description factory
setting
Own
setting
P68 Ramp 9 setpoint 100
P69 band alarm hysteresis 5
P75 Low Level mode analog inputs/
outputs 0
Hybrid relay K1 (2-point)
If the control dierence is xdi < 0 , the hybrid relay opens.
If the control dierence is xdi ≥ 0 , the hybrid relay closes.
Control of an external SSR relay (2-point)
The external SSR relay is switched via a voltage signal from the
controller.
If the control dierence is xdi < 0 , a 0/2V signal is sent to the
output and the SSR relay switches o.
If the control dierence is xdi ≥ 0 , a 10V signal is given to the
output and the SSR relay switches on.
Control of an external power contactor (2-point)
The external power contactor is switched via the controller's
safety relay.
If the control dierence is xdi < 0 , the safety relay opens and
the external power contactor switches o.
If the control dierence is xdi ≥ 0 , the safety relay closes and
the external power contactor switches on.
Parameters used
No. description factory
setting
Own
setting
P01 input variable 1 (X1) Display only
P03 reference variable (W) Display only
P04 current display Display only
P07 current ramp phase Display only
P08 remaining time ramp phase Display only
P10 control setpoint 1 (= W1) 5
P11 switching hysteresis 1 2
P15 sensor correction 1 0
P16 over temperature alarm 1 999
P17 low temperature alarm 1 -99
P18 Lower analog scaling value 0
P19 Upper analog scaling value 100
P28 power monitoring
load output 0
P40 power correction [%] 10
P41 min. ambient temperature -30
P42 material selection 1
P43 insulation material 6
P44 thickness insulation material 6
P45 medium selection 2
P46 geometry 0
P47 pipe outer diameter metal 11
P48 pipe outer diameter plastic 3
P49 cooling times 0
P50 start value 100
P51 Ramp 1 duration 30
P52 Ramp 1 setpoint 100
P53 Ramp 2 duration 30
P54 Ramp 2 setpoint 100
P55 Ramp 3 duration 30
P56 Ramp 3 setpoint 100
P57 Ramp 4 duration 30
P58 Ramp 4 setpoint 100
P59 Ramp 5 duration 30
P60 Ramp 5 setpoint 100
P61 Ramp 6 duration 30
P62 Ramp 6 setpoint 100
P63 Ramp 7 duration 30
P64 Ramp 7 setpoint 100
P65 Ramp 8 duration 30
P66 Ramp 8 setpoint 100
P67 Ramp 9 duration 30

www.eltherm.com
18
operation manual
temperature contoller ELTC-MV2
BU 123
Revision 1
Ramp mode PWM
The actual value x is recorded via a temperature sensor or a
standard signal and converted into a digital signal. Before this
signal is sent to the controller, the actual value is corrected.
The corrected actual value is shown on the display
The setpoints w1 to w9 and the associated running times t1
to t9 are set on the controller. The current ramp phase, the
current setpoint and the remaining run time of the ramp
section can be shown on the display.
The hysteresis h is set on the controller and species the ran-
ge in which the controller clocks.
In the controller the control dierence is formed with the
current setpoint xdi = wi- x
Parameters used
No. description factory
setting
Own
setting
P28 power monitoring
load output 0
P40 power correction [%] 10
P41 min. ambient temperature -30
P42 material selection 1
P43 insulation material 6
P44 thickness insulation material 6
P45 medium selection 2
P46 geometry 0
P47 pipe outer diameter metal 11
P48 pipe outer diameter plastic 3
P49 cooling times 0
P50 start value 100
P51 Ramp 1 duration 30
P52 Ramp 1 setpoint 100
P53 Ramp 2 duration 30
P54 Ramp 2 setpoint 100
P55 Ramp 3 duration 30
P56 Ramp 3 setpoint 100
P57 Ramp 4 duration 30
P58 Ramp 4 setpoint 100
P59 Ramp 5 duration 30
P60 Ramp 5 setpoint 100
P61 Ramp 6 duration 30
P62 Ramp 6 setpoint 100
P63 Ramp 7 duration 30
P64 Ramp 7 setpoint 100
P65 Ramp 8 duration 30
P66 Ramp 8 setpoint 100
P67 Ramp 9 duration 30
P68 Ramp 9 setpoint 100
P69 band alarm hysteresis 5
P75 Low Level mode analog inputs/
outputs 0
Structure switch settings
No. description selection option
S01 Selection actual
value X1
[1] = Pt100, 3-wire (AE1)
2 = Pt100, 2-wire (AE1)
3 = thermocouple type J (AE1)
4 = thermocouple type K (AE1)
5 = voltage input (AE3)
6 = current input (AE3)
S03 Select setpoint W 3 = ramp function
S04 Selection of output
function controller 2 = PWM
S05 Selection swit-
ching output
[1] = internal hybrid relay with
soft start
2 = external power contactor
3 = analog output clocked
Parameters used
No. description factory
setting
Own
setting
P01 input variable 1 (X1) Display only
P03 reference variable (W) Display only
P04 current display Display only
P07 current ramp phase Display only
P08 remaining time ramp phase Display only
P10 control setpoint 1 (= W1) 5
P11 switching hysteresis 1 2
P15 sensor correction 1 0
P16 over temperature alarm 1 999
P17 low temperature alarm 1 -99
P18 Lower analog scaling value 0
P19 Upper analog scaling value 100

19
www.eltherm.com 19
www.eltherm.com
Hybrid relay K1 (PWM)
If the control dierence is xdi ≤ h, the hybrid relay clocks.
If the control dierence is xdi > h, he hybrid relay remains
permanently closed.
If the control dierence is xdi < 0, the hybrid relay remains
open.
Control of an external SSR relay (PWM)
The external SSR relay is switched via a voltage signal from the
controller.
If the control dierence is xdi ≤ h, the analogue output and
the SSR relay clocks.
If the control dierence is xdi > h, a 10V signal is sent to the
output and the SSR relay switches on.
If the control dierence is xdi < 0, a signal with 0/2V is sent to
the output and the SSR relay switches o.
Control of an external power contactor (PWM)
The external power contactor is switched via the controller's
safety relay.
If the control dierence is xdi ≤ h, the safety relay clocks.
If the control dierence is xdi > h, he safety relay remains
permanently closed.
If the control dierence is xdi < 0, he safety relay remains
open.

www.eltherm.com
20
operation manual
temperature contoller ELTC-MV2
BU 123
Revision 1
Ramp mode with continuous output
The actual value x is recorded via a temperature sensor or a
standard signal and converted into a digital signal. Before this
signal is sent to the controller, the actual value is corrected.
The corrected actual value is shown on the display.
The setpoints w1 to w9 and the associated running times t1
to t9 are set on the controller. The current ramp phase, the
current setpoint and the remaining run time of the ramp
section can be shown on the display.
The size of the output signal can be limited by a minimum
and maximum value on the controller.
The hysteresis h is set on the controller. When controlling with
a continuous output, the hysteresis indicates the range in
which the output signal varies between 0/4mA and 20mA or
0/2V and 10V.
The control dierence xdi = wi- x is formed with the current
setpoint in the controller.
If the control dierence is xdi < h, he output emits a signal up
to 20mA or 10V.
If the control dierence is xdi ≥ h, he output emits a signal of
20mA or 10V.
If the actual value is above the set setpoint w, the output
emits a signal of 0/4mA or 0/2V.
Parameters used
No. description factory
setting
Own
setting
P10 control setpoint 1 (= W1) 5
P11 switching hysteresis 1 2
P15 sensor correction 1 0
P16 over temperature alarm 1 999
P17 low temperature alarm 1 -99
P18 Lower analog scaling value 0
P19 Upper analog scaling value 100
P28 power monitoring
load output 0
P50 start value 100
P51 Ramp 1 duration 30
P52 Ramp 1 setpoint 100
P53 Ramp 2 duration 30
P54 Ramp 2 setpoint 100
P55 Ramp 3 duration 30
P56 Ramp 3 setpoint 100
P57 Ramp 4 duration 30
P58 Ramp 4 setpoint 100
P59 Ramp 5 duration 30
P60 Ramp 5 setpoint 100
P61 Ramp 6 duration 30
P62 Ramp 6 setpoint 100
P63 Ramp 7 duration 30
P64 Ramp 7 setpoint 100
P65 Ramp 8 duration 30
P66 Ramp 8 setpoint 100
P67 Ramp 9 duration 30
P68 Ramp 9 setpoint 100
P69 band alarm hysteresis 5
P75 Low Level mode analog inputs/
outputs 0
P76 min. output signal analogue
output 0
P77 max. output signal analogue
output 100
Structure switch settings
No. description selection option
S01 Selection actual
value X1
[1] = Pt100, 3-wire (AE1)
2 = Pt100, 2-wire (AE1)
3 = thermocouple type J (AE1)
4 = thermocouple type K (AE1)
5 = voltage input (AE3)
6 = current input (AE3)
S03 Select setpoint W 3 = ramp function
S04 Selection of output
function controller 4 = continuous control
S05 Selection swit-
ching output 3 = analog output clocked
Parameters used
No. description factory
setting
Own
setting
P01 input variable 1 (X1) Display only
P03 reference variable (W) Display only
P04 current display Display only
P07 current ramp phase Display only
P08 remaining time ramp phase Nur Anzeige
Table of contents
Other eltherm Controllers manuals
Popular Controllers manuals by other brands

Loctite
Loctite Single CureJet Operation manual

Parrot
Parrot Cockpitglasses quick start guide

Micronix
Micronix MPA-20 series Reference manual

Acer
Acer AcerAltos 3102RS user guide

Ruckus Wireless
Ruckus Wireless ZoneDirector 1100 Configuration guide

thomann
thomann Stairville LED Pixel Rail Drive640 MKII user manual