Application Engineering
B U L L E T I N
AE4-1374 R1
heater should be installed as low on the compressor
shell as possible, below the lower bearing pin welds that
protrude from the compressor shell. Ideally the heater
would come together for clamping with the vertical
shell seam weld coming up through the area where the
crankcase heater is clamped together. See Figure 6
for details. Tighten the clamp screw carefully, ensuring
that the heater is uniformly tensioned along its entire
length and that the heating element is in complete
contact with the compressor shell. It's important that
the clamp screw is torqued to the range of 20-25 in-lb
(2.3-8 N m) to ensure adequate contact and to prevent
heater burnout. Never apply power to the heater in free
air or before the heater is installed on the compressor
to prevent overheating and burnout.
Crankcase Heat - Three Phase
A crankcase heater is required for three-phase
compressors when the system charge exceeds the
compressor charge limit listed in Table
4 and an
accumulator cannot be piped to provide free liquid
drainage duringtheoff cycle (SeeFigure2 and Table5).
Pump Down Cycle
A pump down cycle for control of refrigerant migration
is not recommended for scroll compressors of this
size. If a pump down cycle is used, a separate
discharge line check valve must be added. The scroll
compressor’s discharge check valve is designed to stop
extended reverse rotation and prevent high-pressure
gas from leaking rapidly into the low side after shut
off. The check valve will in some cases leak more than
reciprocating compressor discharge reeds, normally
used with pump down, causing the scroll compressor to
recycle more frequently. Repeated short-cycling of this
nature can result in a low oil situation and consequent
damage to the compressor. The low-pressure control
differential has to be reviewed since a relatively large
volume of gas will re-expand from the high side of the
compressor into the low side on shut down. Pressure
control setting: Never set the low pressure control
to shut off outside of the operating envelope. The
exception to this rule is the heat pump as explained
on Page 3. To prevent the compressor from running
into problems during such faults as loss of charge
or partial blockage, the control should not be set
lower than 5 to 10°F (3-6K) equivalent suction
pressure below the lowest design operating point.
Minimum Run Time
There is no set answer to how often scroll compressors
can be started and stopped in an hour, since it is
highly dependent on system configuration. Other
than the considerations in the section on Brief Power
© 2013 Emerson Climate Technologies, Inc.
Printed in the U.S.A.
Interruptions, there is no minimum off time because
Copeland Scroll compressors start unloaded, even
if the system has unbalanced pressures. The most
critical consideration is the minimum run time required
to return oil to the compressor after startup. To establish
the minimum run time, obtain a sample compressor
equipped with a sight tube (available from Emerson)
and install it in a system with the longest connecting
lines that are approved for the system. The minimum
on time becomes the time required for oil lost during
compressor startup to return to the compressor sump
and restore a minimal oil level that will assure oil pick
up through the crankshaft. Cycling the compressor for
a shorter period than this, for instance to maintain very
tight temperature control, will result in progressive loss
of oil and damage to the compressor. See AE17-1262
for more information on preventing compressor short
cycling.
Reversing Valves
Since Copeland Scroll compressors have very high
volumetric efficiency, their displacements are lower
than those of comparable capacity reciprocating
compressors. CAUTION Reversing valve sizing must
be within the guidelines of the valve manufacturer.
Required pressure drop to ensure valve shifting
must be measured throughout the operating range
of the unit and compared to the valve manufacturer's
data. Low ambient heating conditions with low flow
rates and low pressure drop across the valve can
result in a valve not shifting. This can result in a
condition where the compressor appears to be
not pumping (i.e. balanced pressures). It can also
result in elevated compressor sound levels. During
a defrost cycle, when the reversing valve abruptly
changes the refrigerant flow direction, the suction
and discharge pressures will go outside of the normal
operating envelope. The sound that the compressor
makes during this transition period is normal, and the
duration of the sound will depend on the coil volume,
outdoor ambient, and system charge. The preferred
method of mitigating defrost sound is to shut down the
compressor for 20 to 30 seconds when the reversing
valve changes position going into and coming out of
the defrost cycle. This technique allows the system
pressures to reach equilibrium without the compressor
running. The additional start-stop cycles do not exceed
the compressor design limits, but suction and discharge
tubing design should be evaluated.
The reversing valve solenoid should be wired so that the
valve does not reverse when the system is shut off by
the operating thermostat in the heating or cooling mode.
If the valve is allowed to reverse at system shutoff,
suction and discharge pressures are reversed to the
7