Introduction
This installation guide provides instructions for installation,
startup and adjustment. To receive a copy of the
instruction manual, contact your local Sales Office or view
a copy at www.fisher.com. For further information refer to:
67C Series Instruction Manual, D102601X012.
PED Categories
This product may be used as a safety accessory with
pressure equipment in the following Pressure Equipment
Directive categories. It may also be used outside of the
Pressure Equipment Directive using Sound Engineering
Practice (SEP) per table below. For information on the
current PED revision see Bulletin: D103053X012.
PRODUCT SIZE CATEGORIES FLUID TYPE
1/4 NPT SEP 1
Specifications
Body Size and End Connection Style
1/4 NPT
Maximum Inlet Pressure (Body Rating)(1)
67CFS Series: 17.2 bar / 250 psig
67CS Series: 27.6 bar / 400 psig
Maximum Emergency Outlet Pressure(1)
3.4 bar / 50 psig over outlet pressure setting
Proof Test Pressure
All Pressure Retaining Components have been
proof tested per Directive.
Outlet Pressure Ranges(1)
0 to 1.4 bar / 0 to 20 psig
0 to 2.4 bar / 0 to 35 psig
0 to 4.1 bar / 0 to 60 psig
0 to 8.6 bar / 0 to 125 psig
0 to 10.3 bar / 0 to 150 psig
Temperature Capabilities(1)
With Nitrile (NBR)
Standard Bolting: -29 to 82°C / -20 to 180°F
Stainless Steel Bolting: -40 to 82°C / -40 to 180°F
With Fluorocarbon (FKM)
Polyethylene Filter(3) (standard):-18 to 82°C /
0 to 180°F
Stainless steel or Glass Filter (Optional):
-18 to 149°C / 0 to 300°F
With Silicone (VMQ)(2) Diaphragm and Low
Temperature bolting: -51 to 82°C / -60 to 180°F
With Gauges: -40 to 82°C / -40 to 180°F
Installation
▲ WARNING
Only qualied personnel should install
or service a regulator. Regulators should
be installed, operated and maintained
in accordance with international and
applicable codes and regulations and
Emerson Process Management Regulator
Technologies, Inc. instructions.
If the regulator vents uid or a leak
develops in the system, it indicates that
service is required. Failure to take the
regulator out of service immediately may
create a hazardous condition.
Personal injury, equipment damage or
leakage due to escaping uid or bursting
of pressure-containing parts may result
if this regulator is overpressured or
is installed where service conditions
could exceed the limits given in the
Specications section, or where
conditions exceed any ratings of the
adjacent piping or piping connections.
To avoid such injury or damage, provide
pressure-relieving or pressure-limiting
devices (as required by the appropriate
code, regulation or standard) to prevent
service conditions from exceeding limits.
Additionally, physical damage to the
regulator could result in personal injury
and property damage due to escaping
uid. To avoid such injury and damage,
install the regulator in a safe location.
The internal relief valve in the
67CFSR Series regulators does not
provide full overpressure protection. The
internal relief valve is designed for minor
seat leakage only.
Clean out all pipelines before installation of the
regulator and check to be sure the regulator has not
been damaged or has collected foreign material during
shipping. For NPT bodies, apply pipe compound to the
external pipe threads. For anged bodies, use suitable
line gaskets and approved piping and bolting practices.
Install the regulator in any position desired, unless
otherwise specied, but be sure ow through the body
is in the direction indicated by the arrow on the body.
1. The pressure/temperature limits in this installation guide or any applicable standard
limitation should not be exceeded.
2. Silicone (VMQ) is not compatible with hydrocarbon gas.
3. Do not use in high aromatic hydrocarbon service.
67CS and 67CFS Series
Installation Guide
D103097X014