Type HSR
Installation Sheet
D103075X012
June 2019
Introduction
This manual provides instructions for the installation,
startup and adjustment of the Type HSR pressure regulator.
If maintenance is required, refer to the Type HSR
Instruction Manual, form 5753. To receive a copy of the
instruction manual, contact your local Sales Office.
Specifications
Maximum Emergency Inlet Pressures(1)
150 psi / 10.3 bar
Maximum Emergency Outlet (Casing) Pressures(1)
25 psig / 1.72 bar
Outlet Pressure Ranges
4 to 6 in. w.c / 10 to 15 mbar
6 to 8 in. w.c / 15 to 20 mbar
8 to 10 in. w.c / 20 to 25 mbar
10 to 12.5 in. w.c / 25 to 31 mbar
12.5 to 20 in. w.c / 31 to 50 mbar
20 to 35 in. w.c / 50 to 87 mbar
1.25 to 2.2 psig / 0.09 to 0.15 bar
Temperature Capabilities(1)
-20 to 160°F / -29 to 71°C
Installation
!
WARNING
Personal injury, equipment damage or
leakage due to escaping gas or bursting of
pressure-containing parts might result if these
regulators are overpressured or installed
where service conditions could exceed the
limits for which the regulators were designed,
or where conditions exceed any ratings of
the adjacent piping or piping connections.
To avoid such injury or damage, provide
pressure-relieving or pressure-limiting
devices (as required by the appropriate code,
regulation or standard) to prevent service
conditions from exceeding those limits.
Additionally, physical damage to a regulator
could cause personal injury and property
damage due to escaping gas. To avoid such
injury and damage, install the regulator in a
safe location.
A regulator may vent some gas to the
atmosphere in hazardous or flammable gas
service, vented gas might accumulate and
cause personal injury, death or property
damage due to fire or explosion. Vent a
regulator in hazardous gas service to a
remote, safe location away from air intakes or
any hazardous location. The vent line must be
protected against condensation or clogging.
Before installing the regulator, check for damage which might
have occurred in shipment. Also check for dirt or foreign
matter which may have accumulated in the regulator body
or in the pipeline. Apply pipe compound to the male threads
of the pipeline and install the regulator so that the flow is in
the direction of the arrow cast on the side of the body. The
diaphragm actuator assembly can be rotated to any position
relative to the body, in 90° increments. Remove the two
cap screws that hold the body to the actuator in order to
rotate the diaphragm actuator assembly.
Do not install the regulator in a location where there can be
excessive water accumulation, such as directly beneath a
downspout or in an undrained pit.
To obtain the maximum flow capacities or other performance
characteristics, the length of pipe from the regulator outlet
to the meter should have no bends and should be the same
size as the regulator outlet. Replace the regulator if water
gets into the spring case or the lower casing of the regulator.
CAUTION
You are advised to use new vent piping
because defective threads on the relief
vent piping may interfere with the venting
assembly if the piping obstructs the
movement of the vent flapper.
On indoor installations, the vent should be piped outside
the building. Remove the screen from the regulator vent
connection and connect vent piping from that connection
to the outdoors. Install a weather and insect resistant
vent assembly on the outside end of the pipe. Inspect the
vent opening regularly. On some installations, it may be
necessary to install the regulator beneath a protective hood.
The vent should be pointing or sloping down sufficiently
to allow any condensate to drain. Also check the regulator
periodically for external or internal corrosion.
Overpressure Protection
!
WARNING
Some type of overpressure protection is
needed if actual inlet pressure can exceed
the outlet pressure rating. Overpressuring
any portion of this equipment may cause
1. The pressure/temperature limits in this installation sheet and any applicable standard or
code limitation should not be exceeded.
Type HSR
Emerson Automation Solutions
T80573-2A
674
8
16
22
15
27
9
17
23 510 14 25 126
13
12
11
2
3
Americas
McKinney, Texas 75070 USA
T +1 800 558 5853
+1 972 548 3574
Europe
Bologna 40013, Italy
T +39 051 419 0611
Asia Pacic
Singapore 128461, Singapore
T +65 6777 8211
Middle East and Africa
Dubai, United Arab Emirates
T +971 4 811 8100
W[email protected]
Fisher.com
Facebook.com/EmersonAutomationSolutions
LinkedIn.com/company/emerson-automation-solutions
Twitter.com/emr_automation
D103075X012 © 2003, 2019 Emerson Process Management Regulator
Technologies, Inc. All rights reserved. 06/19.
The Emerson logo is a trademark and service mark of Emerson
Electric Co. All other marks are the property of their prospective owners.
Fisher™ is a mark owned by Fisher Controls International LLC, a
business of Emerson Automation Solutions.
The contents of this publication are presented for informational purposes
only, and while every effort has been made to ensure their accuracy,
they are not to be construed as warranties or guarantees, express or
implied, regarding the products or services described herein or their use
or applicability. All sales are governed by our terms and conditions, which
are available upon request. We reserve the right to modify or improve the
designs or specifications of such products at any time without notice.
Emerson Process Management Regulator Technologies, Inc does not
assume responsibility for the selection, use or maintenance of any
product. Responsibility for proper selection, use and maintenance of any
Emerson Process Management Regulator Technologies, Inc. product
remains solely with the purchaser.
damage to regulator parts, leaks in the
regulator or personal injury due to bursting
of pressure-containing parts or explosion
of accumulated gas.
Type HSR regulators provide internal relief that limits the
total outlet pressure buildup over setpoint. This internal relief
may be adequate for the application, if not, provide additional
pressure relief or a pressure-limiting device downstream.
Regulators should be inspected for damage after any
overpressure condition.
!
WARNING
To avoid personal injury or property damage
due to explosion or damage to regulator or
downstream components during startup,
release downstream pressure to prevent an
overpressure condition on the diaphragm of
the regulator.
In order to avoid an overpressure condition
and possible equipment damage, pressure
gauges should always be used to monitor
pressures during startup.
Startup
With proper installation completed, slowly open the
shutoff valve. Check all connections for leaks. Check the
downstream equipment for proper operations.
Adjustment
To increase the outlet pressure setting, turn the adjusting
screw clockwise. To reduce the outlet pressure setting, turn
the adjusting screw counterclockwise. A pressure gauge
should always be used to monitor downstream pressure
while adjustments are being made. Do not adjust the
spring to produce an outlet pressure setting above the limit
identified on the information label. If the required pressure
setting is not within the range of the spring being used,
substitute with the correct spring. When changing the spring,
also change the range identified on the information label
to indicate the actual pressure range of the spring in use.
After the spring adjustment has been completed, replace the
closing cap.
Parts List
Key Description
1 Spring Case Assembly
2 Lower Casing
3 Screen
4 Lever
5 Stem
6 Straight Pin
7 Machine Screw (2 required)
8 Closing Cap
9 Machine Screw (8 required)
10 Relief Valve Spring
11 Diaphragm
Key Description
12 Pusher Post
13 Lower Spring Seat
14 Relief Spring Retainer
15 Body
16 O-ring
17 Cap Screw (2 required)
22 Orifice
23 Disk
25 Spring
26 Adjusting Screw
27 Information Label
Figure 1. Type HSR Regulator Assembly

Other Emerson Controllers manuals

Emerson Bettis RP3E User manual

Emerson

Emerson Bettis RP3E User manual

Emerson PACSystems RX3i Energy Pack User manual

Emerson

Emerson PACSystems RX3i Energy Pack User manual

Emerson FISHER T205B User manual

Emerson

Emerson FISHER T205B User manual

Emerson iPro Series Wiring diagram

Emerson

Emerson iPro Series Wiring diagram

Emerson Spence T61 Series User manual

Emerson

Emerson Spence T61 Series User manual

Emerson EL-O-Matic F-Series User guide

Emerson

Emerson EL-O-Matic F-Series User guide

Emerson Fisher 1098-EGR User manual

Emerson

Emerson Fisher 1098-EGR User manual

Emerson Fisher Type 667 size 80 Manual

Emerson

Emerson Fisher Type 667 size 80 Manual

Emerson Fisher 749B User manual

Emerson

Emerson Fisher 749B User manual

Emerson TESCOM 04 Series Setup guide

Emerson

Emerson TESCOM 04 Series Setup guide

Emerson EL-O-Matic F-Series Installation and operating manual

Emerson

Emerson EL-O-Matic F-Series Installation and operating manual

Emerson VAREC Series Manual

Emerson

Emerson VAREC Series Manual

Emerson Fisher FIELDVUE DLC3020f User manual

Emerson

Emerson Fisher FIELDVUE DLC3020f User manual

Emerson EC2-712 User manual

Emerson

Emerson EC2-712 User manual

Emerson PACSystems RX3i User manual

Emerson

Emerson PACSystems RX3i User manual

Emerson CPHE User manual

Emerson

Emerson CPHE User manual

Emerson Fisher 67C Series User manual

Emerson

Emerson Fisher 67C Series User manual

Emerson TESCOM 44-6800 E Series User manual

Emerson

Emerson TESCOM 44-6800 E Series User manual

Emerson Advantage 2.1 User manual

Emerson

Emerson Advantage 2.1 User manual

Emerson FISHER 657 User manual

Emerson

Emerson FISHER 657 User manual

Emerson KEYSTONE FIGURE 738 Manual

Emerson

Emerson KEYSTONE FIGURE 738 Manual

Emerson Fisher 1052 User manual

Emerson

Emerson Fisher 1052 User manual

Emerson Digitax ST User manual

Emerson

Emerson Digitax ST User manual

Emerson Site Supervisor User manual

Emerson

Emerson Site Supervisor User manual

Popular Controllers manuals by other brands

JNGE Power MPPT user manual

JNGE Power

JNGE Power MPPT user manual

Speck pumpen BADU Eco Touch II quick start guide

Speck pumpen

Speck pumpen BADU Eco Touch II quick start guide

Magnimage LED-F706 user manual

Magnimage

Magnimage LED-F706 user manual

Munters Platinum Touch user manual

Munters

Munters Platinum Touch user manual

4qd pro-150 instruction manual

4qd

4qd pro-150 instruction manual

Elmes Electronic STM-2K quick start guide

Elmes Electronic

Elmes Electronic STM-2K quick start guide

HiModel Fly Series instruction manual

HiModel

HiModel Fly Series instruction manual

CNC UC100 user manual

CNC

CNC UC100 user manual

Unitek BAMO A1 manual

Unitek

Unitek BAMO A1 manual

Burster 9251 PROFINET Series Operation manual

Burster

Burster 9251 PROFINET Series Operation manual

York CCWEB01 Operation manual

York

York CCWEB01 Operation manual

KTE KT-PPC instruction manual

KTE

KTE KT-PPC instruction manual

Spirax Sarco 1600V user manual

Spirax Sarco

Spirax Sarco 1600V user manual

IDTECK Star RFL200 quick guide

IDTECK

IDTECK Star RFL200 quick guide

Rollerdor RD10X2ELL installation guide

Rollerdor

Rollerdor RD10X2ELL installation guide

Brainchild P41 user manual

Brainchild

Brainchild P41 user manual

Savant SmartControl 12 Quick reference guide

Savant

Savant SmartControl 12 Quick reference guide

Emec PH CONTROLLER operating manual

Emec

Emec PH CONTROLLER operating manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.