Quick Start Guide
7
April 2019
Specific Conditions of Use (X):
1. See certificate for ambient temperature range.
2. The non-metallic label may store an electrostatic charge and become a source of
ignition in Group III environments.
3. Guard the LCD display cover against impact energies greater than 4 joules.
4. Flameproof joints are not intended for repair.
5. A suitable certified Ex d or Ex tb enclosure is required to be connected to temperature
probes with Enclosure option "N".
6. Care shall be taken by the end user to ensure that the external surface temperature on
the equipment and the neck of DIN Style Sensor probe does not exceed 130 °C.
7. Non-Standard Paint options may cause risk from electrostatic discharge. Avoid
installations that cause electrostatic build-up on painted surfaces, and only clean the
painted surfaces with a damp cloth. If paint is ordered through a special option code,
contact the manufacturer for more information.
International
E7 IECEx Flameproof
Certificate: IECEx FMG 12.0022X
Standards: IEC 60079-0:2011, 60079-1:2014-06
Markings: Ex db IIC T6…T1 Gb, T6(–50 °C ≤Ta≤+40 °C), T5…T1(–50 °C ≤Ta≤
+60 °C)
Specific Conditions of Use (X):
1. See certificate for ambient temperature range.
2. The non-metallic label may store an electrostatic charge and become a source of
ignition in Group III environments.
3. Guard the LCD display cover against impact energies greater than 4 joules.
4. Flameproof joints are not intended for repair
5. A suitable certified Ex d or Ex tb enclosure is required to be connected to temperature
probes with Enclosure option "N".
6. Care shall be taken by the end user to ensure that the external surface temperature on
the equipment and the neck of DIN Style Sensor probe does not exceed 130 °C.
7. Non-Standard Paint options may cause risk from electrostatic discharge.
Brazil
E2 INMETRO Flameproof
Certificate: UL-BR 13.0535X
Standards: ABNT NBR IEC 60079-0:2013; ABNT NBR IEC 60079-1:2016; ABNT NBR
IEC60079-31:2014
Markings: Ex db IIC T6…T1 Gb T6…T1: (–50 °C ≤Ta≤+40 °C), T5…T1: (–50 °C ≤Ta≤
+60 °C), Ex tb IIIC T130 °C Db (–40 °C ≤Ta≤+70°C )
Special Conditions for Safe Use (X):
1. See certificate for ambient temperature range.
2. The non-metallic label may store an electrostatic charge and become a source of
ignition in Group III environments.
3. Guard the LCD display cover against impact energies greater than 4 joules.
4. A suitable certified Ex d or Ex tb enclosure is required to be connected to temperature
probes with Enclosure option "N".
5. Care shall be taken by the end user to ensure that the external surface temperature on
the equipment and the neck of DIN Style Sensor probe does not exceed 130 °C.
6. Consult the manufacturer if dimensional information on the flameproof joints is
necessary.