manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Emerson
  6. •
  7. Temperature Controllers
  8. •
  9. Emerson dixell XW30VS Wiring diagram

Emerson dixell XW30VS Wiring diagram

1592009730 XW30-35VS GB r1.2 31.07.2015 XW30VS - XW35VS 1/4
XW30VS - XW35VS
Digital controller for normal temperature with
configurable relay
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick
reference.
The instrument shall not be used for purposes different from those described hereunder. It cannot
be used as a safety device.
Check the application limits before proceeding.
Dixell Srl reserves the right to change the composition of its products, even without notice,
ensuring the same and unchanged functionality.
1.2 SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding
sudden temperature changes with high atmospheric humidity to prevent formation of
condensation
Warning: disconnect all electrical connections before any kind of maintenance.
Fit the probe where it is not accessible by the End User. The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell s.r.l.”
(see address) with a detailed description of the fault.
Consider the maximum current which can be applied to each relay (see Technical Data).
Ensure that the wires for probes, loads and the power supply are separated and far enough from
each other, without crossing or intertwining.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in
parallel with inductive loads could be useful.
2. GENERAL DESCRIPTION
Model XW35VS, 100x64 format, is a microprocessor based controllers suitable for applications on
medium or normal temperature refrigerating units.
XW30VS is provided with 3 relay outputs to control compressor, alarm and the lights.
XW35VS is provided with 3 relay outputs to control compressor, evaporator fans and the lights.
It’s also provided with 2 NTC or PTC probe inputs, one for temperature control the second to display
temperature of another point.
An output allows the user to programme the parameter list with the “Hot Key”.
3. CONTROLLING LOADS
3.1 THE COMPRESSOR
The regulation is performed according to the temperature measured by the thermostat probe with a
positive differential from the set point: if the temperature increases and reaches set point plus
differential the compressor is started and then turned off when the temperature reaches the set point
value again.
In case of fault in the thermostat probe the start and stop of the compressor are timed through
parameters “COn” and “COF”.
3.2 FAST FREEZING
When defrost is not in progress, it can be activated the keypad by holding the okey pressed for about
3 seconds. The compressor operates in continuous mode for the time set through the “CCt” parameter.
The cycle can be terminated before the end of the set time using the same activation key, ofor about
3 seconds.
3.3 DEFROST
The defrost interval is control by means of parameter “EdF”: (EdF=in) the defrost is made every “IdF”
time, (EdF=Sd) the interval “IdF” is calculate through Smart Defrost algorithm (only when the
compressor is ON).
Defrost is performed through a simple stop of the compressor. Parameter “IdF” controls the interval
between defrost cycles, while its length is controlled by parameter “MdF”.
3.4 CONTROL OF EVAPORATOR FANS –ONLY FOR XW35VS
The fan control mode is selected by means of the “FnC” parameter:
FnC=C-n fans will switch ON and OFF with the compressor and not run during defrost:;
FnC= O-n fans will run continuously, but not during defrost
After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd” parameter.
FnC=C-y fans will switch ON and OFF with the compressor and run during defrost;
FnC=O-y fans will run continuously also during defrost
4. KEYBOARD
To display and modify target set point; in programming mode it selects a parameter or
confirm an operation.
By holding it pressed for 3s when max or min temperature is displayed it will be erased.
To see the max. stored temperature; in programming mode it browses the parameter
codes or increases the displayed value. By holding it pressed for 3s the fast freezing cycle
is started.
To see the min stored temperature; in programming mode it browses the parameter codes
or decreases the displayed value.
By holding it pressed for 3s the defrost is started.
Switch ON and OFF the light of the cold-room
Switch ON and OFF the instrument.
KEY COMBINATIONS
+
To lock and unlock the keyboard.
+
To enter the programming mode.
+
To exit the programming mode.
4.1 USE OF LEDS
Each LED function is described in the following table.
LED
MODE
Function
ON
The compressor is running
FLASHING
- Programming Phase (flashing with LED )
- Anti-short cycle delay enabled
ON
The fan is running
FLASHING
Programming Phase (flashing with LED )
ON
The defrost is enabled
FLASHING
Drip time in progress
ON
The Fast Freezing cycle is enabled
ON
- ALARM signal
- In “Pr2” indicates that the parameter is also present in “Pr1”
ON
The light is on
4.2 HOW TO SEE THE MIN TEMPERATURE
1. Press and release the nkey.
2. The “Lo” message will be displayed followed by the minimum temperature recorded.
3. By pressing the nkey or waiting for 5s the normal display will be restored.
4.3 HOW TO SEE THE MAX TEMPERATURE
1. Press and release the okey.
2. The “Hi” message will be displayed followed by the maximum temperature recorded.
3. By pressing the okey or waiting for 5s the normal display will be restored.
4.4 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
To reset the stored temperature, when max or min temperature is displayed :
1. Press SET key until “rST” label starts blinking.
N.B. After the installation RESET the temperature stored .
1592009730 XW30-35VS GB r1.2 31.07.2015 XW30VS - XW35VS 2/4
4.5 HOW TO SEE AND MODIFY THE SET POINT
1. Push and immediately release the SET key: the display will show the Set point value;
2. The SET LED start blinking;
3. To change the Set value push the o or narrows within 10s.
4. To memorise the new set point value push the SET key again or wait 10s.
4.6 TO START A MANUAL DEFROST
1. Push the DEF key for more than 2 seconds and a manual defrost will start.
4.7 TO ENTER IN PARAMETERS LIST “PR1”
To enter the parameter list “Pr1” (user accessible parameters) operate as follows:
1. Enter the Programming mode by pressing the Set and DOWN key for few
seconds ( and start blinking).
2. The instrument will show the first parameter present in “Pr1”
4.8 TO ENTER IN PARAMETERS LIST “PR2”
To access parameters in “Pr2”:
1. Enter the “Pr1” level.
2. Select “Pr2” parameter and press the “SET” key.
3. The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero.
4. Use oor nto input the security code in the flashing digit; confirm the figure by pressing “SET”.
The security code is “321“.
5. If the security code is correct the access to “Pr2” is enabled by pressing “SET” on the last digit.
Another possibility is the following: after switching ON the instrument the user can push Set and DOWN
keys within 30 seconds.
NOTE: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing “SET” + n.
When a parameter is present in “Pr1” LED is on.
4.9 HOW TO CHANGE THE PARAMETER VALUE
1. Enter the Programming mode.
2. Select the required parameter with oor n.
3. Press the “SET” key to display its value ( and LED starts blinking).
4. Use oor nto change its value.
5. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15s without pressing a key.
NOTE: the new programming is stored even when the procedure is exited by waiting the time-out.
4.10 HOW TO LOCK THE KEYBOARD
1. Keep the oand nkeys pressed together for more than 3 s the oand nkeys.
2. The “POF” message will be displayed and the keyboard is locked. At this point it is
only possible the viewing of the set point or the MAX o Min temperature stored and
to switch ON and OFF the light, the auxiliary output and the instrument.
TO UNLOCK THE KEYBOARD
Keep the oand nkeys pressed together for more than 3s.
4.11 ON/OFF FUNCTION
By pushing the ON/OFF key, the instrument shows “OFF” for 5 sec. and the ON/OFF
LED is switched ON.
During the OFF status, all the relays are switched OFF and the regulations are stopped;
N.B. During the OFF status the Light button is active.
4.12 TO SEE THE PROBE VALUES
1. Enter in “Pr2” level.
2. Select “Prd” parameter with oor n.
3. Press the “SET” key to display “Pb1” label alternate with Pb1 value.
4. Use o and nkeys to display the other probe values.
5. Press “SET” to move to the following parameter.
5. PARAMETER LIST
REGULATION
Hy Differential: (0,1÷25,5°C; 1÷45°F): Intervention differential for set point, always positive.
Compressor Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the
temperature reaches the set point.
LS Minimum set point limit: (-50,0°C

SET; -58°F÷SET) Sets the minimum acceptable value for
the set point.
US Maximum set point limit: (SET

110°C; SET÷230°F) Set the maximum acceptable value for set
point.
OdS Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up
of the instrument and inhibits any output activation for the period of time set in the parameter.
(Light can work)
AC Anti-short cycle delay: (0÷30 min) interval between the compressor stop and the following
restart.
CCt Thermostat override: (0min ÷23h 50min) allows to set the length of the continuous cycle. Can
be used, for instance, when the room is filled with new products.
Con Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is active
in case of faulty thermostat probe. With COn=0 compressor is always OFF.
COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is off
in case of faulty thermostat probe. With COF=0 compressor is always active.
CH Type of action: CL = cooling; Ht = heating.
DISPLAY
CF Temperature measurement unit: °C = Celsius; °F = Fahrenheit. When the measurement unit is
changed the SET point and the values of some parameters have to be modified.
rES Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display.
dE = 0,1°C; in = 1 °C
Lod Local display : select which probe is displayed by the instrument:
P1 = Thermostat probe; P3 = Display probe; P2: not set it, 1r2: not set it
DEFROST
EdF Defrost mode:
in = interval mode. The defrost starts when the time “Idf” is expired.
Sd = Smartfrost mode. The time IdF (interval between defrosts) is increased only when the
compressor is running (even non consecutively) and only if the evaporator temperature is less
than the value in "SdF” (set point for SMARTFROST).
IdF Interval between defrosts: (1÷120h) Determines the time interval between the beginning of two
defrost cycles.
MdF (Maximum) duration of defrost: (0÷255 min) When P2P = n, no evaporator probe, it sets the
defrost duration, when P2P = y, defrost end based on temperature, it sets the maximum length for
defrost.
dFd Display during defrost:
rt = real temperature; it = temperature reading at the defrost start;
Set = set point; dEF = “dEF” label; dEG = “dEG” label;
dAd Defrost display time out: (0

255 min) Sets the maximum time between the end of defrost and
the restarting of the real room temperature display.
dPO First defrost after start-up:
y = Immediately; n= after the IdF time
dAF Defrost delay after fast freezing: (0min÷23h 50min) after a Fast Freezing cycle, the first defrost
will be delayed for this time.
FANS –Only for XR35VS
FnC Fan operating mode:
C-n = running with the compressor, OFF during the defrost;
C-y = running with the compressor, ON during the defrost;
O-n = continuous mode, OFF during the defrost;
O-y = continuous mode, ON during the defrost;
Fnd Fan delay after defrost: (0÷255 min) The time interval between the defrost end and evaporator
fans start.
ALARMS
ALC Temperature alarm configuration
rE = High and Low alarms related to Set Point
Ab = High and low alarms related to the absolute temperature.
ALU High temperature alarm setting:
ALC= rE, 0

50°C or 90°F
ALC= Ab, ALL

110°C or 230°F
when this temperature is reached and after the ALd delay time the HA alarm is enabled.
ALL Low temperature alarm setting:
ALC = rE , 0

50 °C or 90°F
ALC = Ab , - 50°C or -58°F

ALU
when this temperature is reached and after the ALd delay time, the LA alarm is enabled,.
AFH Temperature alarm differential: (0,1÷25,5°C; 1÷45°F) Intervention differential for temperature
alarm set point, always positive.
ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm condition
and the corresponding alarm signalling.
dAO Delay of temperature alarm at start-up: (0min÷23h 50min) time interval between the detection
of the temperature alarm condition after the instrument power on and the alarm signalling.
EdA Alarm delay at the end of defrost: (0

255 min) Time interval between the detection of the
temperature alarm condition at the end of defrost and the alarm signalling.
dot Delay of temperature alarm after closing the door : (0

255 min) Time delay to signal the
temperature alarm condition after closing the door.
doA Open door alarm delay:(0÷255 min) delay between the detection of the open door condition and
its alarm signalling: the flashing message “dA” is displayed.
nPS Pressure switch number: (0

15) Number of activation of the pressure switch, during the “did”
interval, before signalling the alarm event (I2F= PAL).
If the nPS activation in the did time is reached, switch off and on the instrument to restart
normal regulation.
PROBE INPUTS
Ot Thermostat probe calibration: (-12.0

12.0°C/ -21

21°F) allows to adjust possible offset of the
thermostat probe.
O3 Display probe calibration: (-12.0

12.0°C/ -21

21°F) allows to adjust possible offsets of the
display probe.
P3P Display probe presence: n= not present:; y= present:.
HES Temperature increase during the Energy Saving cycle : (-30,0°C

30,0°C / -22÷86°F) sets
the increasing value of the set point during the Energy Saving cycle.
DIGITAL INPUTS
odc Compressor and fan status when open door:
no = normal; Fan = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan OFF.
I2P Configurable digital input polarity:
CL : the digital input is activated by closing the contact;
OP : the digital input is activated by opening the contact
I2F Digital input operating mode: configure the digital input function:
EAL = generic alarm; bAL = serious alarm mode; PAL = Pressure switch; dFr = Start
defrost;
AUS = Not used; Es = Energy Saving; onF = remote On/OFF; dor = door switch
did Time interval/delay for digital input alarm:(0

255 min.) If I2F=EAL or bAL (external alarms),
“did” parameter defines the time delay between the detection and the successive signalling of the
alarm.
1592009730 XW30-35VS GB r1.2 31.07.2015 XW30VS - XW35VS 3/4
OTHER
Adr RS485 serial address (1÷247): Identifies the instrument address when connected to a ModBUS
compatible monitoring system.
PbC Type of probe: it allows to set the kind of probe used by the instrument:
PbC = PBC probe, ntC = NTC probe.
rEL Release software: (read only) Software version of the microprocessor.
Ptb Parameter table: (read only) it shows the original code of the Dixell parameter map.
Prd Probes display: (read only) display the temperature.
Pr2 Access to the protected parameter list (read only).
6. DIGITAL INPUT
The controllers have 1 free contact digital input. It is programmable in seven different configurations by
the “I2F” parameter.
6.1 DOOR SWITCH INPUT (I2F = dor)
It signals the door status and the corresponding relay output status through the “odc” parameter:
no = normal (any change);
Fan = Fan OFF;
CPr = Compressor OFF;
F_C = Compressor and fan OFF.
Since the door is opened, after the delay time set through parameter “dOA”, the alarm output is
enabled and the display shows the message “dA”. The alarm stops as soon as the external digital input
is disabled again. During this time and then for the delay “dot” after closing the door, the high and low
temperature alarms are disabled.
6.2 GENERIC ALARM (I2F = EAL)
As soon as the digital input is activated the unit will wait for “did” time delay before signalling the “EAL”
alarm message. The outputs status don’t change. The alarm stops just after the digital input is de-
activated.
6.3 SERIOUS ALARM MODE (I2F = BAL)
When the digital input is activated, the unit will wait for “did” delay before signalling the “BAL” alarm
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated.
6.4 PRESSURE SWITCH (I2F = PAL)
If during the interval time set by “did” parameter, the pressure switch has reached the number of
activation of the “nPS” parameter, the “PAL” pressure alarm message will be displayed. The
compressor and the regulation are stopped. When the digital input is ON the compressor is always
OFF.
If the nPS activation in the did time is reached, switch off and on the instrument to restart
normal regulation.
6.5 START DEFROST (I2F = DFR)
It executes a defrost if there are the right conditions. After the defrost is finished, the normal regulation
will restart only if the digital input is disabled otherwise the instrument will wait until the “Mdf” safety time
is expired.
6.6 ENERGY SAVING (I2F = ES)
The Energy Saving function allows to change the set point value as the result of the SET+ HES
(parmeter) sum. This function is enabled until the digital input is activated.
6.7 REMOTE ON/OFF (I2F = ONF)
This function allows to switch ON and OFF the instrument.
6.8 DIGITAL INPUTS POLARITY
The digital input polarity depends on the “I2P” parameters.
CL : the digital input is activated by closing the contact.
OP : the digital input is activated by opening the contact
7. INSTALLATION AND MOUNTING
Instruments shall be mounted on vertical panel, in a 72x56 mm hole, and fixed using screws

3 x
2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RGW-V).
The temperature range allowed for correct operation is 0 - 60 °C. Avoid places subject to strong
vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes.
Let the air circulate by the cooling holes.
7.1 CUT OUT
56
72
40
83,5
8. ELECTRICAL CONNECTIONS
Relays, power supply, digital and analogue inputs have a Faston connection (6,3mm). Heat-resistant
cables have to be used. Before connecting cables make sure the power supply complies with the
instrument’s requirements. Separate the probe cables from the power supply cables, from the outputs
and the power connections. Do not exceed the maximum current allowed on each relay, in case of
heavier loads use a suitable external relay.
N.B. Maximum current allowed for all the loads is 20A.
8.1 PROBE CONNECTIONS
The probe shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration.
It is recommended to place the thermostat probe away from air streams to correctly measure the
average room temperature.
9. USE OF THE PROGRAMMING “HOT KEY “
The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to the
“Hot Key” and vice-versa.
9.1 DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT)
1. Turn OFF the instrument by means of the ON/OFF key, remove the TTL serial cable if present,
insert the “Hot Key” and then turn the Wing ON.
2. Automatically the parameter list of the “Hot Key” is downloaded into the Wing memory, the
“DoL” message is blinking. After 10 seconds the instrument will restart working with the new
parameters.
3. Turn OFF the instrument remove the “Hot Key”, plug in the TTL serial cable, then turn it ON
again.
At the end of the data transfer phase the instrument displays the following messages:
“end “ for right programming. The instrument starts regularly with the new programming.
“err” for failed programming. In this case turn the unit off and then on if you want to restart the
download again or remove the “Hot key” to abort the operation.
9.2 UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”)
1. Turn OFF the instrument by means of the ON/OFF key and remove the TTL serial cable if
present; then turn it ON again.
2. When the Wing unit is ON, insert the “Hot key” and push okey; the "uPL" message
appears.
3. Push “SET” key to start the UPLOAD; the “uPL” message is blinking.
4. Turn OFF the instrument remove the “Hot Key”, plug in the TTL serial cable, then turn it ON
again.
At the end of the data transfer phase the instrument displays the following messages:
“end “ for right programming.
“err” for failed programming. In this case push “SET” key if you want to restart the programming again
or remove the not programmed “Hot key”.
10. ALARM SIGNALS
Message
Cause
Outputs
“P1”
Thermostat probe failure
Alarm output ON; Compressor output according to
parameters “COn” and “COF”
“P3”
Display probe failure
Alarm output ON; Other outputs unchanged
“HA”
Maximum temperature alarm
Alarm output ON; Other outputs unchanged
“LA”
Minimum temperature alarm
Alarm output ON; Other outputs unchanged
“EE”
Data or memory failure
Alarm output ON; Other outputs unchanged
“dA”
Door switch alarm
Alarm output ON; Other outputs unchanged
“EAL”
External alarm
Alarm output ON; Other outputs unchanged
“bAL”
Serious external alarm
Alarm output ON; Other outputs OFF
“PAL”
Pressure switch alarm
Alarm output ON; Other outputs OFF
The alarm message is displayed until the alarm condition is recovery.
All the alarm messages are showed alternating with the room temperature except for the “P1” which is
flashing. To reset the “EE” alarm and restart the normal functioning press any key, the “rSt” message is
displayed for about 3s.
10.1 SILENCING BUZZER
Once the alarm signal is detected the buzzer can be silenced by pressing any key.
10.2 “EE” ALARM
The Dixell instruments are provided with an internal check for the data integrity. Alarm “EE” flashes
when a failure in the memory data occurs. In such cases the alarm output is enabled.
10.3 ALARM RECOVERY
Probe alarms : “P1” (probe1 faulty) and “P3”; they automatically stop 10s after the probe restarts
normal operation. Check connections before replacing the probe.
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns
to normal values or when the defrost starts.
Door switch alarm “dA” stop as soon as the door is closed.
External alarms “EAL”, “BAL” stop as soon as the external digital input is disabled
Pressure switch alarm “PAL” alarm is recovered by switching OFF the instrument.
1592009730 XW30-35VS GB r1.2 31.07.2015 XW30VS - XW35VS 4/4
11. TECHNICAL DATA
Housing: self extinguishing ABS.
Case: facia 100x64 mm; depth 76mm
Mounting: panel mounting in a 56x72 mm panel cut-out with two screws.

3x2mm. Distance between
the holes 40mm
Protection: IP20.
Frontal protection: IP65 with optional frontal gasket mod RGW-V (XW35VS).
Connections: 6,3mm faston heat-resistant wiring and/or 2,8mm for probes and d.i.
Power supply: 230Vac or. 110Vac

10%
Power absorption: 7VA max.
Display: 3 digits, red LED, 14,2 mm high.
Inputs: 2 NTC or PTC probe
Relay outputs: Total current on loads MAX. 20A
compressor: relay SPST 20(8) A, 250Vac or. SPST 8(3) A, 250Vac
light: : relè SPST 16(6) A, 250Vac
fans: relay SPST 8(3) A, 250Vac
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B.
Pollution grade: normal
Software class: A.
Operating temperature: 0÷60 °C.
Storage temperature: -25÷60 °C.
Relative humidity: 20

85% (no condensing)
Measuring and regulation range:
PTC probe: -50÷150°C (-58÷302°F)
NTC probe: -40÷110°C (-58÷230°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,5 °C ±1 digit
12. CONNECTIONS
12.1 XW30VS
Light
Power supply: use terminal 3-4; according to the model 230Vac or 120Vac or 24Vac
12.2 XW35VS
Light
Power supply: use terminal 3-4; according to the model 230Vac or 120Vac or 24Vac
13. DEFAULT SETTING VALUES
Label
Name
Range
Default
Level
REGULATION
°C/°F
Set
Set point
LS÷US
3/37
Pr1
Hy
Differential
0,1÷25,5 °C / 1÷45°F
2/4
Pr1
LS
Minimum set point
-50,0°C÷SET / -
58°F÷SET
-10/14
Pr2
US
Maximum set point
SET ÷ 110°C / SET ÷
230°F
20/68
Pr2
OdS
Outputs activation delay at start up
0÷255 min.
0
Pr2
AC
Anti-short cycle delay
0÷30 min.
1
Pr1
CCt
Compressor ON time during fast freezing
0 ÷ 23h 50 min.
0.0
Pr2
COn
Compressor ON time with faulty probe
0÷255 min.
15
Pr2
COF
Compressor OFF time with faulty probe
0÷255 min.
30
Pr2
CH
Type of regulation
CL, Ht
CL
Pr2
DISPLAY
CF
Temperature measurement unit
°C ÷ °F
°C/F
Pr2
rES
Resolution (integer/decimal point)
in ÷ de
dE/-
Pr1
Lod
Local display
P1 ÷ 1r2
P1
Pr2
DEFROST
EdF
Defrost mode
In, Sd
in
Pr2
IdF
Interval between defrost cycles
1÷120h
8
Pr1
MdF
(Maximum) length for 1° defrost
0÷255 min.
20
Pr1
dFd
Displaying during defrost
rt, it, SEt, dEF, dEG
it
Pr2
dAd
MAX display delay after defrost
0÷255 min.
30
Pr2
dPO
First defrost after start up
n ÷ y
n
Pr2
dAF
Defrost delay after fast freezing
0 ÷ 23h 50 min.
0.0
Pr2
FANS- only XW35VS
FnC
Fans operating mode
C-n, C-y, O-n, O-y
O-n
Pr2
Fnd
Fans delay after defrost
0÷255 min.
10
Pr2
ALARMS
ALC
Temperature alarms configuration
rE÷Ab
Ab
Pr2
ALU
MAXIMUM temperature alarm
-50,0÷110°C/ -58÷230°F
110/230
Pr1
ALL
minimum temperature alarm
-50,0÷110°C/ -58÷230°F
-40/-40
Pr1
AFH
Temperature alarm differential
0,1÷25,5 °C / 1÷45°F
2/4
Pr2
ALd
Temperature alarm delay
0÷255 min.
15
Pr2
dAO
Delay of temperature alarm at start up
0 ÷ 23h 50 min.
1,3
Pr2
EdA
Alarm delay at the end of defrost
0÷255 min.
30
Pr2
dot
Delay of temperat. alarm after closing the
door
0÷255 min.
15
Pr2
dOA
Open door alarm delay
0÷255 min.
15
Pr2
nPS
Pressure switch number
0÷15
0
Pr2
ANALOGUE INPUTS
Ot
Thermostat probe calibration
-12,0÷12,0°C / -21÷21°F
0/0
Pr2
O3
Display probe calibration
-12,0÷12,0°C / -21÷21°F
0/0
Pr2
P3P
Display probe presence
n ÷ y
n
Pr2
HES
Temperature increasing during the Energy
Saving cycle
-30÷30°F/-54÷54°F
0
Pr2
DIGITAL INPUTS
Odc
Open door control
no, Fan, CPr, F_C
no
Pr2
I2P
Configurable digital input polarity
CL÷OP
cL
Pr2
i2F
Digital input configuration
dor, EAL, bAL, PAL, dFr,
AUS, ES, OnF
dor
Pr2
dId
Digital input alarm delay
0÷255 min.
5
Pr2
OTHER
Adr
Serial address
0÷247
1
Pr2
Pbc
Kind of probe
PbC, ntc
ntc/Ptc
Pr2
rEL
Software release
- - -
2.0
Pr2
Ptb
Map code
- - -
- - -
Pr2
Prd
Probes display
Pb1
- - -
Pr2
Pr2
Access parameter list
- - -
- - -
Pr1

This manual suits for next models

1

Other Emerson Temperature Controllers manuals

Emerson XT110C User manual

Emerson

Emerson XT110C User manual

Emerson TS1 Series User manual

Emerson

Emerson TS1 Series User manual

Emerson R-410A User manual

Emerson

Emerson R-410A User manual

Emerson Blue Wireless Easy Install 1F98EZ-1621 User manual

Emerson

Emerson Blue Wireless Easy Install 1F98EZ-1621 User manual

Emerson Rosemount 65 Series User manual

Emerson

Emerson Rosemount 65 Series User manual

Emerson dixell WING XW20L Wiring diagram

Emerson

Emerson dixell WING XW20L Wiring diagram

Emerson E2 User manual

Emerson

Emerson E2 User manual

Emerson Dixell XH360L-V Wiring diagram

Emerson

Emerson Dixell XH360L-V Wiring diagram

Emerson Blue Wireless Easy Install 1F98EZ-1621 User manual

Emerson

Emerson Blue Wireless Easy Install 1F98EZ-1621 User manual

Emerson TS1-G User manual

Emerson

Emerson TS1-G User manual

Emerson Dixell XW30L - CL01 Wiring diagram

Emerson

Emerson Dixell XW30L - CL01 Wiring diagram

Emerson Rosemount 65Q User manual

Emerson

Emerson Rosemount 65Q User manual

Emerson E2 User manual

Emerson

Emerson E2 User manual

Emerson 16E09-101 User manual

Emerson

Emerson 16E09-101 User manual

Emerson COOL MATE XLH260 User manual

Emerson

Emerson COOL MATE XLH260 User manual

Popular Temperature Controllers manuals by other brands

Carrier Transicold 69NT40-541 Series Operation and service

Carrier

Carrier Transicold 69NT40-541 Series Operation and service

System Sensor 5351B Installation and maintenance instructions

System Sensor

System Sensor 5351B Installation and maintenance instructions

Sensit TG8 instruction manual

Sensit

Sensit TG8 instruction manual

OJ Electronics CPST10 instructions

OJ Electronics

OJ Electronics CPST10 instructions

domat THERMASGARD ATF Series Operating Instructions, Mounting & Installation

domat

domat THERMASGARD ATF Series Operating Instructions, Mounting & Installation

Chauvin Arnoux STATOP 9601 user manual

Chauvin Arnoux

Chauvin Arnoux STATOP 9601 user manual

Delta Controls RTS-424 Application guide

Delta Controls

Delta Controls RTS-424 Application guide

Bühler technologies TF with IO-Link Installation and operation instructions

Bühler technologies

Bühler technologies TF with IO-Link Installation and operation instructions

Omron E5AN-H datasheet

Omron

Omron E5AN-H datasheet

Fike FIK-2351T Installation and maintenance instructions

Fike

Fike FIK-2351T Installation and maintenance instructions

AURATON Cetus manual

AURATON

AURATON Cetus manual

Viessmann VITOPLANAR Installation and operating instructions

Viessmann

Viessmann VITOPLANAR Installation and operating instructions

2VV ESSENSSE NEO COMFORT Installation and operation instructions

2VV

2VV ESSENSSE NEO COMFORT Installation and operation instructions

Oregon Scientific S+ARCK PS-R01 user manual

Oregon Scientific

Oregon Scientific S+ARCK PS-R01 user manual

Prosense ETS Series operating instructions

Prosense

Prosense ETS Series operating instructions

hotset C 148 user manual

hotset

hotset C 148 user manual

Kramer RC-6E user manual

Kramer

Kramer RC-6E user manual

Pentair Raychem RTD-200 installation instructions

Pentair

Pentair Raychem RTD-200 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.