EMS SmartCell SmartDoor User manual

©2021 EMS Ltd. All rights reserved. MK347-0001-99 Issue 2 25/08/2021 AJM
SmartDoor
Installation Guide

©2021 EMS Ltd. All rights reserved. Page 2 of 16 MK347-0001-99 Issue 2 25/08/2021 AJM
Part number and description
Pre installation
Components
Equipment familiarisation
Insert batteries
Configuration
Position template against door
Drill fixing positions
Fix unit to door
Position floor plate
Mark floor plate fixing positions
Drill floor plate fixing positions
Fix floor plate to floor
Open fire door & depress plunger
Test device
Troubleshooting
Device tone & flash indication
Specification
Regulatory information
3
3
3
4
4
5
6
6
7
7
8
8
9
9
10
11
12
13
14
Contents

©2021 EMS Ltd. All rights reserved. Page 3 of 16 MK347-0001-99 Issue 2 25/08/2021 AJM
!
Ensure ESD
protection label is
fitted when
installing WDC on
metal kick plates
or uneven surfaces
(inside cut out)
!
Installation must conform to applicable local installation codes and
should only be installed by a fully trained competent person.
Ensure that the device is fitted to the side of the door that shuts
against the door frame.
Check that the fire door is suitable e.g. self closing, has a flat surface to
fix to and has appropriate clearance under the door to accommodate
the floor plate.
The supplied ESD protection label must be fitted when installing the
SmartDoor on metal kick plates or uneven surfaces.
Any door closing devices used in conjunction with SmartDoor must
conform to EN 1154.
To ensure correct operation, products must be used within the
specified environmental operating conditions.
SmartDoor
Small & large
floor plates
21
1 2 Fixing template
(MK350)
3
34
Fixings
4
5
ESD protection
label
5
Pre installation
Part number Product description
SC-44-0200-0001-99 SmartDoor (white)
SC-44-0300-0001-99 SmartDoor (black)
Components

©2021 EMS Ltd. All rights reserved. Page 4 of 16 MK347-0001-99 Issue 2 25/08/2021 AJM
Ferrule
Plunger
Battery
compartment
Log on button
Fixing position
Fixing position
Fixing position
Fixing position
When fitting / replacing batteries;
observe correct polarity, using only
specified batteries.
Indication LED
!
Note; upon first power
up the device will
initiate a start-up sequence,
denoted by a series of low
pitched beeps and motor
operations. This sequence will
take approximately 15 seconds
and concludes with three low
pitched beeps.
Should the sequence close with
a mix of high and low pitched
beeps, refer to page 13.
Equipment familiarisation
Insert batteries

©2021 EMS Ltd. All rights reserved. Page 5 of 16 MK347-0001-99 Issue 2 25/08/2021 AJM
The device must now be added (programmed) to the control panel.
Note: the device can also be programmed utilising the control panel’s cause and
effects, as part of the buildings evacuation plan.
Refer to the programming manual for full programming details.
SmartCell panel = TSD155
SmartCell WZM = MK067
Configuration
Device powering
Method 1 Log on button
Method 2
Via computer
Method 3

©2021 EMS Ltd. All rights reserved. Page 6 of 16 MK347-0001-99 Issue 2 25/08/2021 AJM
= 2.5mm
Drill all four fixing positions.
!
If the device is to be tted to a metal surface, e.g. a
metal kick plate, the ESD protection label must be
tted. Simply ax the label inside the xing template’s cut
out, on to the metal surface.
Drill fixing positions
Position template against door

©2021 EMS Ltd. All rights reserved. Page 7 of 16 MK347-0001-99 Issue 2 25/08/2021 AJM
Door
Bump
stop
Side view
Ferrule
Floor plate
Use all four fixing positions.
Use supplied fixing screws.
Position floor plate
Fix unit to door

©2021 EMS Ltd. All rights reserved. Page 8 of 16 MK347-0001-99 Issue 2 25/08/2021 AJM
!
Use small oor plate, if bump stop
creates a trip hazard
Mark all four fixing positions.
!
Before drilling, check
locations of water pipes,
gas pipes & electrical cables
= 6 mm
Drill floor plate fixing positions
Mark floor plate fixing positions

©2021 EMS Ltd. All rights reserved. Page 9 of 16 MK347-0001-99 Issue 2 25/08/2021 AJM
Use all four fixing holes.
Use supplied fixing screws.
!
Open the door against the
bump stop and depress the
plunger - check that the ferrule
ts neatly into the recess
Fix floor plate to floor
Open fire door & depress plunger

©2021 EMS Ltd. All rights reserved. Page 10 of 16 MK347-0001-99 Issue 2 25/08/2021 AJM
Test device

©2021 EMS Ltd. All rights reserved. Page 11 of 16 MK347-0001-99 Issue 2 25/08/2021 AJM
In the rare event of an issue with the device’s operation, refer to the points below:
Device is not releasing upon a fire alarm condition?
Check that the device is added correctly to the system and that it is fault free at
the SmartCell control panel.
Check that the door closes freely when closed manually.
Check that the plunger has a minimum of 10 mm clearance between the ferrule
and the floor / floor plate.
Check the
SmartDoor
’s output properties are set correctly within the control
panel programming.
Why does the fire door not close freely?
Check that the ferrule is not worn or damaged. Replace as necessary.
Check that the plunger has a minimum of 10 mm clearance between the ferrule
and the floor / floor plate.
Device is not holding the door in an open position
Check that the plunger is depressed fully.
Check that the device is added correctly to the system and fault free at the
control panel.
Check that the device is positioned low enough for a good connection between
the ferrule and the floor plate. The optimum plunger movement is 10 - 15 mm.
Device is in tamper fault?
Check that the device is fixed correctly to the door.
Check that the surface is flat and that the tamper switch is engaging correctly,
when the device is fixed to the door.
Battery fault / device is not powered?
Check the polarity and the voltage of the batteries.
Check that the battery cover is fitted correctly.
Troubleshooting

©2021 EMS Ltd. All rights reserved. Page 12 of 16 MK347-0001-99 Issue 2 25/08/2021 AJM
In addition to fault reporting at the control panel,
SmartDoor
has various beep and
flash sequences to indicate a number of conditions.
Beep sequence
Low-Low-Low
High-High-Low
(repeated until
resolved)
High-High-High-
High-Low-Low-
Low-Low
None
Flash sequence
None
Red-Red (on first
two beeps only)
Red-Red-Red-Red
(on first four beeps
only)
Red-Green
Indicative meaning
Start-up complete
Motor fault
Internal fault
(non-serviceable
part)
Battery pack low /
incorrectly inserted
(2x C batteries)
Action required
None
Remove and re-insert
batteries
Remove and re-insert
batteries (If fault persists,
return to manufacturer)
Replace / remove and
re-insert batteries
(as appropriate)
During device start-up sequence / motor operation
Beep sequence
Low-Low-High
(repeated until the
plunger releases)
High-Low-Low-Low
(repeated until
resolved)
High-Low
(seven times, then
door releases)
Flash sequence
Red (on low beeps
only)
Red (on first
sequence only)
Red (on first beep
in sequence only)
Indicative meaning
Plunger fault
Internal fault
(non-serviceable
part)
Door is about to
close†
Action required
Check for obstructions
to the plunger
Remove and re-insert
batteries (If fault persists,
return to manufacturer)
Move away from the
doorway
During standard operation
† Door closing can be as a result of many factors such as a fire condition, a loss of
communication or a battery critical condition. Refer to the control panel for details.
Device tone and flash indication

©2021 EMS Ltd. All rights reserved. Page 13 of 16 MK347-0001-99 Issue 2 25/08/2021 AJM
Operating temperature -10 °C to 55 °C
Storage temperature 5 °C to 30 °C
Humidity Up to 95% non-condensing
Supply 2x C Alkaline (Panasonic LR14AD Powerline /
Varta 4014 Industrial)
CAUTION!
This is a life safety product. Only use manufacturer approved battery types.
Failure to do so may result in damage to the product.
DO NOT mix batteries of different type or age.
When replacing batteries; remove all old batteries before fitting replacements.
Supply voltage 2.22 to 3.3 VDC
Current consumption 60 µA
Operating frequency 868 MHz
Output transmitter power 0 - 14 dBm / 0 - 25 mW
Signalling protocol X5
Dimensions (W x H x D) 195 x 205 x 45 mm
Weight 0.5 kg
Location Type A: For indoor use
Max. hold open power size 7
Max. door leaf width 1600 mm
Max. test door mass 160 kg
Max. overload test drop weight 36 kg
Max. test door friction 0.8 Nm
Min. angle between door open 66 °
and closed positions
Note: SmartDoor is not for use on metal doors.
Specification

©2021 EMS Ltd. All rights reserved. Page 14 of 16 MK347-0001-99 Issue 2 25/08/2021 AJM
Manufacturer
Year of manufacture See devices serial number label
European Union directives
Approved to BS EN1155:1997. Incorporating Amendment No. 1 and
Corrigendum Nos. 1, 2 and 3.
BS 7273-4:2007. Code of practice for the operation of fire
protection measures – Part 4: Actuation of release
mechanisms for doors. (Category B)
EN54-25:2008. Incorporating corrigenda September 2010
and March 2012. Fire detection and fire alarm systems. Part
25: Components using radio links.
Certification
Certification body
CPR DoP 0905-CPR-202117
Carrier Manufacturing Polska Sp. Z o.o. Ul. Kolejowa 24.
39-100 Ropczyce, Poland
0905
EMS declares that the radio equipment type
SmartDoor
is
in compliance with Directive 2014/53/EU. The full text of
the EU declaration of conformity is available at the
following internet address: www.mysmartcell.com
21
2012/19/EU (WEEE directive):
Products marked with this symbol cannot be disposed of
as unsorted municipal waste in the European Union. For
proper recycling, return this product to your local supplier
upon purchase of equivalent new equipment, or dispose of
it at designated collection points. For more information
see www.recyclethis.info
Dispose of your batteries in an environmentally friendly
manner according to your local regulations.
Operating temperature -10 °C to 55 °C
Storage temperature 5 °C to 30 °C
Humidity Up to 95% non-condensing
Supply 2x C Alkaline (Panasonic LR14AD Powerline /
Varta 4014 Industrial)
CAUTION!
This is a life safety product. Only use manufacturer approved battery types.
Failure to do so may result in damage to the product.
DO NOT mix batteries of different type or age.
When replacing batteries; remove all old batteries before fitting replacements.
Supply voltage 2.22 to 3.3 VDC
Current consumption 60 µA
Operating frequency 868 MHz
Output transmitter power 0 - 14 dBm / 0 - 25 mW
Signalling protocol X5
Dimensions (W x H x D) 195 x 205 x 45 mm
Weight 0.5 kg
Location Type A: For indoor use
Max. hold open power size 7
Max. door leaf width 1600 mm
Max. test door mass 160 kg
Max. overload test drop weight 36 kg
Max. test door friction 0.8 Nm
Min. angle between door open 66 °
and closed positions
Note: SmartDoor is not for use on metal doors.
Regulatory information

©2021 EMS Ltd. All rights reserved. Page 15 of 16 MK347-0001-99 Issue 2 25/08/2021 AJM

©2021 EMS Ltd. All rights reserved. Page 16 of 16 MK347-0001-99 Issue 2 25/08/2021 AJM