Accuthermo ATEC302 User manual

ATEC302
TE Temperature Controller
Reference Manual
Rev 1.10
Mar, 2018
Accuthermo Technology Corp.

Accuthermo Technology Corp. 2
Table of Content
1. Introduction..................................................................................................................3
1.1 Using Manuals ...................................................................................................... 4
2. System Overview .........................................................................................................5
2.1 System Configuration Overview........................................................................... 5
2.2 Panel Dimension & Cutout ................................................................................... 6
2.3 Front Panel Description ........................................................................................ 6
2.4 Back Panel Wiring Diagram ................................................................................. 7
2.5 USB Wiring & Color Code................................................................................... 7
2.6.1 Sensor Type & Measurement Range.................................................................. 7
2.6.2 Sensor Type & Dip-switch setting ..................................................................... 9
2.7 Menu (Parameters) Overview ............................................................................... 9
2.8 Error Message & Troubleshooting........................................................................ 9
2.9 Power Input......................................................................................................... 10
3. Front Panel Operation ................................................................................................11
3.1 Push Buttons ...................................................................11
i. Return to Top Level Display......................................................................11
ii. Go to Menu Mode......................................................................................11
iii. Select Parameters in Menu.........................................................................11
iv. Changing Parameter value .........................................................................11
3.2 Power UP Display Sequence............................................................................... 12
3.3 Change the SV (Set Value) Number ................................................................... 12
4. Parameters Description ..............................................................................................12
4.1 Communication Protocol .................................................................................... 12
4.1.1 Communication Method .......................................................................... 12
4.1.2 Communication Protocol Format............................................................. 13
4.1.3 Communication Read/Write Format........................................................ 13
4.1.4 Prior to Writing Your Own Software ....................................................... 15
4.2 Read Only Parameters [x03] Table ..................................................................... 15
4.3 Read[x03]/Write[x06] Parameter Table .............................................................. 18
4.4 Error Read Back Parameter Table....................................................................... 23
5. Control Method..............................................................................................................24
5.1 PID Control:........................................................................................................ 24
5.2 Auto-tune Function: ............................................................................................ 24
5.3 Programmable Step Control Profile:................................................................. 256
5.4 Alarm Function: ................................................................................................ 267
6. SPECIFICATIONS ........................................................................................................28

Accuthermo Technology Corp. 3
1. Introduction
This manual contains information for the installation, operation and tuning of your Accuthermo ATEC302
TE Panel Temperature Controller, ATEC402 Din-Rail TE Temperature Controller and FTX700 High
Power TE Amplifier/Driver. ATEC302 can also be connected to FTX300 or FTX100 H-bridge amplifiers.
ATEC302
TE Panel Controller
ATEC402
(alpha ver.)
TE Din-rail Controller
FTX700D
TE Amplifier/Driver
FTX100/FTX300
TE H-bridge Amp
Pic
Pic
Pic
FTX100(6Amp)
FTX300 (12Amp)
RS232/RS485/USB USB/RS485 5~36Vdc (30Amp)
X100:0~7V, X300:7~15V
The Accuthermo microprocessor controllers are FUZZY ENHANCED “proportional + integral +
derivative” (PID) controllers that come in with industry standard DIN72x72mm and Din-Rail size. The
input is configurable and allows selection of input between thermocouples, RTD and Thermistor*.
The TE Amplifier is capable of running up to 700Watt of power. It is a very efficient TE power amplifier.
The amplifier can run without force air (fan) under 350Watt in ambient condition. Over 350Watt, it is
recommended to add in fan for proper ventilation.
The controller can talk to PC through a dedicated USB cable or a RS232 communication daughter card
(option on ATEC302) that Accuthermo provides. And it comes with very sophisticated PC software for
FREE.
The controllers can also be serial linked together and talk to one PC by using RS-485 communication
method (option on ATEC302, default on ATEC402).
Caution: When USB cable is connected to the controller, the RS232 or RS485 communication daughter
card should not be plugged inside the controller. Otherwise, it will have conflict.

Accuthermo Technology Corp. 4
1.1 Using Manuals
There are three manuals for this system:
Reference Manual (this one): The manual is designed for user who wants to use the front panel buttons to
controller the system. The users who want to write their own program to control the system. It provides the
instructions of how to use the front panel buttons, the parameter table. Users are encouraged to read the
following two manuals first.
TE Temperature Controller System Installation Guild: This is the must read document for user to putting the
system together. It is a step-by-step guide, with lots of pictures for easy reading.
Software Installation Guild & User Manual: The software contains a very completed function sets for user to
change parameters; control and run the system; monitor and logging data. It took us more than a year to design
and develop the software. More than 95% of the users find the software can satisfied their task without
re-writing their own software.

Accuthermo Technology Corp. 5
2. System Overview
2.1 System Configuration Overview

Accuthermo Technology Corp. 6
2.2 Panel Dimension & Cutout
2.3 Front Panel Description
LED Indication:
KLK keypad Lock: when keyboard is locked, the push bottom is not accessible, only working through the software
communication. LED lights on when keypad is enable.
PGR Program Ramp: LED lights on when temperature is ramping up/down.
PGS Program Soak: LED lights on when temperature is at soaking stage.
ENB Controller Enable: LED lights on when controller sent the Enable signal to the amplifier.
DIR Controller Hot/Cold Direction: LED indicator for the hot/cold direction command signal.
PWM Pulse Width Modulation Signal: LED signal lighted when PWM signal is send from controller to amplifier. During the
low duty cycle, the LED might not be bright enough for visual.
AL1 Alarm #1 indicator: LED on when Alarm #1 is triggered.
AL2 Alarm #2 indicator: LED on when Alarm #2 is triggered.
AT: Auto Tune LED
light indicator
MAL: Manuel Control
LED Light Indicator
PV: Process Value
The measured temperature
SV: Set Value
The expecting temperature
SET / LEFT / UP / DOWN
4 Control Buttons

Accuthermo Technology Corp. 7
2.4 Back Panel Wiring Diagram
2.5 USB Wiring & Color Code
Caution: If the USB cable has extra wire with RED (+5V) and Black (GND), user should either cut them off
(recommended) or isolate those leads. Otherwise, possible electric short could happen.
2.6.1 Sensor Type & Measurement Range
There are three types of sensors supported by the TE Panel controllers
Thermocouple (TC): Thermocouple is a 2-wire temperature sensor and has polarity for each wire. Please follow
the installation guild for proper connections. Accuracy: ±1°C
TYPE Range
J -120.0°C ~ 200.0°C
K -120.0°C ~ 200.0°C
T -120.0°C ~ 200.0°C

Accuthermo Technology Corp.
Thermistor (TR):
Thermistor is a resistance based temperature sensor and does not have polarity.
TYPE
TR1 (2.252K ohm)
TR2 (10K ohm)
RTD PT-100 (PT): These can be 2-
wire or 3
(PTB) together. Accuracy: ±0.2°C
TYPE
DPT(PT100)
2.6.2
Sensor Type & Dip
SW1.1
SW1.2
TC ON
PT ON
TR OFF
There is a Dip-
Switch at the inside of the controller. The user needs to pull out the controller from back case.
There are two blue-color Dip-
Switch. Adjust the on/off setting according to the sensor type you
Example: TR: Thermistor 2252 or 10k ohm
1. Pull out the Panel Cover
Note:
The yellow circles are the Dip
communi
cation daughter card (either for RS232 or RS485) position.
Caution:
if USB cable is used, the communication card (red circle area) should have no card plug in.
Remove the plug-
in card if user wants to use USB communication cable.
Thermistor is a resistance based temperature sensor and does not have polarity.
Range
-50.0°C ~ 150.0°C
-20.0°C ~ 150.0°C
wire or 3
-wire RTD sensors. If 2-
wire is used, just short the pin7 & pin8
Range
-120.0°C ~ 200.0°C
Sensor Type & Dip
-Switch Setting
SW1.2 SW1.3 SW2.1 SW2.2
OFF OFF ON ON
OFF OFF OFF ON
ON ON OFF OFF
Switch at the inside of the controller. The user needs to pull out the controller from back case.
Switch. Adjust the on/off setting according to the sensor type you
Example: TR: Thermistor 2252 or 10k ohm
– SW1:
OFF-ON-ON
, SW2:
OFF-OFF
2. Sensor Setting Switch
The yellow circles are the Dip
-
Switches and Switch setting table, the red circle showing the
cation daughter card (either for RS232 or RS485) position.
if USB cable is used, the communication card (red circle area) should have no card plug in.
in card if user wants to use USB communication cable.
8
Thermistor is a resistance based temperature sensor and does not have polarity.
wire is used, just short the pin7 & pin8
Switch at the inside of the controller. The user needs to pull out the controller from back case.
Switch. Adjust the on/off setting according to the sensor type you
want to use.
Switches and Switch setting table, the red circle showing the
if USB cable is used, the communication card (red circle area) should have no card plug in.

Accuthermo Technology Corp. 9
2.7 Menu (Parameters) Overview
Refer to Sec. 4.3 Parameter Table (Page 18) for Front Panel operation instruction
2.8 Error Message & Troubleshooting
Symptom Probable Solution
PV value flashing -Input signal below the low limit
-Incorrect input sensor selection
-Set a higher value to high limit.
-Check connect input sensor selection.
PV value flashing -Input signal below the low limit
-Incorrect input sensor selection
-Set al lower value to low limit.
-Check correct input sensor selection
-Sensor break error
-Sensor not connected
-Replace sensor
-Check the sensor is connected correctly
-A/D converter damage
-Unit must be repaired or replaced.
-
Check for outside source of damage such as
transient voltage spikes.

Accuthermo Technology Corp. 10
Keypad no function -Keypads are locked,
-When key locked, LED is off.
-Set” ”to a proper value
-
If you lock the keypads, you can only use our
PC software to unlock it (page. 16)
Process value
unstable
-
Improper setting of Pb, Ti, Td
and CT
-Start AT process to set Pb, Ti, Td
automatically
-Set Pb, Ti, Td manually
No heat/cold or output
-No heater/cold power
-
Output device defective or
incorrect output used
-Check output wiring and fuse
-Replace output device
All LED’s and display
not light
-No power to controller
-Check power lines connection
Process Value
changed abnormally
-Electromagnetic Interference
(EMI) or Radio Frequency
Interference (RFI)
-Suppress arcing contacts in system to
eliminate high voltage spike sources.
Separate sensor and controller wiring from
“dirty” power lines. Ground heaters
Entered data lost -Fail to enter data to EEPROM -Update EEPROM again
2.9 Power Input
The default setting is 9V-36V DC. There is a jumper inside the controller that you can set it for a fixed 5VDC.
When using 5VDC as supply, the USB cable CANNOT work.
When using 5V setup. Not only change the 5V jumper position; there are two components next to jumper R111
and D101 needed to be shorted. Otherwise, they would affect the voltage drop of 5V.
If the R111 and D101 are shorted, the ’Input power reverse protection’ is no longer working. Please be very
caution on it. If that was damaged, it won’t be covered by our standard warranty.
If the jumper has converted for 5VDC, connecting to supply power other than 5V will damage the
system; and the warranty is void.

Accuthermo Technology Corp. 11
3. Front Panel Operation
User should learn some front panel operation during hardware installation. This section will describe more in
detail.
3.1 Push Buttons
Referring to 2.4 Menu Overview, users can select different level of menu and change the parameters using these
four push buttons.
i. Return to Top Level Display
If you make mistake, just press & two buttons, it will return to top level display for normal
operation.
ii. Go to Menu Mode
Press and hold two buttons for 5 seconds, the screen will jump to menu mode. The RED LED line
should show . It is the first level menu. By pressing button, user can select various top menus in
sequence, using button to select the previous menu.
Note: If keypads are locked, you can only run our PC software to unlock it (page. 16)
iii. Select Parameters in Menu
The parameters selection in each menu is in a loop format. At each top menu, press button to select its
parameters. If you miss it, just press continuously until it reaches the parameter you are looking for.
iv. Changing Parameter value
The parameter is Number (ex. temperature): To change a parameter value, press to select the digit you

Accuthermo Technology Corp. 12
want to change, the specific digit LED should be highlighted. Then press to add number or to
reduce the number. Press to confirm the value.
The parameter is Type (ex. sensor type): Use or buttons to choose the desire one.
3.2 Power UP Display Sequence
When power up the controller, the display will show from Top/Bottom display in sequence:
LED all on test →Sensor type/Temperature unit →High Limit/Low Limit
→PV(process value)/SV(set value)
3.3 Change the SV (Set Value) Number
i. Use to highlight the digit you want to change.
ii. Use or buttons to change to the value desired.
iii. Press to confirm the value.
4. Parameters Description
4.1 Communication Protocol
4.1.1 Communication Method
One controller to one PC: There is a special USB data cable supplied by Accuthermo. It is a
serial-to-USB data converter. While connecting a PC and the controller with this cable, the
software Accuthermo supplied will work on this setup.
Multiple controllers to one PC: By serialized multiple controllers together through the RS485 lines
(TX+/ TX-). A PC act as a master and talk to those controllers as slave units. Each controller
should have a unique ID address number. We recommend a RS485-to-USB converter act as a

Accuthermo Technology Corp. 13
communication agent between PC and controllers. The software supplied by Accuthermo cannot
talk to multiple controllers; only one at a time with proper ID address selected.
4.1.2 Communication Protocol Format
RS232/ RS485-Modbus RTU
Party None
Data bit 8 Bit
Stop bit 1 Bit
Baud rate 19200 bps
CRC16 YES
4.1.3 Communication Read/Write Format
Read Command Code: hex x03 Write Command Code: hex x06
Each time a command is sent from the master (ex. Computer) to the controller, the controller
receives should immediately response a similar message back to its master. For example:
SEND: The PC send a command set (total of 8 bytes) asking for the temperature that was just
measured: x01-03-1000-0001-CCCC
RETURN: The slave unit (controller) returned an 8-bytes data to its master:
x01-03-0002-01F7-CCCC. Where “x01F7” is the temperature measured in Hex format (=50.3
℃
);
where “x” means hex format, “C” means CRC data.
1 2 3 4 5 6 7 8
Represent ID R/W Function Parameter Address
or Byte count
Data Cnt
Or Rtn
CRC
Byte Count 1 1 bytes 2 bytes 2 bytes 2 bytes
Byte 1 – ID: It is the ID number of the controller, the default is 1.
Byte 2 – R/W Function: Read function is hex number x03, Write function is hex number x06
Byte 3,4 – Parameter Address or Return Byte Count: See the following example and description
for detail.
Byte 5,6 – Data/Data Count/Data Return Count. The 2 bytes have different meanings during the
read-send/return. For write process, the send return should have the same value.
Byte 7,8 – Modbus CRC: 16bits Cyclic Redundancy Check is done to prevent corrupted data
during communication transmission. It takes the first known command bytes through a
CRC calculation and generates the 2-CRC bytes at the end.

Accuthermo Technology Corp. 14
Write Process Example:
During the write process the response bytes should match the command set.
Master ask the controller to set the SV temperature at 55.0℃
1 2 3 4 5 6 7 8
Represent ID R/W Function Parameter Address Data CRC
Byte Count 1 1 bytes 2 bytes 2 bytes 2 bytes
x01 x06 x0000 x0226 xCCCC
Response from the controller
1 2 3 4 5 6 7 8
Represent ID R/W Function Parameter Address Data CRC
Byte Count 1 1 bytes 2 bytes 2 bytes 2 bytes
x01 x06 x0000 x0226 xCCCC
Read Process Example:
During the read process, you can ask for one data back, or you can ask a set of data back in
sequence. The byte 3-4 is the initial parameter address. The byte 5-6 is to tell slave how many
consecutive data you want. The following example only asks for one data.
The master ask the controller to read current temperature (PV value)
1 2 3 4 5 6 7 8
Represent ID R/W Function Parameter Address Data Cnt CRC
Byte Count 1 1 bytes 2 bytes 2 bytes 2 bytes
x01 x03 x1000 x0001 xCCCC
In the response data set, the byte 3-4 is the byte count of the data return. The following example is
the response data from above command. The byte 3-4 tell the master it has 2 bytes of data. The
content of the return data is at byte 5-6.
Response from the controller (measured 28.7
℃
)
1 2 3 4 5 6 7 8
Represent ID R/W Function Byte Count Data Rtn CRC
Byte Count 1 1 bytes 2 bytes 2 bytes 2 bytes
x01 x03 x0002 x011F xCCCC
Note: Byte Count value =2 x Data Count value

Accuthermo Technology Corp.
4.1.4 Prior to Writing Your Own
Most users
will find the software come with the system should work just fine. There are about 5% engineers
need to write their own software to integrate with other hardware. To better understand how the parameters
work, Please use the Protocol Sec
tion of the software that Accuthermo supplied. You can then try out all the
parameters in tables of 4.2 and see how they interacting each other.
Refer to top right pic; the protocol page of Accuthermo PC software. After read PV and conver
same as value showing on the front panel of the ATEC302 controller. To read PV (process value = your sensor temperature), we
"\01\03\10\00\00\01\80\
CA" (Hex code) to send to controller. Here is the explana
a) First byte \01: the controller address.
b) Second byte \
03: to read from the controller (
c) 3&4 byte \10\
00: the x1000 is to read PV+PV
you are reading the PV value.
d) 5&6 byte \00\
01: For READ process, these two bytes does not do anything, so we just put two dummy bytes here.
e) 7&8 byte \80\
CA: The two byte CRC va
Since read PV is a fixed value in this case, you can just write all 8 bytes showing above. You don't have to calculate CRC ev
PV command.
4.2 Read Only Parameters [
Read Only Parameters:
Read parameter and value from the controller
4.1.4 Prior to Writing Your Own
Software
will find the software come with the system should work just fine. There are about 5% engineers
need to write their own software to integrate with other hardware. To better understand how the parameters
tion of the software that Accuthermo supplied. You can then try out all the
parameters in tables of 4.2 and see how they interacting each other.
Refer to top right pic; the protocol page of Accuthermo PC software. After read PV and conver
ted to DegC, it shown 19.7C, and should be the
same as value showing on the front panel of the ATEC302 controller. To read PV (process value = your sensor temperature), we
CA" (Hex code) to send to controller. Here is the explana
tion of those 8 bytes:
03: to read from the controller (
\
06 is to write to the controller). In this case, you want to read PV from the controller.
00: the x1000 is to read PV+PV
-offset value together. In most of the case, the PV-
offset is 0 (unless changed by user). So
01: For READ process, these two bytes does not do anything, so we just put two dummy bytes here.
CA: The two byte CRC va
lue after calculate the prior 6 bytes of data(\01\03\10\00\00\
01).
Since read PV is a fixed value in this case, you can just write all 8 bytes showing above. You don't have to calculate CRC ev
4.2 Read Only Parameters [
x03] Table
Read parameter and value from the controller
15
will find the software come with the system should work just fine. There are about 5% engineers
need to write their own software to integrate with other hardware. To better understand how the parameters
tion of the software that Accuthermo supplied. You can then try out all the
ted to DegC, it shown 19.7C, and should be the
same as value showing on the front panel of the ATEC302 controller. To read PV (process value = your sensor temperature), we
use
06 is to write to the controller). In this case, you want to read PV from the controller.
offset is 0 (unless changed by user). So
01: For READ process, these two bytes does not do anything, so we just put two dummy bytes here.
01).
Since read PV is a fixed value in this case, you can just write all 8 bytes showing above. You don't have to calculate CRC ev
ery time for Reading

Accuthermo Technology Corp. 16
Address
Parameter
Name Contents Unit
x1000 PVPVOF PV + PVOF °C/°F/ ENG
x1001 SVSVOF SV + SVOF °C/°F/ ENG
x1002 OUTL Output Power in Percentage %
x1003
WKERNO
x _ _ _ 0 Alarm2 Off , Alarm1 Off
x _ _ _ 1 Alarm2 Off , Alarm1 On
x _ _ _ 2 Alarm2 On , Alarm1 Off
x _ _ _ 3 Alarm2 On , Alarm1 On
x 0 0 0 _ ENB ,DIR ,PWM Output Off
(Autotune type 1: x010_ ~ x015_ use SV as target temperature)
x 0 1 0 _ Autotune SV
initial
x 0 1 1 _ Autotune SV
start ramping
x 0 1 2 _ Autotune SV
the first positive half cycle
x 0 1 3 _ Autotune SV t
he first negative half cycle
x 0 1 4 _ Autotune SV t
he second positive half cycle
x 0 1 5 _ Autotune SV
P.I.D in analyzing and calculating
(Autotune type 2: x020_ ~ x025_ use SV × 90% as target temperature)
x 0 2 0 _ Autotune 90% SV
initial
x 0 2 1 _ Autotune 90% SV
start ramping
x 0 2 2 _ Autotune 90% SV
the first positive half cycle
x 0 2 3 _ Autotune 90% SV t
he first negative half cycle
x 0 2 4 _ Autotune 90% SV t
he second positive half cycle
x 0 2 5 _ Autotune 90% SV
P.I.D in analyzing and calculating
x 0 3 0 _ Manual Output
x 0 4 0 _ General Control (
single point temperature control)
Programmable step temperature control (multipoint temperature control)
x 0 5 0 _ Program control Ramp 1
x 0 5 1 _ Program control Hold 1
x 0 5 2 _ Program control Ramp 2
x 0 5 3 _ Program control Hold 2
x 0 5 4 _ Program control Ramp 3
x 0 5 5 _ Program control Hold 3
x 0 5 6 _ Program control Ramp 4
x 0 5 7 _ Program control Hold 4
x 0 5 8 _ Program control Ramp 5
x 0 5 9 _ Program control Hold 5
x 0 5 A _ Program control Ramp 6
x 0 5 B _ Program control Hold 6
x 0 5 C _ Program control Ramp 7
x 0 5 D _ Program control Hold 7
x 0 5 E _ Program control Ramp 8
x 0 5 F _ Program control Hold 8
x 0 6 0 _ Hold (pause) Program control
x 1 0 0 _ Error Message OPER (Error sensor input is OPEN)
x 2 0 0 _ Error Message ADER (Error in A/D converting)
x 3 0 0 _ Error Message EPER (memory error)
x 4 0 0 _ Error Message ATER (auto tune error)
x 5 0 0 _ Error Message HIER (PV higher than HILT)
x 6 0 0 _ Error Message LOER (PV lower than LOLT)
Code
x1004 RAMP_TL Tim passed at script programming during ramping or soaking Sec/Min

Accuthermo Technology Corp. 17
x1005 RAMP_TH
x1006 ALM1_TL Time left when using delay alram Sec/Min
x1007 ALM1_TH
x1008 SV0 SV + SVOF (fixed 1 decimal point) °C/°F/ ENG
x1009 PV0 PV value (fixed 1 decimal point) °C/°F/ ENG
x100A PV1 PV history value1 (fixed 1 decimal point) °C/°F/ ENG
x100B PV2 PV history value2 (fixed 1 decimal point) °C/°F/ ENG
x100C ET0 SV – Pv value (fixed 1 decimal point) °C/°F/ ENG
x100D ET1 SV - PV history value1 (fixed 1 decimal point) °C/°F/ ENG
x100E ET2 SV - PV history value2 (fixed 1 decimal point) °C/°F/ ENG
x100F Px Proportional factor %
x1010 Ix Integral factor Sec
x1011 Dx Differential factor Sec
x1012 MRx MR factor %
x1013 ARx AR factor %
x1014 Pout Proportional output % %
x1015 Iout Integral output % %
x1016 Dout Differential output % %
x1017 Pband Proportional band °C/°F/ ENG
x1018 ARW Integral band °C/°F/ ENG
x1019 LEVEL
Code
x101A AD0 A/D 0 after filter Count Count
x101B AD1 A/D 1 after filter Count Count
x1F00 VER Hardware & Firmware version Code
x1F01
x1F02
SERIAL_NH
SERIAL_NL
Product Model number Code

Accuthermo Technology Corp. 18
4.3 Read[x03]/Write[x06] Parameter Table
Read/Write-able Parameters: The following parameter’s data can be changed or just be read out
without change.
Addres
s Naming
Range Init Value
Unit
x0000 SV LOLT ~HILT 20.0 °C/°F
x0001 OUTL -100.0 ~ 100.0 0.0 %
x0002 ENAB
x0000 / OFF (Turn off output)
OFF Index
Code
x0001 / AT1 (auto-tune at SV)
x0002 / AT2 (auto-tune at 90% of SV )
x0003 / MPWR (Manual set duty cyl)
x0004 / SPON (Single Temp point ctrl)
x0005 / PROG (Run Programmable temp profile)
x0006 / HOLD (Hold Temp during prog profile run )
x0003 PB1 0.00 ~ 300.00 5.0 %
x0004 TI1 0 ~ 4500 240 100mSec
x0005 TD1 0~ 1125 60 100mSec
x0006 MR1 0.0 ~ 51.0 0.0 %
x0007 AR1 0.0 ~ 100.0 50.0 %
x0008 ASP1 LOLT ~HILT
(region-1 PID range ex. <0~50.0C) 50.0 °C/°F
x0009 PB2 0.00 ~ 300.00 5.0 %
x000A TI2 0 ~ 4500 240 100m Sec
x000B TD2 0~ 1125 60 100m Sec
x000C MR2 0.0 ~ 51.0 0.0 %
x000D AR2 0.0 ~ 100.0 50.0 %
x000E ASP2 LOLT ~HILT
(region-2 PID range ex. <50.1~100.0C) 100.0 °C/°F
x000F PB3 0.00 ~ 300.00 5.0 %
x0010 TI3 0 ~ 4500 240 100m Sec
x0011 TD3 0~ 1125 60 100m Sec
x0012 MR3 0.0 ~ 51.0 0.0 %
x0013 AR3 0.0 ~ 100.0 50.0 %
x0014 ASP3 LOLT ~HILT
(region-3 PID range ex. <100.1~150.0C) 150.0 °C/°F
x0015 PB4 0.00 ~ 300.00 5.0 %
x0016 TI4 0 ~ 4500 240 100m Sec
x0017 TD4 0~ 1125 60 100m Sec
x0018 MR4 0.0 ~ 51.0 0.0 %
x0019 AR4 0.0 ~ 100.0 50.0 %
x001A A1SP LOLT ~HILT (Alarm 1 set point) 100.0 °C/°F
x001B A1HY -200.0 ~ 200.0 (value for alarm region or delta-t ) 0.0 °C/°F
x001C A1FU
x0007 / OFF ( alarm not activate)
OFF Index
Code
x0008 / HI (alarm on when >A1SP)
x0009 / LO (alarm on when <A1SP)
x000A / DIFH (alarm on when >delta)
x000B / DIFL (alarm on when <delta)
x000C / BDHI (alarm on when out off region)
(alarm on when exit region)
x000D / BDLO (alarm on when PV within region)
x001D A1MD
x000E / NONE (Alarm run in normal condition)
(Alarm on
normal condition)
NONE Index
Code
x000F / STDY (Ignore first alarm)
x0010 / LATH (turn alarm on when latch)

Accuthermo Technology Corp. 19
x0011 / STLA
(Ignore first alarm and turn next alarm on when latch)
x001E A1DT 9999 ~ 0 (delay time to turn alarm on) 0 Sec/Min
x001F A1AB x0012 / ALNO (alarm normal open_L ,when latch turn H) ALNO Index
Code
x0013 / ALNC(alarm normal close_H ,when latch turn L)
x0020 A1ER
x0014 / NONE (controller keep running if alarm is latch)
NONE Index
Code
x0015 / STOP (controller off if alarm is latch)
x0021 A2SP LOLT ~HILT (Alarm 2 set point) 100.0 °C/°F
x0022 A2HY -200.0 ~ 200.0 (value for alarm region or delta-t ) 0.0 °C/°F
x0023 A2FU
x0007 / OFF ( alarm not activate)
OFF Index
Code
x0008 / HI (alarm on when >A2SP)
x0009 / LO (alarm on when <A2SP)
x000A / DIFH (alarm on when >delta)
x000B / DIFL (alarm on when <delta)
x000C / BDHI (alarm on when out off region)
(alarm on when exit region)
x000D / BDLO (alarm on when PV within region)
x0024 A2MD
x000E / NONE (Alarm run in normal condition)
(Alarm on normal condition)
NONE Index
Code
x000F / STDY (Ignore first alarm)
x0010 / LATH (turn alarm on when latch)
x0011 / STLA
(Ignore first alarm and turn next alarm on when latch)
x0025 A2DT 9999 ~ 0 (delay time to turn alarm on) 0 Sec/Min
x0026 A2AB x0012 / ALNO(alarm normal open_L ,when latch turn H) ALNO Index
Code
x0013 / ALNC(alarm normal close_H ,when latch turn L)
x0027 A2ER
x0014 / NONE (controller keep running if alarm is latch)
NONE Index
Code
x0015 / STOP (controller off if alarm is latch)
X0028 TYPE
x0016 / J
TR1 Index
Code
x0017 / K
x0018 / T
x0019 / DPT
x001A / TR1 (2.252K)
x001B / TR2 (10K)
x0037 / mA (option* of new firmware)
x0038 / mV (option* of new firmware)
X0039 / V (option* of new firmware)
x0029 UNIT
x001C / °C
°C Index
Code
x001D / °F
x003E / ENG
x002A DP
x001E / 0000. (no decimal pt)
DP 1 Index
Code
x001F / 000.0 (one decimal pt)
x003F / 00.00 (two decimal pt, option* of new firmware)
x0040 / 0.000 (three decimal pt, option* of new firmware)
x002B DIR x0020 / REV (TE output direction rev) REV Index
Code
x0021 / FWD (TE output direction forward)
x002C LOLT
TYPE
Range
0.0 °C/°F
J /K /T
-70.0°C ~ 200.0°C
DPT -70.0 °C ~ 200.0°C
TR1
(2.252K
-30.0 °C ~ 150.0°C

Accuthermo Technology Corp. 20
TR2
(10K)
-10.0 °C ~ 150.0°C
x002D HILT Same as LOLT parameters 200.0 °C/°F
x002E TUNT x0022 / Sec (controller time unit in sec) Sec Index
Code
x0023 / Min (controller time unit in min)
x002F EROP
(Select output operation when alarm latch)
x0024 / 00 (Alarm1 & Alarm2 OFF, PWM & ENB OFF)
00 Index
Code
x0025 / 01 (Alarm1 ON, Alarm2 OFF, PWM & ENB ON)
x0026 / 10 (Alarm1 ON, Alarm2 ON, PWM & ENB OFF)
x0027 / 11 (Alarm1 ON ,Alarm2 ON, PWM & ENB OFF)
x0030 SPOF -200.0 ~ 200.0
(set-point offset) 0.0 °C/°F
x0031 PVOF -200.0 ~ 200.0
(process-value offset) 0.0 °C/°F
x0032 FILT 0.0 ~ 99.9 (noise filter, larger value filter noise better but delay process
operation) 0.0
Coefficient
x0033 ID 255 ~ 1 (controller ID address) 255 address
x0034 STAT x0028 / OFF (don't save position) OFF Index
Code
x0029 / ON (save current position)
x0035 STAR
x002A / ZERO
(run program start SV-t from 0C)
PV Index
Code
x002B / PV
(run program start SV-t from current PV)
x0036 BAND 0.0 ~ 200.0 20.0 °C/°F
x0037 RT1 0 ~ 9999 (Ramp Time) 60 Sec/Min
x0038 SP1 LOLT ~HILT (1
st
Set Point Value) 20.0 °C/°F
x0039 ST1 0 ~ 9999 (1
st
SP Sock Time) 60 Sec/Min
x003A SF1
x002C / RT8 (after ST time jump to RT8)
END Index
Code
x002D / RT7 (after ST time jump to RT7)
x002E / RT6 (after ST time jump to RT6)
x002F / RT5 (after ST time jump to RT5)
x0030 / RT4 (after ST time jump to RT4)
x0031 / RT3 (after ST time jump to RT3)
x0032 / RT2 (after ST time jump to RT2)
x0033 / RT1 (after ST time jump to RT1)
x0034 / END (After prog turn off output)
x0035 / HOLD (After prog hold temperature)
x0036 / NEXT (After prog goto RT2)
x003B LN1
1~9998 (x270E) Loop number
Infinite loop = 9999 (x270F) 1 count
x003C RT2 0 ~ 9999 60 Sec/Min
x003D SP2 LOLT ~HILT 20.0 °C/°F
x003E ST2 0 ~ 9999 60 Sec/Min
x003F SF2
x002C / RT8 (after ST time jump to RT8)
END Index
Code
x002D / RT7 (after ST time jump to RT7)
x002E / RT6 (after ST time jump to RT6)
x002F / RT5 (after ST time jump to RT5)
x0030 / RT4 (after ST time jump to RT4)
x0031 / RT3 (after ST time jump to RT3)
x0032 / RT2 (after ST time jump to RT2)
x0033 / RT1 (after ST time jump to RT1)
x0034 / END (After prog turn off output)
x0035 / HOLD (After prog hold temperature)
x0036 / NEXT (After prog goto RT3)
x0040 LN2
1~9998 (x270E) Loop number
Infinite loop = 9999 (x270F) 1 count
Table of contents
Popular Temperature Controllers manuals by other brands

Liquidyn
Liquidyn T10 Brief instructions

Ketotek
Ketotek STC-1000 operating manual

Panasonic
Panasonic CZ-64ESMC3 operating instructions

Advanced Power technologies
Advanced Power technologies TTC-1000 instruction & operation manual

STIEBEL ELTRON
STIEBEL ELTRON RTF-TC instructions

Full Gauge Controls
Full Gauge Controls TC-940Ri plus manual

Siemens
Siemens RLE162 installation instructions

Dometic
Dometic CoolAir SP950C installation manual

Shangfang
Shangfang SF-104S-2 quick guide

dixell
dixell XH260L operating instructions

Mitsubishi Electric
Mitsubishi Electric PAC-USSEN001-FM-1 Installation instructions manual

PMA
PMA KS 94 PROFIBUS-DP quick start guide