Endress+Hauser RIA452 User manual

Products Solutions Services
BA00265R/09/EN/13.13
71212732
Software version
2.01.xx
Operating Instructions
RIA452
Panel meter
RIA452 Endress+Hauser
2573
m³/min

Endress+Hauser
Brief overview
For rapid and easy commissioning:
Block circuit diagram
G09-RIA452xx-05-00-xx-en-000
Fig. 1: RIA452 block circuit diagram
Safety instructions →ä4
▾
Installation →ä7
▾
Wiring →ä9
▾
Display and operating elements →ä17
▾
Commissioning →ä20
Device configuration - explanation and use of all the configurable
device functions with the associated value ranges and settings.

RIA452
Endress+Hauser 3
Table of Contents
1 Safety instructions . . . . . . . . . . . . . . . . . . 4
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Installation, commissioning and operation . . . . . . 4
1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.5 Notes on safety conventions and icons . . . . . . . . . 5
2 Identification . . . . . . . . . . . . . . . . . . . . . . 6
2.1 Device designation . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3 Certificates and approvals . . . . . . . . . . . . . . . . . . . . 7
3 Installation . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 Installation instructions . . . . . . . . . . . . . . . . . . . . . . 7
4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.1 Quick wiring guide . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.2 Connecting the device . . . . . . . . . . . . . . . . . . . . . 12
4.3 Post-connection check . . . . . . . . . . . . . . . . . . . . . 13
5 Operation. . . . . . . . . . . . . . . . . . . . . . . . . 14
5.1 Quick operation guide . . . . . . . . . . . . . . . . . . . . . 14
5.2 Display and operating elements . . . . . . . . . . . . . 17
5.3 Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6 Commissioning. . . . . . . . . . . . . . . . . . . . 20
6.1 Function check . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.2 Switching on the measuring device . . . . . . . . . . 20
6.3 Device configuration . . . . . . . . . . . . . . . . . . . . . . . 20
7 Maintenance. . . . . . . . . . . . . . . . . . . . . . 41
8 Accessories . . . . . . . . . . . . . . . . . . . . . . . 41
9 Troubleshooting. . . . . . . . . . . . . . . . . . . 42
9.1 Troubleshooting instructions . . . . . . . . . . . . . . . . 42
9.2 Process error messages . . . . . . . . . . . . . . . . . . . . 42
9.3 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
9.4 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
9.5 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
10 Technical data . . . . . . . . . . . . . . . . . . . . 45
10.1 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
10.2 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
10.3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
10.4 Mechanical construction . . . . . . . . . . . . . . . . . . . 52
10.5 Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . 53
10.6 Certificates and approvals . . . . . . . . . . . . . . . . . . 54
10.7 Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
11 Appendix . . . . . . . . . . . . . . . . . . . . . . . . 55
11.1 Flow conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

Safety instructions RIA452
4Endress+Hauser
1 Safety instructions
Safe operation of the panel meter is only guaranteed if these Operating Instructions have
been read and the safety instructions have been observed.
1.1 Designated use
The panel meter analyzes analog process variables and depicts them on its multicolored
display. Processes can be monitored and controlled using analog and digital outputs and
limit relays. The device provides the user with a wide range of software functions for this
purpose.
Power can be supplied to 2-wire sensors with the integrated transmitter power supply.
– The device is seen as an associated electrical apparatus and may not be installed in
hazardous areas.
– The manufacturer does not accept liability for damage caused by improper or non-
designated use. The device may not be converted or modified in any way.
– The device is designed for installation in a panel and may only be operated in an installed
state.
1.2 Installation, commissioning and operation
This device has been constructed to state-of-the-art technology and meets all applicable
standards and EU directives. The device, however, can be a source of application-related
danger if used improperly or other than intended.
Installation, wiring, commissioning and maintenance of the device must only be carried out
by trained technical personnel. They must have read and understood these Operating
Instructions and must follow the instructions they contain. The information in the electrical
wiring diagrams (see Section 4 'Wiring') must be observed closely.
1.3 Operational safety
Technical improvement
The manufacturer reserves the right to adapt technical details to the most up-to-date
technical developments without any special announcement. Contact your local sales center
for information about the current state of and possible extensions to the Operating
Instructions.
1.4 Return
For a return, e.g. in case of repair, the device must be sent in protective packaging. The
original packaging offers the best protection. Repairs must only be carried out by your
supplier's service organization.
Please enclose a note describing the fault and the application when sending the unit
in for repair.

RIA452 Safety instructions
Endress+Hauser 5
1.5 Notes on safety conventions and icons
Always refer to the safety instructions in these Operating Instructions labeled with the
following symbols:
Symbol Meaning
A0011190-EN
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation
can result in serious or fatal injury.
A0011191-EN
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation
can result in minor or medium injury.
A0011192-EN
NOTICE!
This symbol contains information on procedures and other facts which do not
result in personal injury.
ESD - Electrostatic discharge
Protect the terminals against electrostatic discharge. Failure to comply with
this instruction can result in the destruction of parts or malffunction of the
electronics.
A0011193
Indicates additional information, Tip

Identification RIA452
6Endress+Hauser
2 Identification
2.1 Device designation
2.1.1 Nameplate
Compare the nameplate on the device with the following diagram:
G09-RIA452xx-18-00-xx-xx-000
Fig. 2: Nameplate of the panel meter (example)
1 Order code and serial number of the deviceTab/
2 Power supply
3 Software version number
4 Ambient temperature
5Performance
2.2 Scope of delivery
The scope of delivery of the panel meter comprises:
• Panel meter for panel mounting
• Multilanguage Brief Operating Instructions as hard copy
• Operating Instructions on CD-ROM
• CD-ROM with PC configuration software and interface cable RS232 (optional)
• Fixing clips
• Sealing ring
Please note the device accessories in Section 8 'Accessories' in the Operating
Instructions.

RIA452 Installation
Endress+Hauser 7
2.3 Certificates and approvals
CE mark, declaration of conformity
The panel meter is designed to meet state-of-the-art safety requirements, has been tested
and left the factory in a condition in which it is safe to operate. The device meets the relevant
standards and directives as per IEC 61 010-1 "Safety requirements for electrical equipment
for measurement, control and laboratory use".
The device described in these Operating Instructions thus meets the legal requirements of
the EU directives. The manufacturer confirms that the device has been tested successfully by
affixing the CE mark.
3Installation
3.1 Installation
The permitted ambient conditions (see Section 10 "Technical data" in the Operating
Instructions) must be observed when installing and operating. The device must be protected
against the effects of heat.
3.1.1 Dimensions
Please note the installation depth of 150 mm (5.91 in) for the measuring device plus cable.
Additional dimensions are provided in →å3 and Section 10 "Technical data" in the
Operating Instructions.
3.1.2 Mounting location
Installation in panel with cutout 92x92 mm (3.62x3.62 in) (as per 'EN 60529'). The
mounting location must be free from vibrations.
3.1.3 Orientation
Horizontal +/- 45° in every direction.
3.2 Installation instructions
The required panel cutout is 92x92 mm (3.62x3.62 in). Please note the installation depth of
150 mm (5.91 in) for the measuring device plus cable.

Installation RIA452
8Endress+Hauser
G09-RIA452xx-17-01-06-xx-001
Fig. 3: Installation in panel
1. Push the device with the sealing ring (item 1) through the panel cutout from the front.
2. Keep the device horizontal and suspend the two fixing clips (item 2) in the recesses
provided.
3. Tighten the screws of the fixing clips evenly with a screwdriver.
4. Remove the protective strip from the display.
The dimensions of the panel meter are provided in the "Technical data" section of the
Operating Instructions.

RIA452 Wiring
Endress+Hauser 9
4 Wiring
4.1 Quick wiring guide
G09-RIA452ZZ-04-01-xx-en-000
Fig. 4: Terminal assignment of the panel meter (universal input
→
Page 11)
Terminal assignment
Termin
al
Terminal assignment Type
L/L+ L for AC
L+ for DC
Power supply
N/L- N for AC
L- for DC
NC Not connected
J1 Jumper for locking device operation via
hardware. If the jumper is set to J1, the
configuration cannot be modified.
The device can always be configured with
the PC software via RS232 even if the
jumper is set to J1.
J2 Not connected
11 + 0/4 to 20 mA signal Current input
12 Signal ground (current)

Wiring RIA452
10 Endress+Hauser
81 24 V sensor power supply 1 Transmitter power supply
(optionally intrinsically safe)
82 Ground, sensor power supply 1
41 Normally closed (NC)
Relay 142 Common (COM)
43 Normally open (NO)
51 Normally closed (NC)
Relay 252 Common (COM)
53 Normally open (NO)
44 Normally closed (NC)
Relay 345 Common (COM)
46 Normally open (NO)
54 Normally closed (NC)
Relay 455 Common (COM)
56 Normally open (NO)
141 Normally closed (NC)
Relay 5 (optional)142 Common (COM)
143 Normally open (NO)
151 Normally closed (NC)
Relay 6 (optional)152 Common (COM)
153 Normally open (NO)
144 Normally closed (NC)
Relay 7 (optional)145 Common (COM)
146 Normally open (NO)
154 Normally closed (NC)
Relay 8 (optional)155 Common (COM)
156 Normally open (NO)
96 Ground for digital status inputs
Digital inputs
97 + digital status input 1
197 + digital status input 2
297 + digital status input 3
397 + digital status input 4
Termin
al
Terminal assignment Type

RIA452 Wiring
Endress+Hauser 11
Universal input option
The device can be optionally equipped with a universal input instead of a current input.
G09-RIA452xx-04-10-xx-en-002
Fig. 5: Universal input terminal assignment
Terminal assignment
31 + analog output
Analog output (optional)
32 Ground, analog output
33 + digital output
Digital output (optional)
34 Ground, digital output
91 24 V sensor power supply 2
Transmitter power supply
92 Ground, sensor power supply 2
Termin
al
Terminal assignment Type
Terminal Terminal assignment
11 + 0/4 to 20 mA signal
12 Signal ground (current, voltage, temperature)
13 + 1 V, + thermocouples, - resistance thermometer signal (3/4 wire)
15 + resistance thermometer signal (4-wire)
17 + 30 V
19 + resistance thermometer power supply (3-wire/4-wire)

Wiring RIA452
12 Endress+Hauser
4.2 Connecting the device
CAUTION
!
Danger through electric tension
‣Do not install or wire the device when it is connected to the power supply.
4.2.1 Connecting the power supply
NOTICE
Damage to device through wrong supply voltage
‣Before wiring the device, ensure that the supply voltage corresponds to the specification
on the nameplate.
‣For the 90 to 250 V AC version (power supply connection), a switch marked as a
separator, as well as an overvoltage organ (rated current ≤10 A), must be fitted in the
supply line near the device (easy to reach).
G09-RIA452xx-04-10-xx-xx-000
Fig. 6: Connecting the power supply
4.2.2 Connecting external sensors
Current input 0/4 to 20 mA
G09-RIA452xx-04-10-xx-en-001
Fig. 7: Connection of the two-wire sensor to the current input 0/4 to 20 mA
Active and passive sensors with analog, TC, resistance and RTD sensors can be
attached to the device.
Depending on the type of signal of the sensor in question, the terminals can be freely
selected.

RIA452 Wiring
Endress+Hauser 13
Universal input
G09-RIA452xx-04-10-xx-en-003
Fig. 8: Connection of the four-wire sensor, transmitter power supply and universal input
4.3 Post-connection check
Device condition and specifications Notes
Is the device or cable damaged (visual inspection)? -
Electrical connection Notes
Does the supply voltage match the specifications on the nameplate? 90 to 250 V AC (50/60 Hz)
20 to 36 V DC
20 to 28 V AC (50/60 Hz)
Are all of the terminals firmly engaged in their correct slots? Is the
coding on the individual terminals correct?
-
Are the mounted cables strain relieved? -
Are the power supply and signal cables correctly connected? See wiring diagram on the
housing
Are all screw terminals firmly tightened? -

Operation RIA452
14 Endress+Hauser
5Operation
5.1 Quick operation guide
M1 Analog input
INPUT
Signal typeConnection type* Curve Signal damping
Signal type Connection Curve Damp
Dimension Decimal point 0% value 100% value
Dimension Dec. point 0% value 100% value
Offset Comparat.
temperature*
Fixed comparat.
temp.*
Open circuit
detection
Offset Comp. temp. Const. temp. Open circ.
M2 Display
DISPLAY.
Assign numerical
display
Alternating display Assign bargraph Decimal point
bargraph
Ref. num. Displ. sw. Ref. bargraf Dec. point
Bargraph 0% value Bargraph 100%
value
Assign bargraph
Bar 0% Bar 100% Ref. bargraf
M3 Analog output*
ANALOG OUT
Assignment Damping Output range Decimal point
Ref. num. Out damp Out range Dec. point
0% value 100% value Offset Output in the event
of a fault
Out 0% Out 100% Offset Fail mode
Value in the event of
a fault
Simulation mA Simulation Volt
Fail value Simu mA Simu V
M5 Digital input 1-4
DIGITAL INP.
Function digital input
1-4
Active level 1-4 Pump monitoring
sampling time
Function Level Sampl. time
*) Only available if the option in question is installed in the device

RIA452 Operation
Endress+Hauser 15
M10-
M17
Limit 1-4 (8)*
LIMIT
Assignment Function 1-4 (8) Decimal point Switch point A Switch point B
Ref. num Function Dec. point Setpoint A Setpoint B
Hysteresis or switch-
back gradient
Switching delay1-4
(8) in seconds
Alternate function
1-4
Delay for 1st
switch-on every 24
h
Switch-on period
for switch-on every
24 h
Hysteresis Delay Alternate Sw. delay Sw. period
Display runtime 1-8 Display switch.
frequency 1-8
Reset switch.
frequency and
runtime
Relay simulation
Runtime Count Reset Simu relay
M18 Integration*
Integration
Signal source for
integration
Pre-
counter
Integration base Decimal point
factor
Conversion factor
Ref. Integr. Pre-counter Integr. base Dec. factor Factor
Dimension totalizer Decimal point
totalizer
Set pre-counter Set preliminary
alarm
Display totalizer
Dimension Dec. point T Set count A Set count B Totalizer
Reset totalizer Flow calculation Dimension of input
signal
Dimension of
linearized value
Decimal point for
formula
Reset total Calc flow Dim. Input Dim. flow Dec. flow
Decimal point for
display
Alpha value Beta value Gamma value C value
Dec. point Alpha Beta Gamma C
Khafagi- Venturi
channels
Iso-Venturi
channels
Venturi channels as
per British Standard
Parshall
channels
Parshall-
Bowlus
channels
Kha Venturi Iso-Venturi BST-Venturi Parshall Parshall-Bow
Rectangular weirs Rectangular weirs
with constriction
Rectangular weirs
as per NFX
Rectangular weirs
as per NFX with
constriction
Trapezoid. weirs
Rect. WTO Rect. WThr NFX Rect. WTO NFX Rect. WThr Trap. WTO
Triangular
weirs
Triangular weirs as
per British Standard
Triangular weirs as
per NFX
Width
V. weir BST V. weir NFX V. weir width
M19 Pulse output*
PULSE OUT
Decimal point pulse
value
Pulse value Pulse width Simulation pulse
output
Dec value Unit Value Pulse width Sim pulseout
*) Only available if the option in question is installed in the device

Operation RIA452
16 Endress+Hauser
M20 Min/Max memory
MIN/MAX
Signal source for
Min/Max
Decimal point Display minimum
value
Ref. min/max Dec. point Min. value
Display maximum
value
Reset minimum
vaule
Reset maximum
value
Max. value Reset min Reset max
M21 Linearizationtable
LIN-TABLE
Number of support
points
Dimension of
linearized value
Decimal point Y-
axis
Delete all support
points
Display all support
points
Counts Dimension Dec. Y value Del points Show points
M23-
Mxx
Lin. support points
NO 01 NO 32
X-axis Y-axis
X value Y value
M55 Operating
parameters
PARAMETERS
User code Limit value lock Program name Program version Pump alternation
function
User code Limit lock Prog. name Version Func. alt.
Relay lock time Relay failsafe mode Time for gradient
evaluation
Failsafe mode 4-20
mA input
Error limit 1
Lock time Rel. Mode Grad. Time Namur Range 1
Error limit 2 Error limit 3 Error limit 4 Display contrast
Range 2 Range 3 Range 4 Contrast
M56 SERVICE Only for service staff. The service code must be entered.
M57 EXIT Exit the menu. If you have changed parameters, you are asked whether you want to save the changes.
M58 SAVE Changes are saved and you exit the menu.
*) Only available if the option in question is installed in the device

RIA452 Operation
Endress+Hauser 17
5.2 Display and operating elements
5.2.1 Display
Relay display
No power to relay: no display
Power to relay: (symbol lit)
Remove the protective strip from the display as this restricts display legibility
otherwise.
Range Display Relay Analog output Integration
Input current is
below the lower
error limit
Display " " Fault condition Set failsafe mode No integration
Input current above
lower error limit
and below lower
limitations of
validity
Display " " Normal limit value
behavior
Normal behavior
with max. 10%
overrange. No
output<0mA/0V
possible
Normal behavior
(negative
integration not
possible)
Input current in
valid range
Display scaled
measured value
Normal limit value
behavior
Normal behavior
with max. 10%
overrange. No
output<0mA/0V
possible
Normal behavior
(negative
integration not
possible)
Input current below
upper error limit
and above upper
limitations of
validity
Display " " Normal limit value
behavior
Normal behavior
with max. 10%
overrange. No
output<0mA
possible.
Normal behavior
(negative
integration not
possible)
Input current above
upper error limit
Display " " Fault condition Set failsafe mode No integration

Operation RIA452
18 Endress+Hauser
Digital input status display
Digital input configured: (green)
Signal at digital input: (yellow)
5.3 Local operation
Operating menu activated by pressing the jog/shuttle dial for 3 seconds at least.
5.3.1 Operation via the jog/shuttle dial
A) 3-key function
B) Selection from list
5.3.2 Entering text
G09-RIA452ZZ-19-00-00-en-001
Fig. 11: Text entry
Information on troubleshooting can be found in Sections 9.1 and 9.2 of the
Operating Instructions.
G09-RIA452ZZ-19-00-00-xx-002
Fig. 9: Operation via jog/shuttle dial
• Press = "Enter"
• Rotate in clockwise direction = "+"
• Rotate in counterclockwise direction = "-"
G09-RIA452ZZ-19-00-00-xx-003
Fig. 10: Selecting from list via jog/shuttle dial
▾Arrow pointing down:
Option is at the top of the picklist. The other entries become visible
when the jog/shuttle is turned in the clockwise direction.
▴
▾
Both arrows visible:
User is in the middle of the picklist.
▴Arrow pointing up:
The end of the picklist is reached. The user moves back towards the
start when the jog/shuttle is turned in the counterclockwise
direction.

RIA452 Operation
Endress+Hauser 19
Possible characters
The following characters can be entered:
Space +ABCDEFGHIJKLMNOPQRSTUVWXYZabcdefghijklmnopqrstuvwxyz0123456789/
\%°23+-.;:*() followed by return symbol (arrow to left)
5.3.3 Disabling the programming mode
User code
The configuration can be protected against unintentional access by means of a four-digit
code. This code is defined in menu item 55 "Parameter/user code". All the parameters remain
visible but can only be changed after entering the user code.The "key" symbol is shown on the
display. If the limit values are also to be locked, the "Limit code" must be set to "On" in menu
item 55. Limit values can then only be changed after entering the user code. If the limit code
is set to "Off", limit values can be changed without entering the user code. All the other
parameters are locked, however.
Hardware locking
In addition, configuration can also be locked using a connector on the rear of the device (see
drawing). This is indicated by the "padlock" symbol on the display.
To hardware-lock the measuring device, insert the jumper into position J1 in the top right-
hand corner on the rear of the device.
G09-RIA452ZZ-19-00-00-xx-004
Fig. 12: Position of the jumper on the rear of the device
Item
No.
Description
1 Activate the operating menu by pressing the jog/shuttle dial for at least 3 seconds. The
first character then starts flashing.
2 You can change the flashing (selected) character by turning the jog/shuttle dial (see
"Possible characters" in the next paragraph). You can go back to the previous character
by selecting the back symbol (arrow to left).
3 Press the jog/shuttle dial to accept the selected character and to switch to the next
character.
4 Press the jog/shuttle dial briefly for the last character to accept the entry.
5 Press the jog/shuttle dial for longer than 1 second (max. 2 seconds) to reject the entry
at the point in question.
The hardware lock does not affect the PC operating software.

Commissioning RIA452
20 Endress+Hauser
6 Commissioning
6.1 Function check
Make sure that all post-connection checks have been carried out before you commission
your device:
• Checklist Section 4.3 'Post-connection check'
6.2 Switching on the measuring device
Once the operating voltage is applied, the green LED indicates that the instrument is
operational.
• When the unit is delivered, the device parameters are used as per the factory settings.
• When commissioning a device already configured or preset, measuring is immediately
started as per the settings. The limit values only switch once the first measured value has
been determined.
• The limit values are only activated as per their configuration once a valid measured value
is present.
6.3 Device configuration
This section describes all the configurable instrument parameters with the associated value
ranges and factory settings (default values, marked in bold).
6.3.1 Analog input - INPUT/M1
All the parameters that can be selected for the input can be found under the analog input
menu item which is marked as INPUT in the device.
Remove the protective strip from the display as this restricts display legibility
otherwise.
Function
(menu
item)
Parameter setting Description
Signal type 4 - 20 mA
0 - 20 mA
0 - 5 mA (*)
0 - 100 mV (*)
0 - 200 mV (*)
0 - 1 V (*)
0 - 10 V (*)
± 150 mV (*)
± 1 V (*)
± 10 V (*)
± 30 V (*)
Type B (IEC584) (*)
Type J (IEC584) (*)
Type K (IEC584) (*)
Type L (DIN43710) (*)
Type L (GOST) (*)
Type N (IEC584) (*)
Type R (IEC584) (*)
Type S (IEC584) (*)
Type T (IEC584) (*)
Type U (DIN43710) (*)
Type D (ASTME998) (*)
Type C (ASTME998) (*)
Selects the signal type of the connected sensor.
Parameters marked with an asterisk (*) can only be
selected with the universal input option.
Other manuals for RIA452
9
Table of contents