Energomera CE208 User manual

СЕ208
САНТ.411152.068-05.1 РЭ
Operation Manual
Manufacturer:
Electrotechnical Factories Energomera JSC
415 Lenina Str., Stavropol, Russia 355029
Tel.: (8652) 35-75-27, Fax: 56-66-90,
Hot line (free): 8-800-200-75-27
e-mail: concern@energomera.ru
www.energomera.ru
Warranty service:
217 Gagarina street, Nevinnomyssk,
Stavropol region, 357106
Electric energy meter
Single-phase multifunctional
Case type S7
OKP 42 2863 6
Harmonized System Codes (TN VED) 9028301 100

2

2 3
CONTENTS
1 SAFETY REQUIREMENTS ....................................................................................................................................5
2.1 Purpose ............................................................................................................................................................... 6
2.2 Designation of meter modifications .................................................................................................................... 8
2.3 The meter is certified.......................................................................................................................................... 12
2.4 Normal operating conditions: .............................................................................................................................12
2.5 Operating usage conditions ...............................................................................................................................12
2.6 Ambient conditions ...........................................................................................................................................13
2.7 Technical specifications ..................................................................................................................................... 13
2.8 Meter design ..................................................................................................................................................... 18
3 PREPARING THE METER FOR OPERATION........................................................................................................ 19
3.1 Unpacking .........................................................................................................................................................19
3.2 Preparing for operation ......................................................................................................................................19
3.3 Installation procedure ........................................................................................................................................20
3.4 Wiring diagrams ................................................................................................................................................21
3.5 Lithium cell replacement .................................................................................................................................... 26
3.6 Meter configuration ........................................................................................................................................... 27
4 READING THE METER ..................................................................................................................................... 27
4.1 Displaying information on the LCD ....................................................................................................................27
4.2 Viewing total accumulated values (on an accrual basis) ......................................................................................29
5 METER VERIFICATION ..................................................................................................................................... 35
6 MAINTENANCE AND SEALING........................................................................................................................ 36

4
7 ROUTINE MAINTENANCE ...............................................................................................................................36
8 STORAGE AND TRANSPORTATION CONDITIONS ............................................................................................. 37
9 CONTAINERS AND PACKING ...........................................................................................................................38
10 LABELING .....................................................................................................................................................39
ANNEX A ...........................................................................................................................................................40
ANNEX B ........................................................................................................................................................... 41
ANNEX C ...........................................................................................................................................................42

4 5
This САНТ.411152.068-05.1 РЭ Operation Manual contains brief information about CE208 S7 multifunctional
single-phase electric energy meter (hereinafter referred to as the «Meter»). Complete information on the above
meter is contained in САНТ.411152.068-05.1 РП User Manual, which can be found at the manufacturer’s website:
www.energomena.ru/ru/products/meters/ce208-all.
When learning about the meter and operating it, you must be additionally guided by
САНТ.411152.068-03.1 ФО Data Sheet (supplied with the meter) and САНТ.411152.068-05.1 РП User Manual.
Only persons who have received special training for working with voltages up to 1000 V and who have studied
the Operation Manual are allowed to work with the meter.
1 SAFETY REQUIREMENTS
1.1 By operational safety, the meter meets the safety requirements of GOST 22261-94 and IEC 61010-1:2001.
1.2 Protection against electric shock is ensured through the use of double or reinforced insulation according
to IEC 61010-1:2001.
1.3 The insulation between all current and voltage circuits connected together and with the «ground» can
withstand a voltage of 4 kV AC at 50 Hz for 1 minute. During the test, the leads of the electrical test output device,
the interface circuits are connected to the «ground» (the «ground» is a conductive foil film enclosing the meter and
attached to a flat conductive surface on which the meter base is mounted).
1.4 The insulation between all current and voltage circuits connected together and with the «ground» can
withstand pulse voltage of 6 kV. During the test, the leads of the electrical test output device must be connected to
the «ground».
1.5 Insulation resistance between the casing and electrical circuits, at least:
20 MΩ — under conditions of clause 2.5;
7 MΩ – at an ambient air temperature (40±2) °С, relative air humidity of 93%.
1.6 The meter must be installed and operated in accordance with the applicable rules for technical operation of
electrical installations.
1.7 Do not put foreign objects on the meter, avoid bumps.

6
2 METER DESCRIPTION
2.1 Purpose
The meter is single-phase, multifunctional, direct connection, and is designed to measure active and reactive
electric energy in single-phase AC circuits.
The meter has the following functions:
• multi-tariff electricity metering (with three tariff levels - event-based, external and time-based tariffing);
• maintenance of the retrospective (recording the current values of energy storage devices: at the end of the
billing period (month), at the end of the day, at the end of the year and upon occurrence of a specific event);
• maintaining a load profile, with the ability to customize the type of the parameters stored and the averaging
time;
• measuring network parameters: voltage frequency, current in the phase and neutral wires, voltage, angle
between current and voltage, active power factor, active, reactive and apparent power;
• measuring Unified Power Quality Index (UPQI) in accordance with class «S» of the measurement process
specifications in IEC 61000-4-30:2008: stable voltage deviation, network frequency deviation, duration and depth
of voltage dips, duration and maximum value of overvoltage, interruptions in power supply;
• power quality analysis for compliance with quality standards in accordance with EN50160:2010;
• indicating the instance of violating an individual power quality indicator on the LCD (disabled by default);
• recording the violation of an individual power quality indicator (event logs available for reading on the interface);
• monitoring active power consumption;
• monitoring «instantaneous power» consumption;
• monitoring active energy consumption (control of energy limits, prepaid mode, low consumption control);
• monitoring supply network voltage;
• monitoring current;
• monitoring network frequency;
• monitoring the oncoming power flow (in the phase and neutral wires);

6 7
• telemetric output with the ability to use it as a «relay»;
• alarm using the interface (the ability to act as an initiator of communication with the level of DCU or HES during:
terminal cover opening; exposure to a magnetic field; reparameterization; maximum power excess; deviation
from the normalized value of voltage level, etc., in accordance with the full list, for details, see the user manual
САНТ.411152.068-05.1 РП);
• time accounting;
• self-diagnostics;
• information protection;
• protection against unauthorized opening (electronic seals);
• magnetic field sensor;
• event logs with recording of: terminal cover opening; case opening; dates of last re-programming; exposure
to a magnetic field causing unacceptable deviations of the metrological characteristics of the metering device;
facts of communication with the metering device that led to data changes; voltage deviations from the device’s
nominal values in the measuring circuits; results of self-diagnostics; changes in the current values of time and date
during time synchronization (at least 3,500 records using the DMLS protocol), etc., for details, see the user manual
САНТ.411152.068-05.1 РП;
• mechanism for flexible adjustment of the reaction to events occurring in the meter;
• DLMS/COSEM exchange protocol support;
• display of information on the LCD accompanied by OBIS codes;
• management of consumer load according to a predefined schedule.
The meter’s functions are described in detail in the full version of САНТ.411152.068-05.1 РП.
The meter can be used in Automatic Informational and Measuring Systems for Commercial Electric Power
Metering (AMI systems) to transfer the parameters measured or calculated to the control room for controlling,
accounting and distributing electric power.
The measurement results are obtained through processing and calculating current and voltage input signals
performed by the microprocessor circuit on the meter board. The measured data and other information are displayed

8
on a liquid crystal display (LCD) and can be transmitted via an optical port or one of the interfaces.
The meter has an electronic measuring mechanism performing active and reactive energy measurement in
kW•h and kVar•h, respectively, cumulatively and according to eight tariffs in one or two (for a bi-directional meter)
directions of electric energy metering.
The meter has two additional electronic measuring mechanisms performing active and reactive energy metering
in kW•h and kVar•h, respectively, in one or two (for a bi-directional meter) directions of electric energy metering by
specified events (tariff 9, tariff 10).
Changing time of the measuring mechanism indications complies with the requirements of IEC 62052-11:2003,
IEC 62053-21:2003 and IEC 62053-23:2003.
2.2 Designation of meter modifications
2.2.1 The structure of meter designation is shown in Figure 2.1.

8 9
СЕ 208 S7.Х4Х.Х.OХ.XXXX XXX
Designation of the integrated communication module
Additional functions:
See Table 2.3.
Integrated communication interfaces:
See Table 2.2.
Number of measuring elements:
1 – meter with one current sensor (in the phase circuit);
2 – meter with two current sensors (in the phase and neutral circuits);
Nominal or base (max.) current:
5 – 5(60) А;
6 – 5(100) А.
Nominal voltage (phase/line):
4 – 3x230/400 V.
Active/reactive energy accuracy class:
8 – 1/2 for active/reactive energy;
7 – 1/1 for active/reactive energy.
Body type and number:
S7 – for 3 screws mounting
Figure 2.1 – Designation structure

10
Table 2.1
Item No. Designation Interface
1 O Optical port
2 А RS485
3 P PLC interface
4 R1 Radio interface with a built-in antenna
5 R2 Radio interface with an external antenna socket
6 G GSM/GPRS modem
7 N Ethernet interface
Table 2.2
Item No. Designation Additional function
1 Q* Load control relay
2 Y* 2 directions of metering
3 U* Network parameters
4 V* Electronic seals
5 F* Magnetic field sensor
6L* LCD backlight
7 Z* Extended set of parameters
* — by default, included in all meter versions

10 11
2.2.2 Meter modifications, nominal voltage, the meter constant and the position of the decimal point when
displaying energy values on the LCD, depending on the nominal voltage (U
nom
), base (I
b
) and maximum (I
max
)
current, are shown in Table 2.1.
Table 2.3
Meter designation Nominal
voltage, V
Nominal, base
(max.) current, A
Meter constant
imp/(kW•h),
imp/(kVar•h)
Position
of the decimal
point
CE208 S7.845.X...X;
CE208 S7.745.X...X 230 5 (60) 2000 000000.00
CE208 S7.846.X...X;
CE208 S7.746.X...X 230 5 (100) 2000 000000.00
2.2.3 Example of a meter inscription
When ordering a meter, the required version is determined by the structure of the designation shown
in Figure 2.1.
A meter inscription example: accuracy class 1 meter for active energy and 2 for reactive energy (8), with nominal
voltage of 230 V (4), with base current 5 A and maximum current 60 A (5), with two current sensors (in the phase
and neutral channels) (2), with an optical port (O), with an RS485 interface (A), with a load control relay (Q), for
two measuring directions (Y), measuring power quality parameters (U), with a cover opening control (V), with a
magnetic field sensor (F), with an indicator backlight (L) and an extended set of parameters (Z):
Multifunctional single-phase electric meter
CE208 S7.845.2.OA.QYUVFLZ ТУ 4228-090-63919543-2012.

12
2.3 The meter is certified
The information on meter certification is given in the САНТ.411152.068-03.1 ФО Data Sheet
2.4 Normal operating conditions:
– ambient air temperature (23±2)°С;
– ambient air relative humidity (30-80)%;
– atmospheric pressure from 70 to 106.7 kPa (537-800 mm Hg).
– network frequency (50±0.5) Hz;
– the shape of the voltage curve of the measuring network is sinusoidal with a nonsinusoidal factor according to
EN50160:2010*.
2.5 Operating usage conditions
The meter is connected to a single-phase AC network and installed in closed premises with operating usage
conditions:
– temperature range from minus 45 to 70 °С
– ambient air relative humidity (30-98) %;
– atmospheric pressure from 70 to 106.7 kPa (537...800 mm Hg).
– network frequency (50±2.5) Hz;
– the shape of the voltage curve of the measuring network is sinusoidal with a nonsinusoidal factor according to
EN50160:2010*.
* ATTENTION! WHEN OPERATING METERS IN CONJUNCTION WITH A POWERFUL NON-LINEAR LOAD
WHICH CAN DEGRADE THE POWER QUALITY (FOR EXAMPLE, AN ELECTRIC DRIVE WITH A FREQUENCY
CONVERTER), YOU SHOULD USE SPECIAL FILTERING DEVICES.
OTHERWISE, THE METER MAY OVERHEAT AND FAIL. FAILURE OF THE METERS DUE TO POOR POWER
QUALITY IS NOT A WARRANTY CASE. THE MANUFACTURER IS NOT RESPONSIBLE FOR DAMAGE TO THE
CONSUMER’S PROPERTY RESULTING FROM VIOLATION OF THE OPERATING CONDITIONS OF THE METERS
DESCRIBED IN THIS OPERATION MANUAL, INCLUDING DUE TO A POOR POWER QUALITY.

12 13
2.6 Ambient conditions
2.6.1 In terms of resistance to climatic influences, the meter belongs to group 4 in accordance with
GOST 22261-94, with an extended range of temperature and humidity, satisfying version T category 3 in
accordance with GOST 15150-69.
In terms of resistance to mechanical impacts, the meter belongs to group 2 according to GOST 22261-94.
2.6.2 The meter is protected from dust and water. The protection degree of the meter is IP51 according to
IEC 60529:2013.
2.6.3 The meter is resistant against single impacts with a maximum acceleration of 300 m/s
2
.
2.6.4 The meter is resistant to vibrations in the frequency range (10-150) Hz.
2.6.5 The meter body withstands impact of spring hammer blows with kinetic energy (0.20±0.02) J applied to
the external surfaces of the body, including the windows, and to the terminal cover.
2.6.6 Parts and components of the meter that are designed for operation in areas with a tropical climate, in terms
of resistance to the effects of mold fungi, comply with the requirements of GOST 9.048-89.
The permissible growth of fungi amounts up to 3 points according to GOST 9.048-89.
2.7 Technical specifications
2.7.1 The meters meet the requirements of IEC 62052-11:2003, IEC 62053-21:2003 and IEC 62053-23:2003.
2.7.2 The technical specifications given with tolerances or limit values are considered guaranteed. Values without
tolerances are for reference only.
Main technical specifications are given in Table 2.4.
Limits of the permissible errors of the measured values are given in Annex A.

14
Table 2.4
Specification name Specification value Note
Base (max.) currents 5(60); 5(100) А Direct connection
Nominal phase voltage 230 V
Operating phase voltage (0.55...1.21) Unom V
Nominal network frequency (50±2.5) Hz
Non-sinusoidal factor of the measuring
network voltage, %, max –In accordance with
EN50160:2010
Sensitivity threshold 0,002 Ib
Number of decimal places on the LCD from Table 2.1
Apparent power consumed by each
current circuit, max
0.3 (V•A) for version Q
0.05(V•A) for others With nominal (base) current
Apparent (active) power (consumed by
voltage circuit at nominal voltage, max 9(V•A) (1.1 W) With nominal voltage
Active power consumed by the built-in
communication modules at the nominal
voltage value, max, W
3 W For versions with
communication modules
Limit of the clock basic absolute error ± 0.5 s/day
Manual and system correction, clock rate ± 29 s Once a day

14 15
Specification name Specification value Note
Limit of the clock additional
temperature error
± 0.15 s/°С per day From minus 10 to 45 °С
± 0.2 s/°C per day From minus 40 to minus 10 °С
and from 45 to 70 °С
Duration of data storage when
power is off 30 years
Built-in lithium cell service life 16 years
It is possible to install an
additional external lithium cell
(see section 3.5)
Additional external lithium cell service life 5 years
Number of tariffs in the daily schedule up to 8
Number of tariff zones in a day up to 16
Number of seasonal schedules in a year up to 12
Number of exclusive days up to 80
Number of daily rate scales up to 32
Number of power control zones in a day 3
Number of power control zone
schedules up to 12
Power averaging time 1; 2; 3; 4; 5; б; 10; 12; 15;
20, 30, 60 min
Table 2.4 (continued)

16
1The profile storage depth is directly proportional to the averaging time with reduction to the integer part.
Specification name Specification value Note
Number of accounted tariffs by events 2 Tariffs 9 and 10
Depth of monthly energy storage
by tariffs at least 40 months Current and 39 previous
Depth of daily energy storage,
accumulated by tariffs 128 days Current and 127 previous
Depth of annual energy storage,
accumulated by tariffs 10 years Current and 9 previous
Depth of event energy storage by tariffs 20 events
Depth of monthly maximum power
storage in the three power control zones 13 months Current and 12 previous
Number of parameters in a profile up to 6
Profile storage depth, days1 128 With an averaging time
of 60 minutes
Averaging time of load profiles 1; 2; 3; 4; 5; 6; 10; 12; 15;
20, 30, 60 min
Event logs For details, see
САНТ.411152.068-05.1 РП
Table 2.4 (continued)

16 17
Specification name Specification value Note
Nominal (permissible) voltage of
electrical pulse outputs, max 10 (24) V DC voltage
Nominal (permissible) current value of
electrical pulse outputs, max 10 (30) mA DC voltage
Duration of output pulses 35 ms In a TM mode
Interface communication speed From 300 to 19200 bd
Depending on the
characteristics of
communication modules
Optical port communication speed From 300 to 19200 bd
Meter update time 1 s
Reading time of any meter parameter
via interfaces
from 0.1 to 1000 s
(at 9600 bd) Depends on the parameter type
Initial start, max 5 s From the moment the voltage
is supplied
Meter weight, max 1 kg
Overall dimensions
(height; width; length), max 200; 122; 73;
Mean time to failure 220000 h
Table 2.4 (continued)

18
Specification name Specification value Note
Average service life 30 years
Meter cover and terminal block cover
opening control
Meter cover and terminal
cover opening logs
Protection against unauthorized access Meter password,
hardware lock
Maximum relay current during the turn-
off (turn-on) operation, does not exceed 1.1·Imax А
Switching wear resistance of relay
contacts 5000 cycles
2.8 Meter design
The meter design complies with the requirements of IEC 62052-11:2003 and the manufacturer’s drawings.
The meter is made in a plastic case.
The appearance of the meter is given in Annex B.
In general, the meter body consists of two parts, upper and lower, mating along the perimeter, a transparent window
and a removable transparent terminal cover.
On the front panel of the meter, there are the following:
• liquid crystal indicator;
• one indicator of active energy metering and one indicator of reactive energy metering. The indicators operate at the
frequency of the main transmitter. The indicators can be used to calibrate the meter.
• indicator of functioning;
Table 2.4 (continued)

18 19
• optical port elements;
• «FRAME» and «VIEW» buttons;
The clamps for connecting the meter to the network, to interface lines and to pulse outputs,
«ACCESS» button are closable with a plastic cover.
In order to access the «ACCESS» button (programming permission), you need to remove the sealing label of the energy
supplying company that installed the meter.
The meter comprises:
• measuring module;
• supply module;
• load control relay (Q) module;
• one or two current sensors (shunts), depending on the version.
3 PREPARING THE METER FOR OPERATION
The meter is supplied with a set of everything necessary for installation at operating site.
The САНТ.411152.068-05.1 РП has a comprehensive set of information for installing the meter at operating site.
3.1 Unpacking
3.1.1 After unpacking, inspect the meter visually, verify that there are no mechanical damages, and check
the presence and integrity of the seals.
3.2 Preparing for operation
3.2.1 The meters produced by the manufacturer have factory settings. Changes to factory settings are made in
accordance with the САНТ.411152.068-05.1 РП by companies authorized to configure the meter.
ATTENTION! PRESENCE OF READINGS ON THE METERING DEVICE IS CAUSED BY CHECKING THE METER
AT THE MANUFACTURER’S, AND DOES NOT ATTEST TO ITS WEAR OR OPERATION.

20
3.3 Installation procedure
3.3.1 Connect the electric meter to a single-phase AC network with a nominal voltage of 230 V. To do this, remove
the terminal cover and connect the wires by securing them in the terminals of the block according to the wiring
diagram printed on the cover, or given in Annex C.
When installing a meter, the wire (cable) must be stripped of insulation to approximately the amount shown in
Table 3.1. The stripped part of the wire should be smooth, without bends. Insert the wire into the terminal clamp
without tilts. It is not allowed to get a wire with insulation into the terminal, as well as for the stripped area to protrude
outside the block. First, tighten the top screw. Pull the wire lightly to make sure that it has been clamped. Then tighten
the bottom screw. After several minutes, tighten the connection again.
The diameter of the wires connected to the meter is shown in Table 3.1.
Таблица 3.1
Meter with a current range The length of the stripped wire, mm Wire cross-section diameter
2
, mm
5(60) А 27 (1 ÷ 7)
5(100) А 20 (1 ÷ 8)
If it is necessary to connect the meter into an AMI system, connect the signal wires to the interface outputs
in accordance with the wiring diagram.
Make sure that the time and date readings of the meter correspond to the actual values, otherwise set the date
and time (for details see САНТ.411152.068-05.1 РП).
Seal the covers and the «ACCESS» button.
Initialize the electronic seal of the clamp cover (see САНТ.411152.068-05.1 РП).
2The range of the wire diameter is specified based on the possibility of its connection to the meter block. The required cross-section
(and therefore the diameter) of the wire is selected depending on the value of the maximum current
Other manuals for CE208