INSTALLATION INSTRUCTIONS
DESCRIPTION
WIRING DIRECTIONS
3
WARNING
Turn the POWER OFF at the circuit breaker
before installing the sensor
Read and understand these instructions before installing. This device is
intended for installation in accordance with the National Electric Code and
local regulations. It is recommended that a qualified electrician performs this
installation. Make sure to turn off the circuit breaker or fuse(s) and make sure
power is off before wiring the device.
Use copper wire only.
The MPW-L provides a 150° coverage pattern. The coverage shown represents
walking motion at a mounting height of 10 feet. For building spaces with lower
levels of activity or with obstacles and barriers, coverage size may decrease.
The MPW-L passive infrared (PIR) occupancy sensors turn lighting on and off
based on occupancy and ambient light levels. The light level feature keeps lights
from turning on if the ambient light level is sufficient. The sensors can be
configured to turn lighting on, and hold it on as long as PIR technology detects
occupancy. After no movement is detected for the selected time delay, the lights
switch off.
The MPW-L operates on 24V supplied by the MPP-24 Power Packs (Not
Included)
C0VERAGE
MPW-L
150° Passive Infrared • Low Voltage
Occupancy Sensor
SPECIFICATIONS
Adjustable Time Delay.............................................................. 30 Sec. to 30 Min.
Operating Temperature ....................................................32°to 131°F (0°to 55°C)
PIR Adjustment..................................................................................25% to 100%
Adjustable Light Level .................................................................100 Lux -daylight
Voltage ...................................................................................................... 24VDC
Current Consumption....................................................................................40mA
Power Supply.................................................MPP-24 Power Pack (Not Included)
PIR Coverage................................................................................................900ft 2
Black
Red
Blue Control Out
+24V
Common
5. Restore power at circuit breaker or fuse, wait
6. Remove the small cover plate.
7. Locate the adjustment knob on the control panel to perform test
and adjustment.(illustrated as Figure 3. )
8. Replace the small cover plate after testing and adjustment.
one minute.
b. attach sensor switch to the mounting yoke with wires
3. Mount device up to walls or ceilings.
4. Gently position wires in wall/octagon box,
a. attach sensor switch to the box, and fix it to the wall/ceiling .
with two screws.
through its certral hole, and fix the yoke to the wall/ceiling.
1. Make sure that the power has been turned OFF at the circuit breaker.
2. Connect lead wires as WIRING DIAGRAM (see Figure 2): Black lead to
Common, Red lead to +24V, Blue lead to Control Out.
Wiring Diagram:
Figure 2
SETTINGS ADJUSTMENT
1
Figure 1
PIR coverage 50ft
Figure 3
Mounting Yoke
Detection LEDs
Red=PIR
PIR Lens
Control Panel Cover
TIME
LIGHT
RANGE
Ambient Light Level Adjustment Trimpot
Default position: Daylight (100% at position 4)
Adjustable: Clock wise
TIME Adjustment Trimpot
Default position: Time (Test at position 1)
Adjustable: 5 sec. to 30 mins (clockwise)
PIR Adjustment Knob
Default position: Center
Note: Turn toward right for greater room space.
Turn toward left to avoid false alert in smaller room and near
the door way or heat source.
456
TROUBLESHOOTING
© 2019 Enerlites Inc. CA,
U.S.A.
WWW.ENERLITES.COM
0207190146
WARRANTY INFORMATION
This device is warranted to be free of material and workmanship defects for 2 years from
the date of purchase. Original receipt or proof of purchase from an authorized retailer must
be presented upon warranty claim. ALL claims must be verified and approved by Enerlites,
Inc. Warranties from other Enerlites products may vary. This warranty is nontransferable
and does not cover normal wear and tear or any malfunction, failure, or defect resulting from
misuse, abuse, neglect, alteration, modification, or improper installation. To the fullest
extent permitted by the applicable state law, Enerlites shall not be liable to the purchaser or
end user customer of Enerlites products for direct, indirect, incidental, or consequential
damages even if Enerlites has been advised of the possibility of such damages. Enerlites’
total liability under this or any other warranty, express or implied, is limited to repair,
replacement or refund. Repair, replacement or refund are the sole and exclusive remedies
for breach of warranty or any other legal theory.
The Sensor Switch is programmed for Occupancy Mode only.
Automatic Turning On/Off the Load
Once the power is on, the load will be turned On according to the
occupancy settings. The sensor time delay operates as programmed.
When the load turns OFF due to the lack of motion detection, the
load can be turned ON again by occupancy detection or switch
activation.
The Sensor keeps the Load On until no motion is detected plus the
set time delay, load(s) will be turned Off automatically.
OPERATION
PIR Activity LED does not flash:
NOTE: When power is initially applied to the sensor, there is a warm-up
period of up to 1 minute before the LED is active.
WARNING: Turn off the power at the circuit breaker before
installation. Lights do not turn on with occupancy, and the
following condition exists:
1.. If the sensor’s Light Level has been turned to minimum (at positi
1), the lights connected to the Light Level Output might be held off
because of the level of ambient light in the controlled area. To test
whether the Light Level adjustment is the problem, cover the PIR lens
and PIR Activity LED with your hand to see if the lights turn on. If
the lights turn on, the Light Level setting was keeping the lights off
(see, “Sensor Adjustment” for readjustment).
2.. Make sure the wire is connected righ
1.. The sensor may be experiencing activations from outside t
controlled or from some type of interference (see “Unwanted Sensor
Activations” below).
2.. Make sure the wire is connected righ
1.. Check that the circuit breaker or any wall switch connected to t
sensor has been turned back on.
2.. Make sure that the PIR Sensitivity is set for Ma
3.. Make sure the wire is connected righ
PIR Activity LED flashes:
Lights do not turn off automatically:

Other Enerlites Accessories manuals

Enerlites MPC-50V User manual

Enerlites

Enerlites MPC-50V User manual

Enerlites MWOS User manual

Enerlites

Enerlites MWOS User manual

Enerlites MPC-50H Quick start guide

Enerlites

Enerlites MPC-50H Quick start guide

Enerlites MPC-52V User manual

Enerlites

Enerlites MPC-52V User manual

Enerlites DWOS-J User manual

Enerlites

Enerlites DWOS-J User manual

Enerlites PL20R User manual

Enerlites

Enerlites PL20R User manual

Enerlites DWHOS User manual

Enerlites

Enerlites DWHOS User manual

Enerlites HMVS User manual

Enerlites

Enerlites HMVS User manual

Enerlites MPC-50L User manual

Enerlites

Enerlites MPC-50L User manual

Enerlites DWODS-010 User manual

Enerlites

Enerlites DWODS-010 User manual

Enerlites MPC-50H User manual

Enerlites

Enerlites MPC-50H User manual

Popular Accessories manuals by other brands

Seneca R-GWR-IP-1 installation manual

Seneca

Seneca R-GWR-IP-1 installation manual

Baninni ON THE GO PASSO BNSTA005 manual

Baninni

Baninni ON THE GO PASSO BNSTA005 manual

MICRO-EPSILON wireSENSOR WPS-MK46 Assembly instructions

MICRO-EPSILON

MICRO-EPSILON wireSENSOR WPS-MK46 Assembly instructions

Aroma Retail Professional user guide

Aroma Retail

Aroma Retail Professional user guide

Trilux LMS DIM PICO 1 Mounting and operating instructions

Trilux

Trilux LMS DIM PICO 1 Mounting and operating instructions

Bresser Rotatable Star Map manual

Bresser

Bresser Rotatable Star Map manual

weinor BiConnect BiSens Agido-3V operating instructions

weinor

weinor BiConnect BiSens Agido-3V operating instructions

BEA MAGIC SWITCH CHROMA quick start guide

BEA

BEA MAGIC SWITCH CHROMA quick start guide

IFM OY4**S Series operating instructions

IFM

IFM OY4**S Series operating instructions

Bugaboo wheeled board manual

Bugaboo

Bugaboo wheeled board manual

Amphenol Temposonics R V Analog Series Operation manual

Amphenol

Amphenol Temposonics R V Analog Series Operation manual

NuTone ABWPD36SB install guide

NuTone

NuTone ABWPD36SB install guide

RED SHIELD WS-103 Installation and operating instructions

RED SHIELD

RED SHIELD WS-103 Installation and operating instructions

J Plus JLT733A user manual

J Plus

J Plus JLT733A user manual

SoundCraft Vi DANTE User and setup guide

SoundCraft

SoundCraft Vi DANTE User and setup guide

Philips HD7003 owner's manual

Philips

Philips HD7003 owner's manual

Omron F160 Vision Sensor manual

Omron

Omron F160 Vision Sensor manual

SENSECAP S210X How to connect

SENSECAP

SENSECAP S210X How to connect

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.