The MPC-52V has 4 DIP switches under the lens cover. They are used to
set the sensitivity and time delay. This device is factory preset for quick
installation and is ready to test once installed. After testing, adjust the DIP
switches and Light dial to desired levels.
Time Delay 2
Test/15 Seconds
5 Minutes
10 Minutes
15 Minutes
20 Minutes
25 Minutes
30 Minutes
34
Sensitivity
100%
50%
1
Factory setting
=OFF =ON
Sensitivity setting: DIP switch 1
50% -This setting will decrease the amount of area the sensor will cover to
half the range.
100% -This setting will allow the sensor to utilize the maximum range.
Maximum range of MPC-52V coverage is 800 square feet.
Time delay: DIP switch 2,3,4
The time delay is set with Dip switches 2, 3 and 4, from 15 seconds to
30 minutes. When there is no movement detected by sensor, the lights will
automatically turn off after the selected time delay has expired.
LED does not blink:
1. Make sure the sensor has power.
2. Check the location of the sensor and verify that the sensor
can detect motion from human body. If not , the LED will
not blink.
3. Check the wire connections and verify that the wires are
secured with wire caps.
4. Make sure the HOT and NEUTRAL wires are not reversed.
LED blinks but lights do not turn ON:
1. Check the “Light” setting. If the arrow is pointed to the
“-“position, the area needs to be dark enough for the sensor to
operate. Cover the light sensor lens to simulate darkness. If the
light turns ON, the light level setting needs to be adjusted.
2. Make sure the wires are connected and bulbs are working.
3. Check for obstructions in the lens cover.
4. Make sure that power to the sensor has been ON continuously for
at least one minute. Wait for the warm-up period to end.
Lights do not turn OFF automatically:
1. If there is no motion from people or equipment in the sensor’s view but
the LED blinks, look for any nearby source of infrared energy (heat) in
motion, such as turbulent air from a heating or cooling supply.
•Mount the sensor so that it’s lens is below the edge of the fixture
and does not directly view the lamps.
•Move the air supply away from the sensor, or move the sensor.
2. Verify the time delay settings in switches 2-4. The time delay can be set
from 15 seconds to 30 minutes. Ensure that the time delay is set to the
desired delay and that there is no movement within the sensor’s view for
that time period.
3. Check sensor wire connections, verify load and neutral wires are
secure.
TESTING OCCUPANCY SENSOR
Note: There is a 60- second warm-up period when power is first applied. Use a
small screwdriver to open the front cover and make changes to the settings.
The pre-set time delay is Test mode and light level is set at maximum
Refer to Figure 5 and 6.
1. Ensure the PIR Activity is enabled, red LED flashes, and PIR Sensitivity
is set to 100% (DIP switch 1 ON).
2. Ensure the Time Delay is set for Test Mode.
3. Ensure that the Light Level is at the maximum position (see" LIGHT
LEVEL ADJUSTMENT”).
4. Remain still. The red LED should not flash. The lights should turn off after
15 seconds. (If not, see “TROUBLESHOOTING.”)
5. Move around in front of the coverage area. The lights should turn on
automatically. When functional test is complete, set DIP Switches, Time
Delay and Light Level to the desired settings, and put the front cover
back on the sensor.
WARRANTY INFORMATION
This device is warranted to be free of material and workmanship defects for 2 years from the
date of purchase. Original receipt or proof of purchase from an authorized retailer must be
presented upon warranty claim. ALL claims must be verified and approved by Enerlites, Inc.
Warranties from other Enerlites products may vary. This warranty is nontransferable and
does not cover normal wear and tear or any malfunction, failure, or defect resulting from
misuse, abuse, neglect, alteration, modification, or improper installation. To the fullest extent
permitted by the applicable state law, Enerlites shall not be liable to the purchaser or end
user customer of Enerlites products for direct, indirect, incidental, or consequential damages
even if Enerlites has been advised of the possibility of such damages. Enerlites’ total liability
under this or any other warranty, express or implied, is limited to repair, replacement or
refund. Repair, replacement or refund are the sole and exclusive remedies for breach of
warranty or any other legal theory.
SENSOR ADJUSTMENT
The sensor may be adjusted to operate at the desired level of light under normal
lighting conditions of the immediate area.
To do so, turn the dial to point the arrow toward
the “-”sign for sensor to detect motion and
operate during low light or no light.
Point the arrow toward the “+”sign for
sensor to operate when there’s more light in
the area or even during daylight.
If the sensor detects occupancy during the warm-up, the time delay will
increase.
If no occupancy is detected during the warm-up,the light turns OFF after the
initial 60-second warm-up period.
PIR Sensor
Surface
Mounting
Screw Hole
DIP Switches
Detection
Indicator LED
CDS
Light Level
Adjustment
Surface
Mounting
Screw Hole
Note: The LED indicator flashes during the 60-second
warm-up period when power is first applied
LIGHT LEVEL ADJUSTMENT
Figure 5
Figure 6