EnerSys datasafe HX Manual

Installation, Operation
and Maintenance
Instructions
RESERVE
POWER
2
IMPORTANT
Please read this manual immediately on receipt of battery before unpacking and installing.
Failure to comply with these instructions will render any warranties null and void.
CARE FOR YOUR SAFETY
Handling
DataSafe®HX+/HX batteries are supplied in a fully
charged state and must be unpacked carefully to
avoid very high short-circuit currents between
terminals of opposite polarity. Use care when
handling and moving batteries. Appropriate lifting
equipment must be used.
Keep flames away
In case of accidental overcharge, a flammable
gas can leak off the safety vent.
Discharge any possible static electricity from
clothes by touching an earth connected part.
Tools
Use tools with insulated handles.
Do not place or drop metal objects on the battery.
Remove rings, wristwatch and articles of clothing
with metal parts that may come into contact with
the battery terminals.
Dispose at registered
waste handling
facility
RECEIVING THE SHIPMENT
Carefully examine the battery shipment upon arrival for any signs of transit
damage and that it agrees with the materials list or packing slip. Be very
careful not to inadvertently discard any accessories contained in the
packing material.
Batteries contain sulphuric acid in glass fibre separators.
Use rubber gloves when handling broken or damaged containers in case of
acid leakage.
STORAGE
Store DataSafe®HX+/HX batteries in a dry, clean and preferably cool
location.
Since the batteries are supplied charged, storage time is limited. In order to
easily charge the batteries after prolonged storage, it is advised not to store
them more than:
•6months at ambient temperature no warmer than 25°C
•4months at 30°C
•2months at 40°C
Give the batteries a freshening charge before the end of the recommended
storage interval. A refreshing charge shall be performed using 2.26 V/cell at
25°C for 96 hours or until the charge current does not vary for a 3 hour
period.
The necessity of a charge can also be determined by measuring the open
circuit voltage of a stored battery. Charging is advised if the voltage drops
below 2.07 V/cell.
Maximum total storage prior to installation is 2 years from the date of
shipment from the factory to the customer. Freshening charges are
required before the end of the storage time period or more frequently, as
noted above. Failure to observe these conditions may result in greatly
reduced capacity and service life.
FAILURE TO CHARGE AS NOTED VOIDS THE BATTERY’S WARRANTY.
INSTALLATION
Install in a clean and dry area. DataSafe HX+/HX batteries release minimal
amounts of gas during normal operation (gas recombination efficiency ≥
95%). They can be installed near the main equipment. Batteries must be
installed in accordance with local, national and international regulations and
manufacturers instructions.
Temperature
Avoid placing the battery in areas of high temperature or in direct sunlight.
The battery will give the best performance and service life when working at a
temperature between 20°C and 25°C. The maximum operating temperature
range is -30°C to +45°C.
Ventilation
Under normal conditions gas release is very low and natural ventilation is
sufficient for cooling purposes and inadvertent overcharge, enabling DataSafe
HX+/HX batteries to be used safely in offices and with main equipment.
However care must be taken to ensure adequate ventilation when placed in
cabinets. Batteries must not be placed in sealed cabinets.
Security
All installation and ventilation must comply with the current local, national
and international regulations.
Mounting
EnerSys®battery racks or cabinets are recommended for proper installation.
Assemble the rack according to instructions. Place the monoblocs or cells on
the rack and arrange the positive and the negative terminals for connection
according to the wiring diagram. Check that all contact surfaces are clean and
apply the bloc or cell connectors and the terminal screws. Tighten the screws
securely. Follow the polarity to avoid short circuiting of cell groups. Finally
connect the battery terminals. It is important that the battery is mounted
firmly.
Installation of High Voltage Batteries
Abattery consisting of 60 or more cells connected in series presents
additional hazards and the following notes on installation should be
employed.
• Limit the battery voltage by omitting inter-cell connectors to give a
maximum section voltage of 120V or 60 cells.
• The omitted inter-cell connectors should be chosen such that they are in an
easily accessible position. These connectors should only be fitted with the
load and charger isolated and when the rest of the installation is complete.
• Never work alone on high voltage batteries.
• Always use insulated tools and wear approved high voltage insulating
gloves.
•When supplied, fit the "high voltage battery" warning labels in a prominent
position.
Torque
Tighten the nuts or bolts to the recommended levels of fastening torque
indicated on the product label (if applicable). A loose connector can cause
problems in charger adjustment, erratic battery performance, possible
damage to the battery and/or personal injury.
CELLS IN PARALLEL STRINGS
When using constant voltage chargers, ensure that the connections
between the charger and the end of each string within the battery have the
same electrical resistance. Parallel strings must be limited to five strings.
CHARGING
Float Voltage
The float/charge voltage is 2.26 V per cell at 25°C. When the average
ambient temperature deviates more than ± 5°C from the reference, it is
necessary to adjust the float voltage as indicated in the following table :
No smoking, no naked flames,
nosparks Electrolyte is corrosive
Clean all acid splash in eyes or on
skin with plenty of clean water.
Then seek medical help. Acid on
clothing is to be washed with water
Danger
Warning: Risk of fire, explosion, or burns.
Donot disassemble, heat above 60ºC, or incinerate.
Avoid any short circuit. Metallic parts under voltage on the
battery, do not place tools or items on top of the battery
Battery must be
recycled
Protect eyes
from electrolyte
Read
instructions
Donot charge in
sealed container
3
Due to the phenomena of gas recombination a difference of ± 2% (earlier in
float life ± 5% is common) for an individual cell voltage can be observed.
However the total voltage of the battery shall be within the limits stated
above.
Charging Current
Utilising a constant voltage charger results in a charging current that is self
limiting.
Fast Recharge
Occasionally (4 or 5 times a year) the battery may be recharged at 2.40Vpc
with a current limit of 0.1C10A. Fast charging should be stopped after
approximately 10 or 15 hours.
Ripple Current
Unacceptable levels of ripple current from the charger or the load can cause
permanent damage and a reduction in service life. It is recommended to
limit the continuous ripple current to 0.05C10A.
State of Charge
The battery state of charge can be determined approximately by measuring
the open circuit voltage after the battery has been at rest for a minimum of
24 hours at 25°C.
DISCHARGING
End of Discharge Voltage
The end of discharge voltage must be limited to 1.60Vpc.
Aprotecting system shall have to be installed to prevent deep discharge.
Discharged Cells/Monoblocs
DataSafe®HX+/HX batteries must not be left in a discharged condition after
supplying the load, but must be immediately returned to float recharge
mode. Failure to observe these conditions may result in greatly reduced
service life and unreliability.
Accidental Deep Discharge
When the battery is completely discharged, the sulphuric acid is completely
absorbed and the remaining electrolyte consists only of water.At this point,
the sulphation of the plates is at its maximum, considerably increasing the
cell’sinternal resistance.
Important notice: this type of deep discharge will provoke a premature
deterioration of the battery and a noticeable effect on life expectancy.
Effect of temperature on capacity
Correction factor of the capacity, according to temperature.
MAINTENANCE/CHECKS
DataSafe HX+/HX batteries are maintenance free, sealed, lead acid batteries
and need no water addition.
Warning: The cases and lids shall be kept dry and free from dust. Cleaning
must be done only with a damp cotton cloth. Do NOT use any type of oil,
solvent, detergent, petroleum-based solvent or ammonia solution to clean
the battery containers or lids. These materials will cause permanent
damage to the battery container and lid and will invalidate the warranty.
Check monthly that the total voltage at battery terminals is (N x 2.24 to 2.27
V) for a temperature of 25°C (N being the number of cells in the battery).
Every 12 months, read and record the following:
• Individual cell or unit voltages (volts)
• Cell-to-cell connection resistance (ohms)
•Terminal connection resistance (ohms)
• Ambient temperature in the immediate battery environment
Keep a logbook to record values, power outages, discharge tests, etc.
An autonomy check can be carried out once or twice a year.
The above record taking is the absolute minimum to protect the warranty.
This data will be required for any warranty claim made on the battery.
5°C 0.84
10°C 0.88
15°C0.93
20°C 0.97
25°C 1.00
30°C 1.03
35°C 1.05
40°C 1.07
Temperature Correction Factor
State of charge Voltage
100% 2.12 to 2.14 V/Cell
80% 2.09 to 2.11 V/Cell
60% 2.05 to 2.08 V/Cell
40% 2.01 to 2.04 V/Cell
20% 1.97 to 2.00 V/Cell
0°C 2.33 to 2.36 Vpc
10°C 2.30 to 2.33 Vpc
20°C 2.27 to 2.30 Vpc
25°C (reference temperature) 2.24 to 2.27 Vpc
30°C 2.23 to 2.26 Vpc
35°C 2.21 to 2.24 Vpc
Temperature Float Voltage
Publication No: EN-HX-IOM-008 -June 2012 - Subject to revisions without prior notice. E.&O.E.
www.enersys-emea.com
Contact:
©2012 EnerSys. All rights reserved.
Trademarks and logos are the property of EnerSys
and its affiliates unless otherwise noted.
EnerSys
2366 Bernville Road
Reading, PA19605
USA
Tel: +1-610-208-1991
+1-800-538-3627
Fax: +1-610-372-8613
EnerSys Ltd.
Oak Court
Clifton Business Park
Wynne Avenue, Swinton
Manchester M27 8FF
UK
Tel: +44 (0)161 794 4611
Fax: +44 (0)161 727 3809
EnerSys Europe
EH Europe GmbH
Löwenstrasse 32
8001 Zurich, Switzerland
EnerSys Asia
152 Beach Road
Gateway East Building, Level 11
189721 Singapore
Tel: +65 6508 1780

This manual suits for next models

1

Other EnerSys Batteries Pack manuals

EnerSys Genesis TD Installation and operating instructions

EnerSys

EnerSys Genesis TD Installation and operating instructions

EnerSys PowerSafe SBS B14 User manual

EnerSys

EnerSys PowerSafe SBS B14 User manual

EnerSys FRONT TERMINAL Series User manual

EnerSys

EnerSys FRONT TERMINAL Series User manual

EnerSys GAZ lomain KGM P User manual

EnerSys

EnerSys GAZ lomain KGM P User manual

EnerSys PowerSafe DDmP125-33 LP Operating instructions

EnerSys

EnerSys PowerSafe DDmP125-33 LP Operating instructions

EnerSys PowerSafe SBS XC+ User manual

EnerSys

EnerSys PowerSafe SBS XC+ User manual

EnerSys SuperSafe SBS XC User manual

EnerSys

EnerSys SuperSafe SBS XC User manual

EnerSys OutBack Power SkyBox User manual

EnerSys

EnerSys OutBack Power SkyBox User manual

EnerSys PowerSafe SBS 8 User manual

EnerSys

EnerSys PowerSafe SBS 8 User manual

EnerSys Nexsys 12NXS26 User manual

EnerSys

EnerSys Nexsys 12NXS26 User manual

EnerSys SuperSafe OPzV User manual

EnerSys

EnerSys SuperSafe OPzV User manual

EnerSys PowerSafe SBS XC+ User manual

EnerSys

EnerSys PowerSafe SBS XC+ User manual

EnerSys Hawker Perfect Plus User manual

EnerSys

EnerSys Hawker Perfect Plus User manual

EnerSys PerfectRail DS Troubleshooting guide

EnerSys

EnerSys PerfectRail DS Troubleshooting guide

EnerSys powerbloc dry XFC Series Manual

EnerSys

EnerSys powerbloc dry XFC Series Manual

EnerSys Data Safe MX Manual

EnerSys

EnerSys Data Safe MX Manual

EnerSys NexSys iON User manual

EnerSys

EnerSys NexSys iON User manual

EnerSys PowerSafe OPzV Guide

EnerSys

EnerSys PowerSafe OPzV Guide

EnerSys PowerSafe DDmP Setup guide

EnerSys

EnerSys PowerSafe DDmP Setup guide

Popular Batteries Pack manuals by other brands

Generac Power Systems PWRcell M3 Installation and owner's manual

Generac Power Systems

Generac Power Systems PWRcell M3 Installation and owner's manual

Texas Instruments 2 Series manual

Texas Instruments

Texas Instruments 2 Series manual

Odyssey PC310 owner's manual

Odyssey

Odyssey PC310 owner's manual

PAG Mini PAGlink MPL50 user guide

PAG

PAG Mini PAGlink MPL50 user guide

Sanyo Denki SANUPS E11A102 Series Battery Replacement Procedure

Sanyo Denki

Sanyo Denki SANUPS E11A102 Series Battery Replacement Procedure

Hubble AM-10 manual

Hubble

Hubble AM-10 manual

Goodwe Pytes E-BOX Series Installation and configuration manual

Goodwe

Goodwe Pytes E-BOX Series Installation and configuration manual

Toro 88605 Operator's manual

Toro

Toro 88605 Operator's manual

Ryobi OP241A Operation manual

Ryobi

Ryobi OP241A Operation manual

Sea-Bird Scientific SUBMERSIBLEBATTERYPACKS user manual

Sea-Bird Scientific

Sea-Bird Scientific SUBMERSIBLEBATTERYPACKS user manual

BBB BLS-96 manual

BBB

BBB BLS-96 manual

iOptron PowerWeight instruction manual

iOptron

iOptron PowerWeight instruction manual

Ryobi PBP004 user manual

Ryobi

Ryobi PBP004 user manual

Deka DURATION DD5300 Installation and user manual

Deka

Deka DURATION DD5300 Installation and user manual

CyberPower BPE36V60AS user manual

CyberPower

CyberPower BPE36V60AS user manual

Mophie juice pack user manual

Mophie

Mophie juice pack user manual

VOLTA evoTractionBattery manual

VOLTA

VOLTA evoTractionBattery manual

BCB BZ-70BL user manual

BCB

BCB BZ-70BL user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.