
12 USER GUIDE ENTEGRIS, INC.
INVUE INTEGRATED FLOW CONTROLLERS, MODELS NT6510, NT6520
When installing flared tubing to the
flow controller, the flared tube is
pushed over the valve’s fitting until
the fitting reaches the smaller tube
diameter. The amount of torque
required to tighten the nut is depen-
dent upon the size of the fitting.
Flaretek Fitting 1⁄4”3⁄8”1⁄2”3⁄4”
Torque (in•lbs) 5 8 11 14
Torque (N•m) 0.56 0.90 1.24 1.58
Care should be taken when installing
the flow controller to avoid fluid
leaks. Do not use excessive torque or
subject the unit to high heat during
installation. The unit and base
bracket assembly must be mounted
to a solid surface to ensure stability.
Verify the body and the electrical
cable are free from mechanical stress
from the surrounding equipment.
Power Supply Requirements
The power supply range for the
flow controller is 24 VDC ±10%
regulated. The power supply must
provide continuous 1.0 ampere
(nominal) service for each flow
controller installed. The power
supply requirements must be met
at the wire connections or connector
of the flow controller, not only at the
power supply itself.
The power supply to the unit must
provide clean power and must be
used only to power similar measure-
ment-type devices. The power supply
must not be used to power other
inductive loads, such as motors,
relays, or solenoids. These devices
may produce electrical transients
that may affect unit measurements.
An induced power spike, creating an
interruption in power greater than
10 milliseconds in duration, may
cause the unit to reset.
In addition to providing clean power,
the instrumentation signals and
power return lines must not be run
within the same conduit or cable
along with heavy current demands
from motors, charging capacitors
or other inductive loads. This may
cause a voltage change within the
instrumentation signal line, causing
erroneous output readings from the
flow controller. Loss of power will
not cause the loss of any system
parameters or calibration values.
Input Impedance of the
Voltage Setpoint
The input impedance of the voltage
setpoint is 37 kOhm.
Voltage Drop at the 4–20 mA
Setpoint Input
The 4–20 mA input will drop
<5 V at 20 mA. Input impedance
is <250 ohms.
Lift-off Voltage of the 4–20 mA
Output Loops
The minimum lift-off voltage of the
4–20 mA output loops (flow, pressure
measurements) is 12 VDC. The mini-
mum lift-off voltage is the voltage
required at the unit for proper
operation. The maximum load
resistance for a 24 VDC supply is
600 ohms and includes the resis-
tance of measurement devices
and the interconnecting cable.