eta KNX User manual

2020-05-25
EN
0000000488
V.001
X.49.0
939112-001
KNX Communication
for ETAtouch control system
Operating instructions

ETA Heiztechnik
Gewerbepark 1
A-4716 Hofkirchen an der Trattnach
Tel: +43 (0) 7734 / 22 88 -0
Fax: +43 (0) 7734 / 22 88 -22
www.eta.co.at

General information
3
1 General information
Copyright
All contents of this document are property of ETA
Heiztechnik GmbH and are protected by copyright.
Any reproduction, transfer to third parties or use for
other purposes is prohibited without written permission
from the owner.
Software Description
The software version described in this documentation
corresponds to the version valid at the time of publica-
tion. The software version installed on your product
may differ from that described in this documentation.
A software update to a more recent version can
always be performed. With the appropriate au-
thorisation, the required files can be found at
"www.eta.co.at".
Subject to technical changes
We reserve the right to make technical modifications
without notice. Printing and typesetting errors or
changes of any kind made in the interim are not cause
for claims. Individual configurations depicted or
described here are only available optionally. In the
event of contradictions between individual documents
regarding delivery scope, the information in our current
price list applies.
Explanation of symbols
Instructions and information
Layout of safety instructions
SIGNAL WORD!
Type and source of danger
Possible effects
• Measures for avoiding the danger
Types of safety instruction
CAUTION!
On non-compliance with this safety instruction, there is
a risk of material damage.
WARNING!
On non-compliance with this safety instruction, there is
a risk of physical injury.
DANGER!
On non-compliance with this safety instruction, there is
a risk of major physical injury.

4 www.eta.co.at
Commissioning
2 Commissioning
Assembly and installation only by qualified
specialist personnel
The assembly and installation may be performed
by specialist personnel with the corresponding
qualifications only.
Download the current version of the KNX database
You can find the current version of the KNX database
in the login area on the website <www.ETA.co.at>. To
download, log in with the username: software and the
password: 4716.
If you are registered on the platform <www.meinE-
TA.at>, you can also download the database there in
the [Settings] under the [Installation & Software] menu.
KNX USB interface stick
The requirements for communication between the
ETAtouch control system and the KNX installation bus
are:
• Software version X.49.0 or higher is installed on
the ETAtouch control panel
• ETAtouch control panel of the generation [BE-P2]
or [BE-P3]
A "KNX USB interface stick," which is connected to the
ETAtouch control system [BE-P], serves as the
interface for the KNX installation bus for the ETAtouch
control panel.
Fig. 2-1: KNX USB interface stick
Connect the KNX bus line to the USB interface stick.
The KNX polarity is marked on the housing with +/-;
see the graphic below.
Fig. 2-2: Correct KNX polarity
Further details on the KNX USB interface stick
can be found in the manufacturer's operating in-
structions in Chapter 4 "Appendix".
Plug the KNX USB interface stick into a free USB port
on the ETAtouch control panel. Use the supplied USB
extension for this.
Fig. 2-3: USB connections on the control panel [BE-P3]
Fig. 2-4: USB extension for KNX bus
The configuration is performed via the "ETS"
programming software (version 5 or higher) on a
laptop or PC. The possible parameters and communi-
cation objects from the ETAtouch control system are
listed in Chapter 3 "Adjustable parameters".
Establish a KNX connection to the ETAtouch
control system
1. Make sure the KNX USB interface stick is
connected to the ETAtouch control panel.
2. On the ETAtouch control system, press the
(bottom left) symbol to open the system settings.
Press the [Authorisation] button. Enter the
password "135" and confirm this.

Commissioning
5
3. Switch to the [Internet & interfaces] menu and
select [KNX bus system]. An overview opens.
Fig. 2-5: Overview of the KNX interface
4. The [Programming button] button must be
pressed to allow the KNX USB interface stick to be
identified. An address can then be assigned to the
USB interface stick using the "ETS" programming
software.
If the error symbol appears among the
symbols for USB and KNX (in the upper left
area), check whether both the USB interface stick
and the KNX bus line are connected correctly.
5. The assignment of the function blocks, e.g., hot
water tank [WW] to the KNX groups is performed
via the selection list for the respective function
block. Select the [Not used] setting for those
function blocks that are not required for KNX com-
munication.
Fig. 2-6: Assignment
6. Once the assignment has been made, close the
window. Following this, the ETAtouch control
system must be restarted to save and activate the
KNX connection.
The ETAtouch control system must be
restarted for all changes to the configuration
with the "ETS" programming software and
subsequent installation on the KNX USB interface
stick.

6 www.eta.co.at
Adjustable parameters
3 Adjustable parameters
Parameters from the ETAtouch control system for communication via the KNX bus
The following applies to all parameters: If a value greater than 0 is set at [Transmit cyclical?], the ETAtouch control
system sends the values at the set interval. The value "0" deactivates the regular transmission of the values. It can
also be set for all parameters if there is a change in value (e.g., temperature change of 1°C), regardless of whether
these are transmitted or not. In the general settings, the ETAtouch control system can transmit the time and in
adjustable intervals.
The factory settings of the "flags" for the individual communication objects are listed in the following tables. The flags
can be adjusted as needed. The abbreviations mean the following:
• C = Communication (always set)
• R = Read
• W = Write
• T = Transmit
The R flag must be set to facilitate reading. The last value written into the object via the bus is read out. If no
(or no reasonable) value is output for a communication object, the setting [Transmit on change in value?] may
be deactivated in the "ETS" programming software, or [Transmit cyclical?] may be set to 0.
The ETAtouch control system must be restarted for all changes to the configuration with the "ETS"
programming software and subsequent installation on the KNX USB interface stick.
Boiler (maximum 2)
Designation Description DPT Flag
Parameter:
Boiler type:
• Woodchip
• Pellet
•Log
The respective boiler type must be selected for
each boiler.
Exhaust, boiler and return temp. Transmits the relevant boiler temperatures.
Combustion chamber temp. Transmits the furnace temperature (only possi-
ble with the HACK VR moving grate boiler).
Boiler pressure Transmits the heating system water pressure (if
available).
Residual O2 Transmits the residual oxygen content of the flue
gas.
Consumption since de-ashing, consump-
tion since maintenance
Transmits the meter readings for fuel consump-
tion and the meter reading since the last mainte-
nance for automatic boilers (pellet boilers, wood
chip boilers).
Communication objects:
Boiler pressure Only for boilers with a pressure sensor: transmits
the water pressure to the heating system. 14.058 C, R, T
De-ash button
For automatic boilers: starts an additional de-
ashing of the boiler.
For log boilers: switches off the ember mainte-
nance.
1.001 C, R, W,
T
On/off button Automatic boilers only: to switch the boiler on
and off. 1.001 C, R, W,
T
Return temperature Transmits the boiler return temperature. 9.001 C, R, T
State Transmits the operating condition. 16.001 C, R, T

Adjustable parameters
7
Boiler temp. Transmits the temperature of the boiler. 9.001 C, R, T
Flue gas temp. Transmits the exhaust temperature. 9.001 C, R, T
Residual O2 Transmits the residual oxygen content of the flue
gas. 5.001 C, R, T
Pellet bin content Only for pellet boilers: transmits the pellet supply
from the pellet hopper to the boiler. 14.051 C, R, T
Consumption since deash
Only for automatic boilers: transmits the meter
reading of the fuel consumption since the last de-
ashing.
14.051 C, R, T
Consumption since ash box emptied
Only for automatic boilers: transmits the meter
reading of the fuel consumption since the last
emptying of the ash box.
14.051 C, R, T
Combustion chamber temp.
Only with the HACK VR wood chip boiler: trans-
mits the boiler combustion chamber tempera-
ture.
9.001 C, R, T
Automatic mode ignition Only for log boilers: to switch the automatic igni-
tion on and off. 1.001 C, R, W,
T
Fill up pellet bin Only for pellet boilers : to start the vacuum turbine
to fill up the boiler pellet hopper. 1.001 C, R, W,
T
Fault message output Transmits a signal if there is a malfunction in the
boiler. 1.001 C, R, T
Run message output Transmits the status of the boiler. 1.011 C, R, T
Boiler (maximum 2)
Designation Description DPT Flag
Buffer (maximum 4)
Designation Description DPT Flag
Parameter:
Number of buffer temp. sensors
Buffer temps Transmits the values of the temperature sen-
sors.
Charging state Transmits the charge status of the buffer.
Communication objects:
Tem p . 1 Transmits the values of the temperature sen-
sors. Up to 9 temperature sensors can be config-
ured.
9.001 C, R, TTem p . 2
Tem p . 3
Charging state
Transmits the charge status of the buffer. The
charge status corresponds to the average of all
buffer temperature sensors.
A charge status of 0% means that the buffer
is only charged up to the set temperature
[Consumer Return Flow], e.g., 35 °C or lower.
A value of 100% means that the buffer is
charged to an average of 80 °C, or higher if the
required target temperature is greater than 80
°C.
5.004 C, R, T

8 www.eta.co.at
Adjustable parameters
Charge immediately
Only with automatic boilers: this starts the imme-
diate charging of the buffer, even outside the set
time window.
1.001 C, R, W,
T
Charge hotwater immediately
Only for buffers with an integrated hot water sec-
tion: this starts the immediate charging of the hot
water section, even outside the set time window.
1.001 C, R, W,
T
State Transmits the operating condition. 16.001 C, R, T
Buffer (maximum 4)
Designation Description DPT Flag
Hot water tanks (maximum 4)
Designation Description DPT Flag
Parameter:
Tem p s Transmits the values of the temperature sen-
sors.
Communication objects:
State Transmits the operating condition. 16.001 C, R, T
Temperature Transmits the values of the temperature sen-
sors. 9.001 C, R, T
Temp. bottom
Only with an additional temperature sensor:
transmits the hot water temperature in the lower
area of the storage tank.
9.001 C, R, T
Charge immediately This starts the immediate charging of the hot wa-
ter tank, even outside the set time window. 1.001 C, R, W,
T
Heating circuit (maximum 8)
Designation Description DPT Flag
Parameter:
Heating circuit type:
• Heating circuit
• Individual room control heating circuit
The respective type must be selected for each
heating circuit.
Target and actual temps Transmits the target and actual temperatures
from the room sensor.
Flow temp. Transmits the feed temperature of the heating
circuit.
Communication objects:
Actual room temp. Transmits the room temperature from an ETA
room sensor to the ETAtouch control system. 9.001 C, R, T
Target room temp. Defines the desired room temperature. 9.001 C, R, W,
T
Heating button Switches the heating circuit into heating mode. 1.001 C, R, W,
T
Auto button
Switch the heating circuit to automatic mode.
The heating circuit thus changes automatically
between heating and reduced-temperature oper-
ating modes.
1.001 C, R, W,
T

Adjustable parameters
9
Set-back button
Switches the heating circuit to reduced-tempera-
ture mode (lower temperature and outside the
set heating times).
1.001 C, R, W,
T
On/off button For switching the heating circuit on and off. 1.001 C, R, W,
T
Home button
Ends the current operation and switches the
heating circuit to heating mode until the next set
time window. The heating circuit then switches
back to automatic mode.
1.001 C, R, W,
T
Away button
Ends the current operation and switches the
heating circuit to reduced-temperature mode un-
til the next set time window. The heating circuit
then switches back to automatic mode.
1.001 C, R, W,
T
Actual room temp. from bus
The room temperature is measured by an exter-
nal room sensor and the value is transferred to
the ETAtouch control system.
9.001 C, W, T
Target temp. diff. heating
Used to gradually adjust the room temperature in
heating mode.
A value of, for example, 0.5 °C increases the de-
sired room temperature in heating mode (in all
time windows) by 0.5 °C. A value of -1 °C reduc-
es the desired room temperature by 1 °C.
9.002 C, W, T
Target temp. diff. set-back
Used to gradually adjust the room temperature in
reduced-temperature mode.
A value of, for example, 0.5 °C increases the de-
sired room temperature by 0.5 °C in reduced-
temperature mode. A value of -1 °C reduces the
desired room temperature by 1 °C.
9.002 C, W, T
Flow temp. Transmits the feed temperature of the heating
circuit. 9.001 C, R, T
Holiday start daytime 10.001 C, R, W,
T
Holiday start date
Defines the period for the continuous reduced-
temperature mode of the heating circuit. After
this period, the heating circuit automatically
switches back to automatic mode.
11.001 C, R, W,
T
Holiday end daytime 10.001 C, R, W,
T
Holiday end date 11.001 C, R, W,
T
State Transmits the operating condition. 16.001 C, R, T
Heating circuit (maximum 8)
Designation Description DPT Flag
Rooms (maximum 20)
Designation Description DPT Flag
Parameter:
Target and actual temps Transmits the target and actual temperatures
from the room sensor.
Valve value Transmits the position of the control valve for the
room.

10 www.eta.co.at
Adjustable parameters
Communication objects:
Actual room temp. Transmits the room temperature measured by
the room sensor of the ETAtouch control system. 9.001 C, R, T
Target room temp. Defines the desired room temperature. 9.001 C, R, W,
T
Heating button Switches the room to heating mode. 1.001 C, R, W,
T
Auto button
Switch the room to automatic mode. The heating
circuit thus changes automatically between heat-
ing and reduced-temperature operating modes.
1.001 C, R, W,
T
Set-back button
Switches the room to reduced-temperature
mode (lower temperature and outside the set
heating times).
1.001 C, R, W,
T
On/off button For switching the room on and off. 1.001 C, R, W,
T
Home button
Ends the current operation and switches the
room to heating mode until the next set time win-
dow. The room then switches back to automatic
mode.
1.001 C, R, W,
T
Away button
Ends the current operation and switches the
room to reduced-temperature mode until the
next set time window. The room then switches
back to automatic mode.
1.001 C, R, W,
T
Actual room temp. from bus
The current room temperature is measured by
an external room sensor and the value is trans-
ferred to the ETAtouch control system.
9.001 C, W, T
Target temp. diff. heating
Used to gradually adjust the room temperature in
heating mode.
A value of, for example, 0.5 °C increases the de-
sired room temperature in heating mode (in all
time windows) by 0.5 °C. A value of -1 °C reduc-
es the desired room temperature by 1 °C.
9.002 C, W, T
Target temp. diff. set-back
Used to gradually adjust the room temperature in
reduced-temperature mode.
A value of, for example, 0.5 °C increases the de-
sired room temperature by 0.5 °C in reduced-
temperature mode. A value of -1 °C reduces the
desired room temperature by 1 °C.
9.002 C, W, T
Valve value Transmits the position (in percent) of the control
valve for the room.
This object must not be used for on-off ac-
tuators. For on-off actuators, use the "Valve
Status" object instead.
The second valve is only required if a room
is supplied by two heating circuits.
5.001 C, R, T
Valve value 2 5.001 C, R, T
Rooms (maximum 20)
Designation Description DPT Flag

Adjustable parameters
11
Valve state Transmits the status (open/closed) of the control
valve which is controlled via a heating actuator
(via KNX bus).
The second valve is only required if a room
is supplied by two heating circuits.
1.003 C, R, T
Valve state 2 1.003 C, R, T
State Transmits the operating condition. 16.001 C, R, T
Rooms (maximum 20)
Designation Description DPT Flag
Solar heating system (maximum 2)
Designation Description DPT Flag
Parameter:
Collector temp. Transmits the collector temperature.
Heatmeter power
The thermal energy generated by the solar heat-
ing system is transmitted.
The ETAtouch control system calculates
the thermal energy either using additional
temperature sensors or using a flow meter.
Heatmeter energy Transmits the thermal energy generated by the
solar heating system.
Communication objects:
State Transmits the operating condition. 16.001 C, R, T
Collector temp. Transmits the collector temperature. 9.001 C, R, T
Actual power The current output of the solar heating system is
transmitted. 9.024 C, R, T
Production today The thermal energy already generated today is
transmitted. 13.010 C, R, T
Production yesterday The thermal energy generated yesterday is
transmitted. 13.010 C, R, T
Total production The thermal energy generated by the solar heat-
ing system is transmitted. 13.010 C, R, T
Modules (maximum 4)
Designation Description DPT Flag
Parameter:
Module type:
• Fresh water module
• System separation module
• Heat transfer station
The respective type must be set for each mod-
ule.
Temperatures Transmits the relevant temperatures.
Valve value Only possible with the heat transfer station. The
position of the primary valve is transmitted.
Power Transmits the relevant outputs.
Communication objects (fresh water module):
Actual hot water temp. Transmits the current hot water temperature. 9.001 C, R, T

12 www.eta.co.at
Adjustable parameters
Target hot water temp. Defines the desired warm water temperature. 9.001 C, R, W,
T
State Transmits the operating condition. 16.001 C, R, T
Communication objects (system separation module):
Primary flow temp. Transmits the feed temperature on the primary
side (heat producer) of the heat exchanger. 9.001 C, R, T
Secondary flow temp. Transmits the feed temperature on the second-
ary side (consumer side) of the heat exchanger. 9.001 C, R, T
State Transmits the operating condition. 16.001 C, R, T
Communication objects (heat transfer station):
Primary flow temp. Transmits the feed temperature on the primary
side (heat producer) of the heat exchanger. 9.001 C, R, T
Secondary flow temp. Transmits the feed temperature on the second-
ary side (consumer side) of the heat exchanger. 9.001 C, R, T
Primary valve value
Transmit the position of the primary valve with
which the flow and thus the thermal energy is
regulated.
5.004 C, R, T
On/off button For switching the module on and off. 1.001 C, R, W,
T
State Transmits the operating condition. 16.001 C, R, T
Power Transmits the module output. 9.024 C, R, T
Modules (maximum 4)
Designation Description DPT Flag
Burner (maximum 2)
Designation Description DPT Flag
Parameter:
Temperatures Transmits the feed temperature of the burner
(only if a temperature sensor is present).
Target power Transmits the required burner output.
Operating hours Transmits the burner operating hours.
Communication objects:
Burner temp. Transmits the feed temperature of the burner. 9.001 C, R, T
Demanded power Transmits the required burner output. 9.024 C, R, T
Operating hours Transmits the burner operating hours. 13.100 C, R, T
Demand Sends a request to the burner to start. 1.002 C, R, T
Return temperature Transmits the burner return temperature. 9.001 C, R, T
On/off button
To switch the burner on and off in ready mode.
The ETAtouch control system can only re-
quest this if the burner is switched on (i.e.,
ready for operation).
1.001 C, R, W,
T
State Transmits the operating condition. 16.001 C, R, T

Adjustable parameters
13
External heat source (maximum 2)
Designation Description DPT Flag
Parameter:
Tem p . Transmits the feed temperature of the additional
heat producer.
Communication objects:
Tem p . Transmits the feed temperature of the additional
heat producer. 9.001 C, R, T
State Transmits the operating condition. 16.001 C, R, T
Pipeline (maximum 2)
Designation Description DPT Flag
Parameter:
Flow temp. Transmits the feed temperature of the pipeline.
Communication objects:
State Transmits the operating condition. 16.001 C, R, T
On/off button For switching the heat supply on and off via the
pipeline. 1.001 C, R, W,
T
Flow temp. Transmits the feed temperature of the pipeline. 9.001 C, R, T
External demand (maximum 4)
Designation Description DPT Flag
Parameter:
Power demand Display of the heat consumer's requested out-
put.
Tem p . dem an d Display of the heat consumer's requested tem-
perature.
Communication objects:
State Transmits the operating condition. 16.001 C, R, T
Demand Display of a heat request via a digital input on the
circuit board (on/off or yes/no). 1.011 C, R, T
Power demand
Display of the output required by the heat con-
sumer through an analogue input on the boil-
er circuit board (e.g., 0-10V).
9.024 C, R, T
Tem p . dem an d
Display of the temperature required by the heat
consumer through an analogue input on the boil-
er circuit board (e.g., 0-10V).
9.001 C, R, T
Producer ready Display of the operating condition of the heat
producer (e.g., boiler) for the heat consumer. 1.011 C, R, T
Demand from bus
Transmission of a heat request via the KNX bus
to the ETAtouch control system (on/off or yes/
no).
1.003 C, R, W,
T
Power demand from bus
Specification of the required output for the heat
consumer using the KNX actuator to the ETA-
touch control system.
9.024 C, R, W,
T

14 www.eta.co.at
Adjustable parameters
Temp. demand from bus
Specification of the required temperature for the
heat consumer using the KNX actuator to the
ETAtouch control system.
9.001 C, R, W,
T
On/off button For switching the heat consumer on and off. 1.001 C, R, W,
T
External demand (maximum 4)
Designation Description DPT Flag
District heating
Designation Description DPT Flag
Parameter:
Flow temp. Transmits the feed temperature from the district
heating connection.
Flow Transmits the flow rate from the district heating
connection.
Net power Transmits the output extracted from the district
heating connection.
Communication objects:
Flow temp. Transmits the feed temperature from the district
heating connection. 9.001 C, R, T
Flow Transmits the flow rate from the district heating
connection. 9.025 C, R, T
Net power Transmits the output extracted from the district
heating connection. 9.024 C, R, T
On/off button Switching the heat supply to the consumer on
and off. 1.001 C, R, W,
T
State Transmits the operating condition. 16.001 C, R, T
Pool
Designation Description DPT Flag
Parameter:
Temperatures Transmits the relevant temperatures.
Communication objects:
State Transmits the operating condition. 16.001 C, R, T
Temperature Transmission of the current pool temperature. 9.001 C, R, T
On/off button
The heating of the pool is enabled or locked with
this button. The pool can only be heated if it is
enabled.
1.001 C, R, W,
T
Charging active For immediate charging of the pool by the heat
producer (solar heating system or buffer). 1.001 C, R, W,
T
Winter mode Used to activate the frost protection function for
the pool pump. 1.001 C, R, W,
T
Target temp. solar charging Defines the desired pool temperature when
heated by the solar heating system. 9.001 C, R, W,
T
Target temp. buffer charging Defines the desired pool temperature when
heating via the buffer storage. 9.001 C, R, W,
T

Adjustable parameters
15
Pellet conveying system (maximum 2)
Designation Description DPT Flag
Parameter:
Stock Transmits the pellet supply in the storage space.
Communication objects:
Stock Transmits the pellet supply in the storage space. 14.051 C, R, W,
T
State Transmits the operating condition. 16.001 C, R, T
Store empty sensor Transmits the status of the sensor for the pel-
let conveyor line. 1.002 C, R, T
Wood chip conveying system (maximum 2)
Designation Description DPT Flag
Communication objects:
On/off button Used to switch the conveying system on and off. 1.001 C, R, W,
T
State Transmits the operating condition. 16.001 C, R, T
System
Designation Description DPT Flag
Parameter:
Additional temperature sensor Transmission of the values from the additional
temperature sensors.
Outside temp. Transmits the outside temperature from the tem-
perature sensor to the ETAtouch control system.
Communication objects:
Additional temp. 1 Transmission of the values from the additional
temperature sensors. 9.001 C, R, T
Additional temp. 2 9.001 C, R, T
Additional temp. 3 9.001 C, R, T
Additional temp. 4 9.001 C, R, T
Additional temp. 5 9.001 C, R, T
Outside temp. Transmits the outside temperature from the tem-
perature sensor to the ETAtouch control system. 9.001 C, R, T
External fault message from bus Transmission of a fault message from a KNX ac-
tuator to the ETAtouch control system. 1.001 C, W, T
System fault message Switches an output when a malfunction occurs. 1.001 C, R, T
Outside temp. from bus
Transmits the outside temperature from its own
KNX actuator instead of the temperature sensor
on the ETAtouch control system.
9.001 C, W, T

16 www.eta.co.at
Appendix
4 Appendix

Appendix
17
2019 WEINZIERL ENGINEERING GmbH Seite 1/3
Bedienungs- und Montageanleitung
KNX USB Interface Stick 332
(Art. # 5254)
Portables USB Interface in Stickform für den KNX-Bus
KNX USB Interface Stick 332
Anwendung
Das KNX USB Interface Stick 332 dient als Datenschnittstelle
zwischen einem PC oder Laptop und dem Installationsbus KNX.
Das Gerät ist kompatibel mit der ETS® Software (ETS3 oder
höher) und unterstützt erweiterte Telegramme (Lange Tele-
gramme / Long Frames) beim Download.
Die LEDs auf der Oberseite zeigen Betriebszustände sowie
Kommunikationsfehler am Bus an. Der USB-Anschluss ist vom
KNX Bus galvanisch getrennt.
Installation und Inbetriebnahme
Das KNX USB Interface 332 Stick ist als USB-Stick ausgeführt
und kann an eine USB-Schnittstelle Typ A verwendet werden. Er
besitzt folgende Bedienelemente und Anzeigen:
Die Spannungsversorgung erfolgt über den USB Anschluss
durch den PC.
Bei fehlendem USB-Anschluss ist das Gerät ohne Funk-
tion.
KNX Programmiermodus
Die physikalische Adresse der Schnittstelle wird über die ETS
lokal eingestellt. Aus diesem Grund sind kein Programmiertaster
bzw. Programmier-LED am Gerät vorhanden.
Statusanzeige
Die KNX LED
❷
leuchtet grün bei vorhandener KNX Busspan-
nung. Bei Flackern dieser LED findet Telegrammverkehr auf
dem KNX Bus statt.
Fehler in der KNX-Kommunikation (z.B. Telegrammwiederholun-
gen oder Telegrammfragmente) werden durch einen kurzzeitigen
Farbwechsel zu rot angezeigt.
Zusammenfassung der Zustände der KNX LED
❷
:
Die USB LED
❹
leuchtet grün, wenn das Gerät an USB ange-
schlossen ist. Bei Flackern dieser LED findet USB-
Telegrammverkehr.
Fehler in der USB-Kommunikation werden durch einen kurzzei-
tigen Farbwechsel zu rot angezeigt.
Zusammenfassung der Zustände der USB LED
❹
:
USB Suspend
Wenn der PC oder Laptop in den Ruhemodus wechselt, werden
auch angeschlossene USB-Geräte in den Ruhemodus versetzt,
um Energie zu sparen. Computer mit MS Windows® 8.1 oder
höher können auch im Normalbetrieb unbenutzte Peripheriege-
räte in den Standby-Modus setzen. Im Ruhe-Modus sind beide
LEDs der KNX USB Schnittstelle ausgeschaltet.
Werkseinstellungen
Ab Werk ist folgende Konfiguration voreingestellt:
Physikalische Adresse des Gerätes: 15.15.255
Schnittstelleneinstellungen in der ETS
In der ETS können Schnittstellen über das ETS Menü „Bus -
Schnittstellen“ ausgewählt und konfiguriert werden.
Nachdem das KNX USB Interface an den PC und den KNX Bus
angeschlossen wurde, erscheint automatisch in der ETS im
Menüpunkt „Bus“ unter „gefundene Schnittstellen“.
Durch Anklicken der gefundenen Schnittstelle wird diese als
aktuelle Schnittstelle ausgewählt. Auf der rechten Seite des ETS
Fensters erscheinen dann verbindungsspezifische Informationen
und Optionen.
Hier kann die physikalische Adresse des KNX USB Interfaces
geändert werden. Um zu überprüfen, ob die gewünschte physi-
kalische Adresse nicht bereits in der KNX Installation vorhanden
ist, kann die Schaltfläche „Adresse frei?“ betätigt werden.
LED Verhalten
Bedeutung
LED leuchtet grün
KNX Bus Spannung vorhanden
LED blinkt grün
Telegramme auf dem KNX Bus
LED leuchtet kurz rot auf
Kommunikationsfehler auf dem KNX Bus
LED leuchtet orange
Interface ist auf Bus Monitor Modus eingestellt
LED blinkt orange
Telegramme auf dem KNX Bus im Bus Monitor Modus
LED Verhalten
Bedeutung
LED leuchtet grün
USB aktiv
LED blinkt grün
Telegramme über USB
LED leuchtet kurz rot auf
Kommunikationsfehler auf USB
DE
❶KNX Bus Anschluss
❷
KNX LED (mehrfarbig)
❸
USB Anschluss (Typ
A)
❹
USB LED (mehrfarbig)

18 www.eta.co.at
Appendix
2019 WEINZIERL ENGINEERING GmbH Seite 2/3
ETS Datenbank
Die ETS Datenbank (für ETS 4.2 und höher) kann auf der Pro-
duktwebsite (www.weinzierl.de) heruntergeladen werden.
Der ETS-Eintrag ist nicht erforderlich, um die KNX USB-
Schnittstelle als Programmierschnittstelle zu verwenden. Es ist
nur ein Platzhalter, um alle installierten Geräte in der Topologie
zu zeigen.
ETS Parameterdialog
Das KNX USB Gerät hat keine Parametereinstellungen. Der
Parameterdialog zeigt nur eine Beschreibungsseite an.
Busmonitormodus
Die KNX USB Schnittstelle unterstützt den Busmonitormodus,
der auch mit der ETS verwendet werden. Im Busmonitormodus
wird der gesamte Verkehr auf dem KNX-Bus mit ACK-, NACK-
und BUSY-Zeichen angezeigt.
Schnittstellen im Busmonitormodus verhalten sich auf dem Bus
völlig passiv und können daher nicht gleichzeitig für andere
Operationen wie Download verwendet werden. Zur Überwa-
chung eines ETS-Downloads innerhalb derselben ETS kann der
Gruppenmonitor verwendet werden. Der Gruppenmonitor nutzt
die KNX USB-Schnittstelle im Normalbetrieb (Data Link Layer)
und kann parallel zu anderen Busoperationen verwendet wer-
den. Im Gruppenmonitor ist auch das Senden von Telegrammen
möglich.
Hinweis: im Gruppenmonitor-Modus werden physikalisch adres-
sierte Telegramme, die nicht die KNX USB-Schnittstelle adres-
sieren, nicht empfangen.
KNX Long Frames
Standard-KNX-Telegramme sind auf eine APDU-Länge von 15
begrenzt. Die APDU-Länge ist die Anzahl der Bytes der Nutzda-
ten. Ein Gruppentelegramm mit einem 14 Byte String (KNX
Datenpunkt Typ 16) ergibt eine APDU Länge von 15.
Um die Effizienz der KNX-Kommunikation vor allem für den
Download zu erhöhen, wurde ein erweitertes Format definiert. Es
kann verwendet werden, um längere Telegramme auf den Bus
zu senden. Um diese Funktion nutzen zu können, muss sie
unterstützt werden von
xder Software (ETS)
xdem Bus Interface (USB)
xallen dazwischen-liegenden Kopplern
xdem adressierten Gerät
Die ETS ab Version 5 kann automatisch erkennen, ob Long
Frames verwendet werden können und optimiert den Download
entsprechend.
Die maximale APDU-Länge der KNX USB-Schnittstelle, die von
der ETS verwendet wird, beträgt 55. Diese Länge wurde als
Anforderung für neue KNX-Systemgeräte spezifiziert. Eine
APDU-Länge von 55 ergibt die Gesamtlänge eines KNX-
Telegramms auf Twisted Pair von 64 Bytes und belegt den Bus
für ca. 90 ms.
Der Download ist deutlich schneller, wenn die USB-
Schnittstelle in der gleichen Linie wie das Zielgerät in-
stalliert ist. Mit jedem Linienkoppler dazwischen wird die
Downloadzeit länger.
Hinweise für Entwickler
Die KNX USB Kommunikation basiert auf dem HID/cEMI-
Protokoll entsprechend der KNX-Spezifikation. Um die KNX USB
Schnittstelle in eigene Anwendungen unter Windows oder Linux
zu integrieren, steht das Cross-Plattform SDK kDrive von Wein-
zierl zur Verfügung.
Neben der Telegrammschnittstelle über cEMI verfügt die KNX
USB Schnittstelle 332 über einen kompletten KNX Stack mit
Kommunikationsobjekten und BAOS Protokoll V2. So bietet das
Gerät die Möglichkeit, Geräte mit USB-Anschluss (z.B. Boards
mit embedded Linux) zu vollwertigen KNX-Geräte zu erweitern,
die sogar mit der ETS programmiert werden können.
Für weitere Informationen über diese Lösung und verfügbare
SDKs wenden Sie sich bitte an WEINZIERL.

Appendix
19
2019 WEINZIERL ENGINEERING GmbH Seite 3/3
WARNUNG
Das Gerät darf nur von einer zugelassenen
Elektrofachkraft installiert und in Betrieb ge-
nommen werden.
Die geltenden Sicherheits- und Unfall-
verhütungsvorschriften sind zu beachten.
Das Gerät darf nicht geöffnet werden.
Bei der Planung und Errichtung von elektri-
schen Anlagen sind die
einschlägigen Richtli-
nien, Vorschriften und Bestimmungen des je-
weiligen Landes zu beachten.
ETS4/5 Datenbank
www.weinzierl.de/de/products/332/ets4
Datenblatt
www.weinzierl.de/de/products/332/datasheet
CE
-Erklärung
www.weinzierl.de/de/products/332/ce-
declaration
Ausschreibungstext
www.weinzierl.de/de/products/332/tender-text
Weinzierl Engineering GmbH
D-
84508 Burgkirchen / Alz
Deutschland
www.weinzierl.de
info@weinzierl.de
05.03
.2019

www.eta.co.at
www.eta.co.at/downloads
DOWNLOAD
Table of contents
Popular Control System manuals by other brands

RECO
RECO EasyLine RM-216 CB.11 Operating and installation instructions

Speco
Speco A1 installation instructions

Woodward
Woodward AtlasSC 8273-040 Installation and operation manual

Gecko
Gecko in.yj-2 Quick start card

Inovance
Inovance Monarch MCTC-PEC-E1 user guide

Wesco
Wesco FLUSHMASTER WES10-M Installation & setup guide