ETC Unison ERn2-W User manual

Part Number: 7180M2100 Rev: C
Released: 2020-06
ERn Wall-mount Enclosure
Installation Manual

Table of Contents i
Table of Contents
Introduction. . . . . . . . . . . . . . . . . . . . . . . . .1
ERn External Processing Rack. . . . . . . . . . . . . . . . . . . . .1
ERn2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
ERn4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
ERn Modules and Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Contacting ETC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Prepare for Installation . . . . . . . . . . . . . . . .6
Unpack and Inspect . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Main Circuit Breaker Protection . . . . . . . . . . . . . . . . . .6
Maximum Current Input . . . . . . . . . . . . . . . . . . . . . . . .6
Where to Install the Enclosure. . . . . . . . . . . . . . . . . . . .6
Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Rack Dimensions and Weights. . . . . . . . . . . . . . . . . . . . . . . . . .7
Installation Environment Requirements . . . . . . . . . . . . . . . . . .7
Wire Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Wire Routing and Specification. . . . . . . . . . . . . . . . . . . . . . . . .8
Input Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Control Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Data Types and Topologies . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Install Rack Enclosures. . . . . . . . . . . . . . . .10
Install the Rack Enclosure. . . . . . . . . . . . . . . . . . . . . . .10
Rough-in Conduit and Wiring . . . . . . . . . . . . . . . . . . .11
Remove Option Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Rough-in Line and Control Conduit and Wiring . . . . . . . . . .12
Terminate Wiring . . . . . . . . . . . . . . . . . . .13
Connect Line Power Wiring . . . . . . . . . . . . . . . . . . . . .13
Connect Control Wiring . . . . . . . . . . . . . . . . . . . . . . . .14
Connect ERn Right I/O Data Terminations . . . . . . . . . . . . . . .15
Connect ERn Left I/O Data Terminations . . . . . . . . . . . . . . . .18
Final Installation and Power Up . . . . . . . .21
Check Main Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Check Line Voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Final Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Install Rack Options. . . . . . . . . . . . . . . . . .24
Rack Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24

ii ERn Wall-mount Installation Manual
Install the RideThru Option (URTO) Kit. . . . . . . . . . . . . . . . . .24
Install the BatteryPack Option (UBPO) Kit . . . . . . . . . . . . . . .26
Install a Paradigm Repeater or Dual Repeater Module . . . . .28
Install Redundant Power Supply . . . . . . . . . . . . . . . . . . . . . . .31
Status Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Install the Ethernet Switch Module. . . . . . . . . . . . . . . . . . . . .32
Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35

Introduction 1
Introduction
Welcome to the installation manual for the Unison ERn External Control Enclosure. This
manual contains the procedures for safe and efficient installation of wall-mount ERn series
control enclosures, including wire termination and option kit installation.
ERn series enclosures provide Unison architectural control to distributed Unison, Sensor, or
other DMX512 systems. Used stand alone or in multi-processor network systems, the
wall-mount ERn series offers elegant low-profile surface mounting, modular back-lit control
electronics, and the ultimate in architectural lighting control versatility.
ERn External Processing Rack
The ERn enclosure is available in two sizes, ERn2 (single processor) and ERn4 (dual processor),
The ERn is available in three single phase voltage options, 100-120, 230 CE, and 240 VAC to
meet your installation requirements. See the technical datasheet on the ETC website
etcconnect.com for a full listing of available models.
ERn2
The ERn2 enclosure supports a single Paradigm Architectural Control Processor (P-ACP) and
one Paradigm Station Power Module (P-SPM) or a blank module (ERn-BM). The accessory tray
in the bottom of the enclosure can be used for an additional accessory option including a
5-port Ethernet Switch (ERn-NET) or a Redundant Rack Power Supply (ERn-RPS).
ERn4
The ERn4 enclosure supports up to two Paradigm Architectural Control Processors (P-ACP)
and two Paradigm Station Power Modules (P-SPM) or a Paradigm Repeater Module (P-REP).
Alternatively, the top two slots in the enclosure may be used for a Paradigm Dual Repeater
Module (P-DREP). The accessory tray in the bottom of the enclosure can be used for an
additional accessory option including a 5-port Ethernet Switch (ERn-NET) or a Redundant
Rack Power Supply (ERn-RPS).

2ERn Wall-mount Installation Manual
ERn Modules and Options
P-ACP
P-SPM
P-REP
P-DREP
ERn-NET
ERn-RPS
UBPO
URTO
ERn-BM
Model Part
Number Description Notes
P-ACP 7180A1001 Paradigm
Architectural Control
Processor
The P-ACP provides powerful and flexible control for
architectural and theatrical applications with integrated
networking for both NetConnect and LinkConnect networks.
• Supports up to 1024 control channels using industry
standard protocols.
• User interface remains accessible with the enclosure door
closed.
• Supports up to 62 Unison control stations over the
LinkConnect network with the use of Paradigm Station
Power and Repeater Modules.
• Supports up to 12 Paradigm Touchscreen Stations using
LinkConnect or NetConnect protocols.
• Provides two ports, one DMX universe each (512 addresses
each), individually switchable between input and output.
P-SPM 7182A1001 Paradigm Station
Power Module
The P-SPM supplies power for Unison control stations and
sensors over the LinkConnect network, up to 500 m
(1,640 feet).
• Supports up to 32 Unison control stations over
LinkConnect.
P-REP 7182A1003 Paradigm Station
Repeater Module
The P-REP extends the system station bus length by 500 m
(1,640 feet) and increases the possible station count by an
additional 30 stations and sensors. For use only in an ERn4
enclosure.
• For use in an ERn4 enclosure only.
• Supports up to 30 additional Unison control stations over
LinkConnect.
P-DREP 7182A1004 Paradigm Dual
Station Repeater
Module
The P-DREP extends the system station bus length by
1,000 m (3,280 feet) through two separate topology-free
segments, each supporting 500 m (1,640 feet).
• The dual repeater supports up to 30 additional Unison
control stations and sensors.
• For use in an ERn4 enclosure only.

Introduction 3
ERn-NET 7180A1400 ERn Ethernet Switch
Module
The ERn-NET module provides four ports of 802.3af
compliant Power over Ethernet (PoE) and one port for the P-
ACP.
• Not compatible with a rack-mount ERn enclosure.
• Not compatible with ERn4 230 VAC enclosures.
UBPO 7180A1411 Unison Battery Pack
Option Kit
The UBPO provides back-up power during power outages for
the P-ACP for up to 90 minutes for an ERn enclosure with
one P-ACP or up to 45 minutes for an ERn4 with two P-ACPs
installed.
• Not compatible with a rack-mount ERn enclosure.
URTO 7180A1410 Unison Ride Thru
Option Kit
The URTO kit provides power for one P-ACP in the host
enclosure for a limited time (minimum of 12 seconds) during
brief power outages or drop outs.
• If installed in an ERn4 enclosure, one URTO is required per
installed P-ACP.
ERn-BM 7180A1402 Blank Module The ERn-BM is required for any empty module space in the
ERn enclosure.
• Installs into the accessory option module slot of an ERn
enclosure.
ERn-RPS 7180A1401 ERn Redundant
Power Supply
The ERn-RPS provides an additional rack power supply that
powers the ERn enclosure if the primary rack power supply is
removed or fails.
• Tool-free installation into the accessory option slot of an
ERn enclosure.
• Not supported in ERn4 230 VAC enclosures. The
ERn4 230 VAC enclosure requires two rack power supplies
as standard.
Model Part
Number Description Notes

4ERn Wall-mount Installation Manual
Warnings and Notice Conventions
These symbols are used throughout this installation manual to alert you to danger or
important information:
Note:
Notes are helpful hints and information that is supplemental to the main text.
CAUTION:
A Caution statement indicates situations where there may be undefined or
unwanted consequences of an action, potential for data loss or an equipment
problem.
WARNING: A Warning statement indicates situations where damage may occur, people
may be harmed, or there are serious or dangerous consequences of an action.
WARNING: RISK OF ELECTRIC SHOCK! This warning statement indicates situations where
there is a risk of electric shock.

Introduction 5
Contacting ETC
For questions about Unison rack system delivery, contact ETC Systems Group. For general
information, your most convenient resources are the references provided in this manual. To
search more widely try the ETC web site at etcconnect.com.
For technical questions about Unison rack systems, contact ETC Technical Services directly at
one of the offices listed below. Emergency service is available from all ETC offices outside of
normal business hours. When calling for assistance, please have the following information
handy:
• Your location and job name.
• A complete list of ETC equipment.
• A complete list of other installed products and components connected to the system you are
troubleshooting.
• DMX control source, if any
Americas United Kingdom
ETC, Inc. ETC Ltd - UK
Technical Services Department Technical Services Department
3031 Pleasant View Road 26-28 Victoria Industrial Estate
Middleton, WI 53562 Victoria Road,
800-775-4382 (USA, toll-free) London W3 6UU England
+1-608 831-4116 +44 (0)20 8896 1000
Asia Germany
ETC Asia ETC GmbH
Technical Services Department Technical Services Department
Room 1801, 18/F Ohmstrasse 3
Tower 1, Phase 1 Enterprise Square 83607 Holzkirchen, Germany
9 Sheung Yuet Road +49 (80 24) 47 00-0
Kowloon Bay, Kowloon, Hong Kong techserv-germany@etcconnect.com
+852 2799 1220
techserv-asia@etcconnect.com
France
ETC France
Zone Urbaparc -
Bâtiment E
6 Boulevard de la Libération
Saint-Denis, 93200
+33 1 4243 3535

6ERn Wall-mount Installation Manual
Chapter 1
Prepare for Installation
Unpack and Inspect
Before you begin installation, check your shipment and confirm it arrived complete and undamaged.
1: Check the shipping container for physical damage.
2: If you find damage, document it to help with a claim against your shipper.
3: Unpack your order and check the contents against the packing list to be sure your order is
complete.
4: If you discover a problem, call ETC Systems Group.
Main Circuit Breaker Protection
Before you begin installing the Unison external processing rack enclosure, make sure you have installed
a main circuit breaker cabinet or other readily accessible input power disconnect device in the same,
room or in close proximity to the installed ERn enclosure.
Maximum Current Input
The ERn enclosure draws a maximum current of 3.5 amps when fully populated. The maximum
allowable protection device rating is:
• 20A at 120 VAC
• 15A at 230/240 VAC
Where to Install the Enclosure
The Unison External Processing Enclosure (ERn) can be wall-mounted or rack-mounted depending on
the model ordered. For rack-mounted installation instructions see the
ERn Rack-mount Enclosure
Installation Manual
.
Install the ERn wall-mount enclosure on a load bearing wall that is located in an electrical closet or a
room with restricted public access. It is recommended that you install the rack at least 914.4 mm
(36 in) off the floor surface to ensure clear view of the P-ACP for programming and general operation.
WARNING: Circuits that are installed without an accessible power disconnect device
cannot be serviced or operated safely. Follow local codes and restrictions.
AVERTISSEMENT: Il est imprudent d'utiliser ou de réparer les circuits installés sans qu'un
dispositif de déconnexion de l'alimentation ne soit accessible.

Prepare for Installation 7
Clearance Requirements
152 mm
(6”)
394 mm
(15.5”)
914.4 mm
(36”)
Install the ERn enclosure with:
• a minimum of 294 mm (15.5 in) front clearance
for proper door operation.
• a minimum of 152 mm (6 in) clearance from
the left and right sides from walls or other
equipment to allow proper convection airflow
in the enclosure.
Rack Dimensions and Weights
Installation Environment Requirements
A clean (not dusty), temperature controlled environment with the following conditions:
• ambient temperature of 32-104°F / 0-40°C
• ambient humidity of 10-90%, non-condensing
• Restricted public access to prevent tampering is recommended.
• CE Marked equipment, tested to EMC category B environment.
Rack Type
Height Width Depth Product
Weight
Shipping
Weight
inches mm inches mm inches mm lbs kgs lbs kgs
ERn2 - W 8.8 223 15.5 394 9.6 244 15 6.8 20 9.1
ERn4 - W 14.1 358 15.5 394 9.6 244 20 9.1 25 11.3
CAUTION:
HVAC systems must at all times maintain the specified ambient temperature
at the Unison ERn enclosure.

8ERn Wall-mount Installation Manual
Wire Requirements
Wire Routing and Specification
Unison ERn enclosures have conduit knockouts on the top and bottom for incoming power and control
wiring. Alternatively, conduit knockouts are located on both sides of the rack for control signal wiring
as needed. Signal and power wiring must be run in separate conduit in accordance with national and
local codes.
Control and power must be run in separate conduit.
Input Power
Control Specifications
The riser below is typical of a system utilizing the ERn enclosure with the Paradigm Architectural
Control Processor (P-ACP). Paradigm systems provide up to two DMX inputs for control of more
advanced systems. A Paradigm system also utilizes Net3 networking for system wide control.
The following table lists the recommended control wire types used in a typical Unison installation and
the maximum wire runs allowed.
Wire Access
Location
Wire Size
Single Phase, 20A
2 wire + gnd Control Wires
Top of rack preferred acceptable
Bottom of rack preferred acceptable
Left side acceptable acceptable
Right side acceptable acceptable
LinkConnect
DMX input
to ERn rack
ETC Console
(for optional stage lighting)
LinkConnect
Aux Power 24 Vdc
Preset10
Preset6
Preset7
Preset9
Preset8
Preset5
Preset1
Preset2
Preset4
Preset3
Preset10
Preset6
Preset7
Preset9
Preset8
Preset5
Preset1
Preset2
Preset4
Preset3
Preset5
Preset1
Preset2
Preset4
Preset3
Preset5
Preset1
Preset2
Preset4
Preset3
Preset5
Preset1
Preset2
Preset4
MacroRecord
Sequence
Preset3
Preset5
Preset1
Preset2
Preset4
MacroRecord
Sequence
Preset3
dimmer rack dimmer rack
Unison DRd12
rack enclosure
Unison ERn4
processing rack
Unison Paradigm
Touchscreen LCD
Unison Heritage
Stations
SYSTEMLORTNOCGNIHGIL T SYSTEMLORTNOCGNIHGIL T
power
feed
power
feed
power
feed
power
feed

Prepare for Installation 9
Data Types and Topologies
LinkConnect
LinkConnect is the station communication bus from the Architectural Control Processor to the stations.
LinkConnect is based on Echelon LonWorks with LinkPower bidirectional protocol, and uses one pair of
wires (data +, data -). An additional 2.5 mm2 (14 AWG) wire for grounding is required when the wiring
is not installed in grounded metal conduit.
LinkConnect is topology-free and polarity independent, you can install your LinkConnect data runs in
any desired combination of bus, loop, star, and home run. ETC recommends the use of Belden 8471
(or approved equal) wire. The total combined length of a LinkConnect wire run cannot exceed 500 m
(1,640 feet) with a maximum distance of 400 m (1,312 feet) between any two devices.
DMX
DMX can address up to 512 channels of control. DMX is installed in a daisy chain topology and includes
one pair of wires (data+ and data-) plus ground. ETC recommends the use of Belden 9729 (or
approved equal) wire with a single end of line termination (90-150 For best DMX performance,
twist the wires together as close to the pluggable connector as possible. DMX devices manufactured by
ETC are compliant with the USITT DMX512A standard.
Auxiliary 24 VDC
Auxiliary power is required when you are installing powered Unison control devices. ETC recommends
using two 1.5 mm2(16 AWG) stranded wires for 24 VDC auxiliary power. Maximum auxiliary voltage
runs are dependant by the wire gauge and the distribution of auxiliary load determined by installation.
The auxiliary supply is capable is of 36 W (1.5 A at 24 VDC).
Purpose
Stations (Belden
8471)
DMX (Belden
9729)
Ethernet (Cat5
/Belden 1583a)
Feet Meter Feet Meter Feet Meter
Total length of control wire
(without repeater module) 1640 500 1600 487 328 100
Maximum wire length (device
to device) 1313 400 1600 487 N/A N/A
Maximum repeater distance 1640 500 N/A N/A N/A N/A
Note:
Repeater modules may be used to extend the LinkConnect station data bus an
additional 500 m (1,640 feet), with a maximum distance of 400 m (1,313 feet)
between the repeater and any station or station power supply.

10 ERn Wall-mount Installation Manual
Chapter 2
Install Rack Enclosures
Install the Rack Enclosure
The wall must be strong enough to hold the rack fully populated with modules, conduit and wire. The
maximum weight of an ERn enclosure is approximately 20.4 kg (45 lbs).
1: Determine where your rack will be installed using the weight and dimension requirements
detailed in
Where to Install the Enclosure
on
page 6
.
2: Use the measured slot dimensions located in the graphic below to mark the hole locations for the
mounting hardware.
3: Drill the holes and install the mounting hardware for each rack.
• Four 8-10 mm (3/8 in) bolts or screws 50-100 mm (2-4 in) long, and suitable wall plugs are
suggested mounting hardware (lag bolts recommended).
• All hardware must support the weight of the rack unit fully populated with modules.
• Expose at least 25 mm (1 in) of threads for mounting the rack.
4: Attach the rack enclosure to the mounting hardware using the mounting keyholes.
5: Check that the rack is level and plumb, and then tighten the mounting hardware for a secure
installation.
ERn2 - 8.9” / 226mm
ERn4 - 14.2” / 360.7mm
5.5”
139.7mm 5.5”
139.7mm
4.5”
114.3mm
15.5”
393.7mm
ERn2 - 6.8” / 172.7mm
ERn4 - 12” / 304.8mm
3.4”
86.4mm
ERn enclosure rear panel

Install Rack Enclosures 11
Rough-in Conduit and Wiring
Remove Option Modules
Prior to installing conduit and pulling wires into the ERn enclosure, remove the rack power supply (top
of enclosure) and blank option module (bottom of enclosure) to provide a access to the conduit
openings.
1: Loosen the two captured thumbscrews that secure the rack power supply to the ERn enclosure.
2: Pull the supply straight out of the rack.
3: Repeat for the blank option module, Ethernet Switch, or secondary power supply.
4: Place these modules in a safe place until the conduit rough-in and wiring terminations are
complete.
WARNING: RISK OF DEATH BY ELECTRIC SHOCK! Before installing input power, make
sure the upstream source of power is off or isolated. Follow appropriate
Lockout/Tagout procedures as described in NFPA Standard 70E.
AVERTISSEMENT: RISQUE DE MORT PAR ÉLECTROCUTION! Avant d'installer l'alimentation
d'entrée, assurez-vous que la source d'alimentation en amont est éteinte ou
isolée. Suivez les procédures de Consignation/Déconsignation appropriées
prescrites par la norme NFPA 70E.
Note:
For 230 VAC CE enclosures, before removing any modules, loosen the hardware and
slide the module retention bar to the left.
Note:
An ERn4 at 230 VAC does not support the Redundant Rack Power Supply (ERn-RPS)
nor the Ethernet Switch Option Module (ERn-NET). Instead an ERn4 at 230 VAC is
shipped from the factory with a rack power supply installed in the top (normal)
position and in the lower option module slot.
Rack power supply (ERn-PS)
The blank option module installed at
shipment can be replaced with either
the Ethernet Switch Module (ERn-NET)
or the Redundant Power
Supply (ERn-RPS).

12 ERn Wall-mount Installation Manual
Rough-in Line and Control Conduit and Wiring
The ERn enclosure requires line power and control wire terminations. For installation convenience all
terminations are accessible from the front of the rack. A single phase line power and all required
control wires may be pulled through any of the conduit knockouts provided, or other labeled locations.
1: Plan wire entry to the rack. See
Wire Routing and Specification
on
page 8
.
2: Remove the required conduit knockouts from the rack or punch new conduit holes. Pay special
attention to the rack design so that you do not punch conduit access in a location that will
prevent components from being installed.
3: Install conduit fittings or insert lining materials in the new opening.
Note:
Control (signal) wiring and power wiring must be run in separate conduit in
accordance with local code.
CAUTION:
Wire openings must have fittings, bushings, grommets or fish paper lining
material to protect wire and cable insulation from damage by sharp metal
edges.
L
N

Terminate Wiring 13
Chapter 3
Terminate Wiring
Connect Line Power Wiring
ERn enclosures are available in 100-120, 230 CE, and 240 VAC single phase configurations. The ERn
enclosure requires a single phase, 20 amp (maximum) at 120 VAC input feed or a 15 amp (maximum)
at 230 and 240 VAC. The two-wire hot and neutral terminates to the power input terminal block
(terminals accept 2.5 - 0.13 mm2/ 12 - 26 AWG) and a ground wire terminates to the ground bar.
1: Pull the line, neutral, and ground cables to the enclosure through the conduit openings
previously prepared.
2: Strip each wire 10 mm (0.4 in).
3: Insert the ground wire into a screw terminal on the ground terminal block and secure.
4: Use a flat blade screwdriver to open the Neutral terminal block and insert the neutral wire.
Remove the screwdriver to secure the wire into the terminal.
5: Repeat for the Line (hot) wire into the L terminal block.
WARNING: All rack terminations must be done with the power off. Racks installed
without an accessible power disconnect device cannot be serviced or
operated safely.
L
N

14 ERn Wall-mount Installation Manual
Connect Control Wiring
Low voltage data connects to pluggable connectors on the left and right input/output boards of the
ERn enclosure. The ERn2 includes only one each left and right I/O board while the ERn4 includes two
of each.
• The left I/O provides termination for contact inputs and outputs, RS-232 serial, and Ethernet
control.
• The right I/O provides termination for LinkConnect, auxiliary power, DMX in, DMX Out, DMX
through, and all enclosure option kits. The right I/O also provides termination for option modules
installed on the bottom module slot of the rack enclosure for enhanced control and operation.
Note:
All low voltage control cables must be run in separate conduit from power wires in
accordance with local codes.
WARNING: RISK OF DEATH BY ELECTRIC SHOCK! Failure to disconnect all power to the
rack before working in the enclosure could result in serious injury or even
death.
L
N
Right I/O boards
Left I/O board(s)
Wire tie down locations are
provided on the rear panel.

Terminate Wiring 15
Connect ERn Right I/O Data Terminations
Aux Power
2
4
V In
LO
N
-+ - + -
+
-
+-
+
BA B AB
A
B A B A B
A
D
M
X
A
RPS I
n
CDI
LO
N
DM
XB
DM
XA
Ride Thr
u
/Ba
t
t
DMX B
DMXPass-Thru
Auxiliary Power - 24 VDC out
LinkConnect control
DMX A
Input/Output
DMX Pass-Thru
DMX B
Input/Output
ERn-RPS In
Ride Thru / Batt
24 VDC In
Terminate DMX Control Wiring
DMX wire preparation and termination will vary with the type of wire and termination kit being
utilized. Please refer to the instructions supplied with the DMX termination kit for specifics on the wire
preparation.
Note:
The 24 VDC connection is the power Supply (ERn-PS) connection and is connected
for you at the factory. The ERn-RPS and Ride Thru / Batt terminations are detailed in
Rack Options on page 24 .

16 ERn Wall-mount Installation Manual
DMX Input Termination: Screw Terminals Connector
12345678
COM
n/c
n/c
n/c
n/c
n/c
Data + (Red)
Data - (Black)
From source
DMX A
If daisy-chaining to
another rack or
DMX device...
This graphic illustrates DMX termination layout for the screw-
terminal connectors that are intended for use with Belden 9729
cable (or approved equal) cable type.
Screw terminal connectors are supplied as standard in the DMX
Preparation Kit w/ Screw Connector, part number 4100A1012.
Be aware that cable other than Belden 9729 may have a different
color code for its wire pairs.
DMX Input/Output Termination: Insulation Displacement Connectors
The graphic below illustrates DMX termination layout for an insulation displacement connector (IDC).
This connector type is intended for use with belden 1583A (or approved equal, such as Category 5, 5E,
or 6) cable type.
The insulation displacement connector kit (IDC) may be requested from the factory but is not supplied
as standard. Request the IDC Pluggable Connector Termination kit, part number 4100A1013. Be
aware that cable other than Belden 1583A may have different color code for its wire pairs.
Terminate LinkConnect Control Wiring
Unison control stations and sensors communicate with the P-ACP over LinkConnect. See
Wire
Requirements
on
page 8
. Termination is available for up to twelve home runs of LinkConnect utilizing
Belden 8471 cable (or its equivalent) plus one 14 AWG (2.5 mm2) ESD drain wire when the data cable
is not installed in grounded metal conduit.
LinkConnect wiring is topology-free and polarity independent. Wiring may be bus, star, loop, home
run or any combination of these. Total combined length of LinkConnect data runs cannot exceed
500 m (1,640 feet), with a maximum distance of 400 m (1,313 feet) between any two communicating
devices. Without a repeater, no device may be more than 400 m (1,313 feet) away from the P-ACP.
Standard interoperability requires that there should be a maximum of only one station repeater
between any two LinkConnect devices. This means that only one repeater module, whether a
Paradigm Repeater module (P-REP) or a Paradigm Dual Repeater Module (P-DREP), may be used per
P-ACP.
Note:
All low voltage control cables must run in separate conduit from power wires in
accordance with local codes.
12345678
n/c
n/c
COM
Data +
Data - ORG
W/ORG
W/BRN
COM
Data +
Data - ORG
W/ORG
W/BRN
Use this DMX Pass-Thru
connector when
daisy-chaining to
another rack or
DMX device...
DMX A
Thru
DMX B
Thru
1234567812345678
COM
Data +
Data +
Data -
Data - ORG
W/ORG
BRN
GRN
W/GRN
BLU
W/BLU
W/BRN
ORG
W/ORG
BRN
GRN
W/GRN
BLU
W/BLU
W/BRN
COM
From source
DMX A
From source
DMX B
This manual suits for next models
1
Table of contents
Other ETC Enclosure manuals

ETC
ETC 7180A1018 User manual

ETC
ETC OneTrack Backbone T-coupler Housing User manual

ETC
ETC OneTrack Backbone I-coupler Housing User manual

ETC
ETC Unison AX Series User manual

ETC
ETC DRd6-12-120 User manual

ETC
ETC 7180A1018 User manual

ETC
ETC OneTrack Backbone End Feed Housing User manual

ETC
ETC Sensor+ SR+ Series User manual
Popular Enclosure manuals by other brands

Hama
Hama USB 2.0 2.5" SATA HDD MAC Enclosure Operating instruction

Middle Atlantic Products
Middle Atlantic Products HDR Series instruction sheet

AZZA
AZZA OVERDRIVE manual

AFL
AFL OptiNID Duo Quickstart installation instructions

Pulsar
Pulsar AWO385 installation instructions

AZZA
AZZA PYRAMID MINI 806 user manual