Technical data CES-A-ABA-01B
Parameter Value Unit
min. typ. max.
Housing material PA6.6 plastic
Dimensions 114x99x22.5 mm
Weight 0.2 kg
Ambient temperature at UB=DC 24 V -20 - +55 °C
Atmospheric humidity, not condensing - - 80 %
Degree of protection IP20
Degree of contamination 2
Mounting Mounting rail 35mm according to DIN EN 60715
Number of read heads 1 read head per evaluation unit
Connection (plug-in screw terminals/coded) 0.14 - 2.5 mm²
Operating voltage UB(regulated, residual ripple < 5 %) 21 24 27 V DC
For the approval according to the following applies Operation only with UL class 2 power supply or equivalent measures
Current consumption IB(with relay energized) 1) - 150 - mA
External fuse (operating voltage UB) 0.25 - 8 A
Safety contacts 2 (relays with internally monitored contacts)
Switching current (relay outputs)
mA
- at switching voltage AC/DC 21…60 V 1 - 300
- at switching voltage AC/DC 10…30 V 10 - 6000
Switching load according to Max. AC 30 V, class 2/max. DC 60 V, class 2
External fuse (safety circuit) according to EN60269-1 6 A gG or 6 A circuit breaker (characteristic B or C)
Utilization category according to EN60947-5-1 AC-12 60 V 0.3 A/DC-12 60 V 0.3 A
AC-12 30 V 4 A/DC-12 30 V 6 A
AC-14 30 V 2 A/DC-13 24 V 3 A
Rated insulation voltage Ui63 V
Rated impulse withstand voltage Uimp 1.5 kV
Rated conditional short-circuit current 100 A
Resilience to vibration In acc. with EN60947-5-2
Mechanical operating cycles (relays) 10x106
Switching delay from state change 2) - - 180 ms
Discrepancy time (of the switching points of both relays) - - 120 ms
Ready delay 3) - - 3 s
Dwell time 4) 0.5 - - s
Switching frequency max. 5) - - 1 Hz
Repeat accuracy R acc. to ENIEC60947-5-3 ≤10 %
Monitoring outputs (diagnostics ERR, door monitoring output
OUT, semiconductor output, p-switching) 6)
- Output voltage 0.8xUB- UBV DC
- Max. load - - 20 mA
Test input TST
- Input voltage LOW 0 - 2 V DC
HIGH 15 - UB
- Input current HIGH 5 8 10 mA
EMC protection requirements In acc. with EN60947-5-3
Reliability values acc. to ENISO13849-1
as a function of the switching current at 24 V DC ≤0.1 A ≤1 A ≤3 A
Category 3
Performance Level (PL) e
PFHd4.3x10-8
Mission time 20 years
Number of switching cycles/year 760 000 153 000 34 600
Diagnostic coverage DC 90 %
MTTFd100 years
1) Without taking into account the load currents on the monitoring outputs.
2) Corresponds to the risk time according to EN60947-5-3. This is the maximum switch-off delay for the safety outputs following removal of the actuator.
3) After the operating voltage is switched on, the relay outputs are switched off and the door monitoring output is set to LOW potential during the ready delay.
4) The dwell time of an actuator inside and outside the operating distance must be at least 0.5s to ensure reliable detection of internal faults in the evaluation unit (self-monitoring).
5) If the current load is >100mA, a switching frequency of 0.1 Hz should not be exceeded as this will affect the mechanical life of the relay contacts.
6) Not short circuit-proof.