EWC Controls EWT-755WHO User manual

EWT-755WHO
Installation Manual
Thermostat Application Guide
Description
Gas or Oil Heat
Electric Furnace
Heat Pump (No Aux. or Emergency Heat)
Heat Pump (With Aux. or Emergency Heat)
Multi-Stage Systems
Heat Only Systems
Cool Only Systems
Millivolt
Yes
Yes
Yes
Yes
Yes
No
Power Type
Battery Power*
Hardwire (Common Wire)
Hardwire (Common Wire) with
Battery Backup
Table of Contents
Installation Tips
Private Label Badge
Thermostat Quick Reference
Wireless Communication Tips
Connecting To The PROsync
Wireless System
Wiring The Equipment Module
Wiring
Benets To Using The PROsync
Wireless System
Technician Setup Menu
Setting the Humidity
Programming
Specications
Page
A trained, experienced
technician must install this
product.
Carefully read these
instructions. You could damage
this product or cause a
hazardous condition if you fail
to follow these instructions.
Una version en español de este
manual se puede descargar en
la pagina web de la compañia.
Rev. 2321
U.S. Registered Trademark. Patents pending
Copyright 2023 All Rights Reserved.
2-6
11
1
Yes
Yes
12
Installation Tips
2
Installation Tips
The thermostat should be installed approximately 4 to 5 feet above the
oor. Select an area with average temperature and good air circulation.
• Close to hot or cold air ducts
• That are in direct sunlight
• With an outside wall behind the thermostat
• In areas that do not require conditioning
• Where there are dead spots or drafts (in corners or behind doors)
• Where there might be concealed chimneys or pipes
Wall Locations
Pick an installation location that is easy for the user to access. The temperature
of the location should be representative of the building.
Installation Tip
Do not install thermostat in these locations:
34
Installation Tips
13-16
17-18
8-9
7
10
19-35
36
Humidity
Dual Fuel
Yes
Yes
37-42
43-44
When performing an attic installation, instead of placing the
equipmentmodule in the attic, locate the closet nearest to the air
conditioning unit. We reccomend mounting the Equipment module
high on the wall inside the closet or on the ceiling of the closet. This
location will insure the equipment module is below the 150°F
maximum ambient temperature specication while also allowing easy
technician viewing.
Installation Tips
Do not install the base module in locations:
• That are behind a chimney
• Where temperature could exceed 150°F
• Where rain or snow or extreme hot or cold is possible
Note: This base module is NOT weatherproof.
Equipment Module -Attic Location
The PROsync System has been tested in many dierent types of building construction including wood, steel beam, and brick in spaces over
5500 square feet. The wireless range performs well across multiple oors successfully. The PROsync radios constantly search for open
channels to avoid interference and ensure messages are received. The PROsync system has been shown to reliably transmit data across
hundreds of feet indoors and over 1000 feet line of sight.
Living space
closet
Attic
Good
Living Space
Good
Good
No
Wireless Range
Equipment Module - Basement Location

Em.Heat
AutoCool
AutoIAQ
Set At
On LHM
Tech Set
Set Sched
Next
Run Sched
Set Time
Hold
Done
Menu
Prev
HOLD
STAGES
1+2+3+4
COOL ON
HEAT ON
FAN ON
Humidity
Zone
Yes
Humidity %
Outdoor AMPM
SunMonTue
WedThuFriSat
REMOTE
WAKELEAVE
RETURN
SLEEP
56
910
Installation Tips Installation Tips
Wireless Communication Setup
Follow these steps to setup the PROsync Wireless System
1. Choose the equipment module location.
2. Remove the front cover and attach the equipment module to the wall.
3. Wire the equipment module to the air handler.
4. Snap the cover back on. The C terminal light should be illuminated
indicating the equipment module is powered.
5. Install batteries in the main thermostat and ensure it is communicating
with the equipment module. Any changes to the main thermostat
that create a call will now be displayed at the equipment module
in the LEDs associated with the terminals.
6. Choose the install location for the T755WHO. In the tech settings, check
the “Signal Strength” tech setting and ensure the value is greater than zero.
7. Remove the subbase and attach it to the wall using screws and
anchors in the box.
8. If you want to hardwire the thermostat, connect the R and C wires.
9. Snap the thermostat onto the subbase. Make sure the connection
is secure and the display is illuminated.
10. Add any additional remote sensors as desired.
Note.
Each time a message goes back and forth between the remote
thermostat and the equipment module, the light on the equipment
module will blink blue twice, and the antenna icon on the remote will
blink twice.
Getting to know your thermostat
The low battery indicator is displayed when the AA battery power is low. Replace the
batteries when the indicator appears. If the system is in the low battery state for an
extended period, the system will operate with reduced temperature control. If battery power
is lost, the system will cease operation even if the equipment module is still connected.
Important
Indicates the current room temperature
Time and day of the week
Setpoint: Displays the selected setpoint temperature.
Hold is displayed when the thermostat program is permanently overridden.
System Operation Indicators:
The COOL ON, HEAT ON, or FAN ON will display when the COOL, HEAT, or
FAN is on. The compressor delay feature is active if these are ashing.
Low Battery Indicator: Replace batteries when this indicator is shown.
Menu Options: Shows dierent options.
Program Time Periods: This thermostat has 4 programmable time periods
per day.
System: Indicates current mode of operation.
Stages: 1 will appear in the display when the rst stage of heat or cool is on, +2
will appear for the second stage, +3 for third stage and +4 for fourth stage.
1
2
3
7
8
Globe: Globe is displayed if an energy ecient temperature has been selected.
Thermostat Quick Reference
Keypad Lockout: Indicates keypad lockout state is“Locked”.
Radio Antenna: This icon blinks when the thermostat receives a message
from the equipment module.
Vertical Mount
Horizontal Mount For horizontal mount put one screw on
the left and one screw on the right.
All of our products are mercury free. However, if the product you are
replacing contains mercury, dispose of it properly. Your local waste
management authority can give you instructions on recycling and
proper disposal.
Mercury Notice
Failure to disconnect the power before beginning to install this product
can cause electrical shock or equipment damage.
Installation Tip: Electrical Hazard
For vertical mount put one screw on
the top and one screw on the bottom.
Thermostat Subbase Installation Equipment Module Subbase Installation
For the equipment module mount 4 screws in each outer hole.
To connect the equipment module to the master thermostat, refer to
the directions on page 11 of this manual.
Note:
Wire the equipment module’s subbase the same way you would wire a
hardwired thermostat subase.
Wiring Note
The base module must be hardwired (C and R terminals connected to
24V power.)
Note:
Fan Mode: Indicates current air handler fan mode of operation.

Gently slide a screwdriver into the bottom edge of the badge. Gently turn
the screwdriver counter clockwise. The badge is held on by a magnet in
the well of the battery door. The badge should pry o easily.
DO NOT USE FORCE.
About The Badge
All of our thermostats use the same universal magnetic badge. Visit the
company website to learn more about our free private label program.
Private Label Badge
78
11 12
Magnet in door
Use the bevel on lower ridge
Wiring For The Equipment Module
Caution:
Electrical Hazard
All components of the
control system and the
thermostat installation must
conform to Class II circuits
per the NEC Code.
Warning:
Do not overtighten
terminal block screws,
as this can damage the
terminal block. A
damaged terminal block
can keep the thermostat
from tting on the
subbase correctly or
cause system operation
issues.
Installation Tip
Max Torque = 6in-lbs.
Wiring
If you are replacing a thermostat,
make note of the terminal
connections on the thermostat that
is being replaced. In some cases
the wiring connections will not be
color coded. For example, the
green wire may not be connected
to the Gterminal.
Loosen the terminal block screws.
Insert wires then retighten the
terminal block screws.
Place nonammable insulation into
the wall opening to prevent drafts.
1.
2.
3.
Wiring Tips
C Terminal
The C (common wire) terminal does
not have to be connected when the
thermostat is powered by batteries.
Wire Specications
Use shielded or non-shielded 18-22
gauge thermostat wire.
Failure to disconnect the power
before beginning to install this
product can cause electrical shock
or equipment damage.
Note:
In many heat pump systems with
no emergency heat relay, a jumper
can be installed between W1 and
W2 to turn thermostat into a single
stage control for Emergency Heat
Operation.
Getting to know your thermostat
Glow in the dark light button
Fan Button
System Button
Temperature Setpoint Buttons
User Buttons
LCD Display
Private Label Badge
Thermostat Quick Reference
Occupancy Sensor
Adding A Remote Sensor
Establishing communication between a remote sensor and
the equipment module
The main thermostat and equipment module in this package are linked at
our factory. Upon power up, they will automatically begin to communicate.
If you wish to add additional remote sensors, follow the instructions on this
page.
1. Press the PAIR button on the equipment module. The equipment
module will begin double blinking pink for 2 minutes while it listens for a
new remote.
2. Press and hold the light button on the unpaired remote sensor to be
added. The remote sensor will show “PAIRING” on the main screen.
3. When the remote sensor is successfully paired to the equipment module,
the LCD will display“PAIRED” and the equipment module Pair button LED
will blink green.
4. Repeat the process for additional remote sensors.
How To Pair
Network Troubleshooting
For any of the conditions listed below, please visit our website for
troubleshooting instructions at www.pro1iaq.com/prosync
.
Light Color Blinking Type Description
White Single Blink
(slow)
Equipment module network reset - no remotes
paired or connected. Equipment module will
not energize the heating and cooling system.
All remote thermostats are connected to the
equipment module, network is healthy.
Green Single Blink
Yellow Double Blink One or more remote thermostats are
disconnected from the equipment module.
Red Triple Blink All remote thermostats are disconnected.
Equipment module will not energize the
heating and cooling system.
If your remote shows “NO COMM TO BASE” in the text eld, this indicates the
remote thermostat cannot communicate with the equipment module.
Equipment Module Troubleshooting

Wiring
Wiring
13 14
17 18
Terminal Designations on the Equipment Module
This thermostat is shipped from the factory to operate a conventional heating
and cooling system. This thermostat may also be congured for a heat pump
system. See the “heat pump” conguration step on page 16 of this manual to
congure the thermostat for heat pump applications.
Terminal
2 Heat 2 Cool
Conventional
System
2 Heat 2 Cool
Heat Pump
System
4 Heat 2 Cool
Heat Pump
System
RC
RH
C
B
O
G
W1
Y
Y2
W2
Transformer power
(cooling)
Transformer power
(heating)
Transformer common
Energized in heating
Energized in cooling
Fan relay
First stage of heat
First stage of cool
Second stage of cool
Second stage of heat
Transformer power
(cooling)
Transformer power
(heating)
Transformer common
Heat pump changeover
valve energized in heating
Fan relay
First stage of
emergency heat
First stage of heat & cool
Second stage of cool
Auxiliary heat relay,
second stage of heat
Heat pump changeover
valve energized in cooling
Transformer power
(cooling)
Transformer power
(heating)
Transformer common
Heat pump changeover
valve energized in heating
Fan relay
First stage of emergency
heat, third stage of heat
First stage of heat & cool
Second stage of cool
& second stage of heat
Auxiliary heat relay, fourth
stage of emergency heat
Heat pump changeover
valve energized in cooling
Benets To Using The PROsync Wireless System
HHumidify
D
Humidify Humidify
Dehumidify Dehumidify Dehumidify
Terminal
2 Heat 2 Cool
Conventional
System
2 Heat 2 Cool
Heat Pump
System
4 Heat 2 Cool
Heat Pump
System
Terminal Designations on the Master Thermostat
R24 VAC transformer power 24 VAC
transformer power
24 VAC
transformer power
Ctransformer common transformer common transformer common
Wiring Tips
Power supply
Factory - installed jumper. Remove only when installing on a 2 transformer systems.
Use either O or B terminals for changeover valve.
Optional 24 VAC common connection when thermostat is used in
battery power mode.
Typical 2H/2C System: 1 Transformer
RC
RH
Y
C
W/E
G
W2
Y2
COMPRESSOR
RELAY
FAN RELAY
HEAT RELAY 2
COMPRESSOR
RELAY 2
HEAT RELAY
C
R
L2
L1(HOT)
System Averaging
System Averaging will average all remotes together to provide a more accurate temperature of the entire home. Adjusting
the temperature from any remote will temporarily put that room in control of the system. If the upstairs thermostat reads
80 while the basement reads 70 the system will condition the home to a 75 ambient.
Scheduling
With scheduling the system you can make dierent rooms in control for each part of the day. For homeowners with
predictable schedules, this ensures each room will be the target temperature when scheduled to be used. Making the
kitchen in control in the morning, your home oce during the day, your living room in the evening, and your master
bedroom at night is a great hands-free approach to maximize comfort. To turn Scheduling on or o, see the
instructions for the “Program Mode” tech setting in this manual on page 22.
Occupancy Sensing (Last Seen Mode)
This is the perfect solution for homes with a single occupant with less predictable schedules, using the built-in
occupancy sensors moves the comfort around the home without the need for scheduling. As soon as someone
enters a room, it takes control of the system. To turn Last Seen Occupancy Sensing on, see the instructions for
“Occupancy Mode”tech setting in this manual on page 31.
Occupancy Sensing (System Average Mode)
This is an excellent solution for a home with multiple occupants. Each time a remote senses occupancy, it starts an
automatic, internal timer. The system is controlled using the average of the temperatures from only the remotes with
active timers. When a remote’s timer expires, the system removes that remote from the average. To turn System
Average Occupancy Sensing on, see the instructions for “Occupancy Mode” tech setting in this manual on page 31.
80
70
75
68 72
68
68
68
75
70
71
68
When using remote sensing, this system can be congured four separate ways to maximize comfort for homeowner and
cater to each of their unique lifestyles.

15 16
19 20
WiringWiring
This feature allows the installer
to change the calibration of the
room temperature display. For
example, if the thermostat reads
70˚ and you would like it to read
72˚ then select +2.
Tech Setup Steps
Room
Temperature
Calibration 0˚F
You can adjust the room
temperature display to read
up to 4˚above or below the
factory calibrated reading.
Adjustment Options Default
LCD Will Show
This thermostat has a technician setup menu for easy installer
conguration. To set up the thermostat for your particular application:
1. Press the MENU button.
2. Press and hold the technician setup button for 3 seconds. This 3
second delay is designed so that homeowners do not accidentally
access the installer settings.
3. Congure the installer options as desired using the table below.
Use the or keys to change settings and the NEXT step
or PREVIOUS step key to move from one step to another.
Note: Only press the DONE key when you want to exit the
Technician Setup options.
4. Press the DONE key to exit.
COOLSWING
Tech Setup Steps Adjustment Options Default
LCD Will Show
The swing setting often called
“cycle rate”,“dierential”or
“anticipation”is adjustable. A
smaller swing setting will cause
more frequent cycles and a larger
swing setting will cause fewer
cycles.
Cooling
Swing
The cooling swing setting
is adjustable from 0.2˚ to
2˚. For example: A swing
setting of 0.5˚ will turn the
cooling on at approximately
0.5˚ above the setpoint
and turn the cooling o at
approximately 0.5˚ below
the setpoint.
0.5˚
Note: This thermostat is
hardwire powered when the
24V transformer is
connected to the R and C
terminals of the thermostat.
Note: In many systems
with no emergency heat
relay a jumper can be
used between W1 and W2.
Typical Heat Only System With Fan
Typical Cool-Only System With Fan
FAN RELAY
HEAT RELAY
RC
RH
Y
C
W/E
G
C
R
L2
L1(HOT)
FAN RELAY
COMPRESSOR
RELAY
C
R
L2
L1(HOT)
RC
RH
Y
C
G
W/E
Typical 2H/2C System: 2 Transformer
REMOVE JUMPER
RC
RH
Y
C
W/E
G
W2
Y2
C
R
L2
L1(HOT)
C
R
L2
L1(HOT)
COMPRESSOR
RELAY
HEAT RELAY
FAN RELAY
HEAT RELAY 2
COMPRESSOR
RELAY 2
Typical 2H/1C Heat Pump System
RC
RH
Y
C
W/E
G
W2
B
COMPRESSOR
RELAY
FAN RELAY
EMERGENCY
HEAT
C
R
L2
L1(HOT)
OCOOL
CHANGEOVER
VALVE
HEAT
CHANGEOVER
VALVE
Technician SetupTechnician Setup
OFF
This feature will ash a reminder
after the elapsed run time to
remind the user to change the
lter. A setting of “OFF”will
disable this feature.
Filter Change
Reminder
You can adjust the lter
change reminder from“OFF”
to 2000 hours of fan runtime
in 50 hour increments.
This setting will select the
terminal for medium fan speed
operations. The selected terminal
cannot be used for reversing valve
operations when heat pump is
enabled.
Use the and buttons to
select O/B terminals.
0
0
M FAN
TERMINAL
PTAC Mode
This setting allows the thermostat
to operate a PTAC. This will allow
for multiple fan speeds selectable
in the next two tech settings.
Use the and buttons to
select ON/OFF. OFF
PTAC MODE
This setting allows you to choose
the number of fan speeds the
thermostat will control.
G = Low Speed Fan
B/O = Medium Speed Fan
Y2 = High Speed Fan
PTAC Fan
Speeds
(Only displayed if
PTAC mode is set
to“ON”)
2
PTAC FAN
SPEEDS
Use the and buttons to
select , 2 or 3.
1. Speeds: ON, Auto
2. Speeds: Low, High, Auto
3. Speeds: Low, Med, High,
Auto
PTAC Medium
Fan Speed
Terminal
(Only displayed if
PTAC mode is set
to“ON”and PTAC
fan speeds is set
to“3”)
When turned on the thermostat
will operate a heat pump. EM.
Heat will show as an option in the
system switch tech setting.
Use the and button to
adjust.
Heat Pump
OFF congures the
thermostat for conventional
systems.
ON congures the
thermostat for heat pump
systems.
OFF
HEAT PUMP
System Set
Use the or buttons
until the desired application
is ashing. AUTO = (Auto
Changeover) Heat
Off
Cool
SYSTEM SET
O
Heat
Cool
You can congure the system
switch for the particular
application. Heat - O - Cool,
Heat - O, Cool - O, Heat - O -
Cool – Auto.
Note: Emergency Heat is available
in heat pump mode only.
The swing setting often called
“cycle rate”,“dierential”, or
“anticipation”is adjustable. A
smaller swing setting will cause
more frequent cycles and a larger
swing setting will cause fewer
cycles.
Heating
Swing
The heating swing setting is
adjustable from 0.2˚ to 2˚.
For example: A swing setting
of 0.5˚ will turn the heating
on at approximately 0.5˚
below the setpoint and turn
the heating o at 0.5˚ above
the setpoint.
0.8˚
HEAT SWING
CALIBRATE
A Note About Auto Changeover:
In Auto you have the ability to switch between Auto Heat or Auto
Cool by pressing the system key. This can be done once the current
mode has reached its setpoint. For example: if in Auto Heat, the heat
setpoint must be satised before the thermostat will allow you to
switch to Auto Cool. You can switch out of Auto by holding down the
SYSTEM key. To get back into Auto, you must toggle the system key
to Auto.
0

22
21
26
25
Technician SetupTechnician Setup
Technician Setup
Tech Setup Steps Adjustment Options Default
LCD Will Show
Technician Setup
Tech Setup Steps Adjustment Options Default
LCD Will Show
This feature will congure the
fan to run a selected number of
cycles per hour. Note:This mode
can be enabled or disabled at
anytime during normal operation
by selecting IAQ mode with the
fan key. Turning this feature on
shows IAQ option in fan key.
Notes:
This programmable/selectable mode
will operate the fan 1-4 cycles per
hour, 1-45 minutes per cycle. Once
programmed in tech setup, to enable
this mode select“IAQ”with the fan
key. Disable this mode by selecting
“ON”or“AUTO”with the fan key.
IAQ Mode
Cycle
Select OFF, 1, 2, 3 or 4 with the
or buttons. This sets
the number of cycles per hour
that the IAQ fan mode will
operate.
O
IAQ MODE
CYCLE
O
This setting provides the option
to select a terminal for Fresh Air
damper functions. The selected
terminal cannot be used for
reversing valve operations when
the heat pump setting is turned
on.
Fresh Air
Terminal
(Only displayed if
fresh air mode is
turned ON. This
setting cannot be
used with PTAC,
three stages of
cool, or economizer
turned ON)
Use the and buttons
to select O/B.
FRESH AIR
TERM
0O
This setting selects the minimum
number of minutes that the fresh
air damper will be energized.
Fresh Air
Minutes
Use the and buttons
to select 5, 10, 15, 20, 25,
30, 35, 40, 45, 50, 55 or 60
minutes. 5
FRESH AIR
MIN
This allows you to select the
minimum number of minutes
that the fan will run per IAQ
mode cycle. The thermostat will
keep track of fan runtime from
normal heat and cool operation. If
additional fan runtime is needed,
the thermostat will run the fan to
satisfy the IAQ mode minutes.
Notes: This programmable/selectable
mode will operate the fan 1-4 cycles
per hour, 1-45 minutes per cycle. Once
programmed in tech setup, to enable
this mode select“IAQ”with the fan
key. Disable this mode by selecting
“ON”or“AUTO”with the fan key.
IAQ Minutes
Per Cycle
(Only displayed
if“IAQ Mode
Cycle”is greater
than 0)
Select 1, 5, 10, 15, 20, 30 or
45 minutes.
When IAQ fan mode is
enabled, it will ensure the
fan runs at least the selected
number of minutes per IAQ
Mode Cycle.
This step will not appear if
previous step is set to“OFF”.
IAQ MODE
MINUTE
11
This feature allows fresh air into
a unit for a selectable amount
of time.When Fresh Air Mode is
enabled, the fan and the fresh air
damper terminal will energize
simultaneously.
Use the and buttons to
select OFF, OC ON or ON.
OFF:Thermostat does not
enable Fresh Air Mode.
OC ON: Fresh Air Mode is
enabled during the OCCUPIED,
WAKE, RETURN, and SLEEP
time periods (It will not bring
in fresh air during UNOCCUPIED
and LEAVE time periods).
ON:Thermostat will enable
Fresh Air Mode for every time
periods.
OFF
FRESH AIR
MODE
Fresh Air
Mode
(This setting
cannot be used
with PTAC)
This feature will bring in outside
air for rst stage cooling opera-
tions, if the outdoor temperature
is 5 (or more) degrees lower than
the setpoint temperature. This
setting can only be enabled if the
thermostat is in cooling mode.
Free Cooling
(Only displayed if
an outdoor remote
sensor is paired
to the equipment
module)
Use the and buttons
to select ON/OFF.
OFF
FREE
COOLING
Tech Setup Steps Adjustment Options Default
LCD Will Show Tech Setup Steps Adjustment Options Default
LCD Will Show
Dual Fuel
Auxiliary For
Heat Pump
(Only displayed if
heat pump is set
to“ON”)
OFF
This setting allows the system
to run Gas, Oil, Propane or any
other types of auxiliary heat. The
thermostat will default to electric
auxiliary heat in heat pump
applications.
DUAL FUEL
Use the and buttons
to select ON/OFF.
Select GAS to have the system
control the fan during a call for
heat, select Electric to have the
thermostat control the fan during
a call for heat.
Note: If heat pump is set to“ON”this
step will not show, and will default
to ELECTRIC.
Electric or Gas
Fan Operation
Use and buttons to
change the setting.
FAN SET
GAS
This feature allows the thermostat
to keep multiple stages of heat or
cool energized until the setpoint
is satised.
Satisfy
Setpoint
Staging
(Only displayed
if there are more
than one stage of
heat or cool)
Use the or buttons
to turn on of o.
SS STAGING
This feature allows a delay to
occur if an additional stage is
needed.This allows the previous
stage extra time to satisfy the
setpoint.
Staging
Delay
(Only displayed
if there are more
than one stage of
heat or cool)
Use the or key to
select OFF, 5, 10, 15, 30, 45,
60, or 90 minutes.
This feature allows the installer
to select the minimum run
time for the compressor. For
example, a setting of 4 will force
the compressor to run for at
least 4 minutes every time the
compressor turns on, regardless of
the room temperature.
Minimum
Compressor
On Time
You can set the minimum
compressor run time to
“OFF”, “3”,“4”, or“5”minutes.
If 3, 4 or 5 is selected, the
compressor will run for at
least the selected time
before turning o. Use the
and buttons to
change the setting.
MINIMUM
COMP ON
OFF
OFF
OFF
The compressor short cycle delay
protects the compressor from
“short cycling”. This feature will
not altlow the compressor to be
turned on for 5 minutes after it
was last turned o.
Compressor
Short Cycle
Delay ON
Selecting “ON”will not allow
the compressor to be turned
on for 5 minutes after the
last time the compressor was
on. Select “OFF”to remove
this delay. Use the and
buttons to change the
setting.
Cooling Fan
Delay
The cooling fan delay setting will
delay the fan from coming on in
cool mode and keep it running
after the compressor shuts o
for a short time to save energy in
some systems.
You can set the cooling fan
delay to OFF, 10, 30, 60 or 90
seconds. If 10, 30, 60, or 90
is selected the fan will not
turn on for that many seconds
when there is a call for cool
and will run for that many
seconds after satisfying a call
for cool.
OFF
COMP DELAY
COOL FAN
DELAY
Program
Options 5d
PROGRAM
This setting allows you to select
the number of heat and cool
stages.
System
Stages 2H
2H2C Use the and buttons
to select 1H/1C, 1H/2C,
2H/1C, 2H/2C, 3H/1C, 3H/2C,
4H/2C.
Note: Heat and cool choices
are limited based on
conventional, heat pump, or
PTAC system conguration.
SET STAGES
You can congure this thermostat
to have a 7 day program, a
5+1+1 program or No program.
Note: If 7d is selected, in set schedule
you will program all seven days
individually.
If 5d is selected, in set schedule
you will program Monday – Friday
together and Saturday and Sunday
individually.
If 0d is selected the thermostat
becomes non-programmable and
the Set Schedule button goes away
in Menu.
Use the and button
to select 7d for 7 day, 5d for
5+1+1, or 0d for
non-programmable.
STAGING
DELAY

Technician Setup
23 24
27 28
Tech Setup Steps Adjustment Options Default
LCD Will Show
Technician Setup
Tech Setup Steps Adjustment Options Default
LCD Will Show
Tech Setup Steps Adjustment Options Default
LCD Will Show
Pro Recovery
(Only displayed if
Program Option is
set to“5D”or“7D”
or if Occupancy
Control is set to
“ON”)
This feature will start heating and
cooling early to bring the building
temperature to its programmed
setpoint by the beginning of the
WAKE and RETURN time periods.
Use the or key to
select on or o.
ON
PRO
RECOVERY
This setting maximizes eciency
and equipment longevity by
increasing the heating and
cooling swing settings to 2°
during the unoccupied and leave
time periods. This will result in
signicantly fewer system cycles.
OFF
CYCLE
MINIMIZER
Use the or key to
select on or o.
Cycle
Minimizer
(Only displayed if
Program Option is
set to“5D”or“7D”
or if Occupancy
Control is set to
“ON”)
This feature allows you to set a
maximum heating setpoint limit.
The setpoint temperature cannot
be raised above this value.
Heat
Setpoint
Limit
This feature allows you to set a
minimum cooling setpoint limit.
The setpoint temperature cannot
be lowered below this value.
Cool
Setpoint
Limit
Use the or key to
select the minimum cooling
setpoint.
Use the or key to
select the maximum heat
setpoint.
HEAT LIMIT
90˚F
COOL LIMIT
CO 44˚F
You can select either a 12 or 24
hour clock setting.
12 or 24
Hour Clock
Use the or key to
select 12 or 24 hour clock. 12
CLOCK SET
The display light can be
congured to stay on all the
time or turn on when any key
is pressed. There are LOW and
HIGH selections for continuous ON
selection.
Use the and buttons
to select OFF, LOW, or HIGH.
OFF congures the display
light to come on when the
light key or any button is
pressed.
LOW congures the display
light to stay on at a low
intensity constantly. When a
button is pressed, the display
light will transition to high
intensity.
HIGH congures the display
light to remain on at high
intensity all the time.
ALWAYS ON
LIGHT
HARDWIRE
ONLY
LO
Tech Setup Steps Adjustment Options Default
LCD Will Show
Balance point run time will allow
the W2 auxiliary terminal to
energize even if outdoor
temperature is above selected
balance point temperature. If
enabled, auxiliary will energize
for the current cycle after the
balance point run time has
expired.
Balance
Point Run
Time
(Only displayed
if Dual Fuel
Balance Point or
Balance Point
Electric Aux
Cut In are set
to an outdoor
temperature.)
O, 15, 30, 45, 60, 75, 90
BP RUN TIME
OFF
Balance point with electric
auxiliary will optimize heat
pump usage. When the outdoor
temperature is above the AUX CUT
OUT selection, the thermostat
to only allow theY terminal(s)
to energize and lockout theW2
terminal. When the outdoor
temperature falls below the
AUX CUT OUT selection and sits
above the AUX CUT IN selection,
the thermostat to allow theY
terminal(s) and theW2 terminal
to energize. When the outdoor
temperature is below the AUX
CUT IN selection, the thermostat
will only energize theW2
terminal and lockout theY
terminal(s).
Balance Point
Electric AUX
Cut In
(Only displayed if
an outdoor remote
sensor is paired
to the equipment
module, Heat
Pump is“ON”, and
Dual Fuel Aux is
“OF”)
Use the and buttons
to select 10, 15, 20, 25, 30,
35, 40, 45, 50 degrees.
OFF
BP AUX CUT
IN
This feature adds humidity when
the system mode is in HEAT.
Humidify
Use the and key to
turn on or o. If ON is selected
the humidity will be displayed
on the main screen and H
terminal will energize when
the humidity setpoint is above
the ambient humidity in Heat
mode.
OFF
HUMIDIFY
This feature removes humidity
when the system mode is in
COOL.
Dehumidify
Use the and key to
turn on or o. If ON is selected
the humidity will be displayed
on the main screen and D
terminal will energize when
the humidity setpoint is below
the ambient humidity in Cool
mode.
DEHUMIDIFY
OFF
Technician Setup Technician Setup
An outdoor temperature above
balance point will cause the
thermostat to energize theY
terminal(s) only in calls for heat.
An outdoor temperature below
balance point will cause the
thermostat to energize theW2
terminal only in calls for heat.
Dual Fuel
Balance
Point
(Only displayed
if an outdoor
remote sensor
is paired to the
equipment
module, Heat
Pump is“ON”,
and Dual Fuel
Aux is“ON”)
Use the and buttons
to select OFF, 10, 15, 20, 25,
30, 35, 40, 45, 50 degrees.
OFF
BALANCE
POINT
OF
Balance point with electric
auxiliary will optimize heat
pump usage. When the outdoor
temperature is above the AUX CUT
OUT selection, the thermostat
to only allow theY terminal(s)
will energize and lockout the W2
terminal. When the outdoor
temperature falls below the
AUX CUT OUT selection and sits
above the AUX CUT IN selection,
the thermostat will allow theY
terminal(s) and theW2 terminal
to energize. When the outdoor
temperature is below the AUX
CUT IN selection, the thermostat
will only energize theW2 termi-
nal and lockout theY terminal(s).
Balance Point
Electric AUX
Cut Out
(Only displayed if
an outdoor remote
sensor is paired
to the equipment
module, Heat
Pump is“ON”, and
Dual Fuel Aux is
“OF”)
Use the and buttons
to select 10, 15, 20, 25, 30,
35, 40, 45, 50 degrees.
OFF
BP AUX CUT
OUT
Keypad
Lockout
Keypad lockout allows you to
congure the thermostat so some
or all of the keys don’t function.
Note: Unlike other models, keypad
lockout is always engaged if it is
set to PARTIAL or FULL.
Use the + and - buttons to
select OFF, BASIC, PART, FULL
OF - OFF= keypad
lockout has been disabled.
BA - BASIC= locks out menu
PA - PARTIAL= partial keypad
lockout, which locks all the
keys except the or setpoint
keys.
FL - FULL= full keypad lockout,
which locks out all the keys.
OFF
KEYPAD
LOCKOUT
When
Hardwired
This setting provides the option to
select a terminal for Free Cooling
functions. The selected terminal
cannot be used for reversing valve
operations when the heat pump
setting is turned on.
Free Cooling
Terminal
(Fresh air mode and
free cooling can
be used together.
Free cooling cannot
be used with PTAC
mode, three stages
of heat.
Use the and buttons
to select O/B.
O
FREE
COOLTERM
O
This feature allows you to display
temperatures in either Fahrenheit
or Celsius.
˚F or ˚C
˚F for Fahrenheit
˚C for Celsius ˚F
F OR C SET
Display
Light
(This setting is
only applied when
the thermostat is
hardwied)

UNOCC HEAT
Occupancy
Sensitivity
Setting
(Only displayed if
Occupancy Control is
set to ON)
Set the heat temperature that you
would like the system to be while
the space is unoccupied.
High Sensitivity(3):
This is the most sensitive
setting and will detect very
slight motions.This is the
recommended setting
because it will work well for
nearly all applications,and
will detect any movement.
Medium Sensitivity(2):
This is the medium sensitive
setting.This is less likely set
o by pets.
Low Sensitivity(1):
This is the least sensitive
setting and can be used in ar-
eas of heavy trac. Pets, small
children, or people more than
20’from the sensor location
are least likely to trigger the
sensor .
2
Full temperature range
dened by setpoint limits.
First adjust the temperature
using the + and – buttons.
Unoccupied
Heat Setting
(Only displayed if
Occupancy Control is
set to ON)
70˚
Local Ambient
Enable
(Only displayed when
using remote sensors)
Technician Setup Technician Setup
30
29
34
33
Pairing
Signal
Strength
LOCAL
AMBIENT
START
PAIRING
SIGNAL
STRENGTH
ON - Maintains the Main
Thermostat as a control point
to be used in system
averaging and occupancy
control.
OF - Disables the local
ambient temperature
sensor removing the Main
Thermostat from the system
temperature.
Remove this thermostat from
“System Average”temperature
calculation.
Note:The ambient temperature
is not displayed on the main
screen of the thermostat with
“Local Ambient Enable”OF.
ON
Use this setting to pair your
thermostat to the equipment
module. Press and hold to
join the network. This setting is
only displayed when they have
been unpaired for any reason.
N/A
P
N0 - Disconnected
LO - low signal strength
HI - high signal strength
Exit
Network
Press and hold the to remove
this device from the network.
N/A
UP
Tech Setup Steps Adjustment Options Default
LCD Will Show Tech Setup Steps Adjustment Options Default
LCD Will Show
Displays the strength of the
wireless signal and network
status.
Device
Name
(Only displayed when
using remote sensors)
Press the + and - buttons to
choose the name of this device
from a selection of common room
names.
MAIN
EXIT
NETWORK
Network Info
(Only displayed when
using remote sensors) TOTAL
DEVICES
1
N/AThis setting shows information
about the devices on your network.
Press the and buttons to
check the number of total devices,
active indoor, and active outdoor
remotes.
Freeze
Protection
FREEZE
PROTECT
Freeze protection provides some
extra protection in case
communication is lost between
the thermostat (and remote
sensors) and the Equipment
module for any reason.
Note: A thermostat is not a safety
device and the building will need
additional precautions if left un
attended for long periods of time.
OF - Freeze protection defaults
to OFF.
ON - The Equipment Module
will run the heat for 10
minutes every hour in heat
mode or the cool for 20
minutes every hour in cool
mode if the communication
is lost.
OFF
HUM Terminal DHM Terminal
OPTIONS
1
2
3
4
HUM terminal energizes when the ambient
humidity is...
Below the humidity setpoint and heat or
fan is energized.
Below the humidity setpoint and heat is
energized.
Below the humidity setpoint. It will also
energize the fan during a call for humidity.
Below the humidity setpoint.
OPTIONS
1
2
3
4
DUM terminal energizes when the ambient
humidity is...
Above the humidity setpoint and cool or fan
is energized.
Above the humidity setpoint. It will also
energize the fan during a call for dehumidity.
Above the humidity setpoint.
Above the humidity setpoint and the
compressor is not running.
Note: When the dehumidify terminal is congured as normally-closed,
the base module D terminal LED indicator will be lit when the relay is
closed. When the thermostat calls for dehumidication, the D terminal
LED indicator will turn o.
Tech Setup Steps Adjustment Options Default
LCD Will Show
Options for how the HUM
terminal energizes.
See chart below
HUM
Terminal
(Only displayed if
humidify is set to
“ON”)
Use the left and right arrows to
select one of the four options.
View the HUM terminal chart
below for an explanation of
these options. 1
HUM
TERMINAL
1
Options for how the DHM
terminal energizes.
See chart below
Use the left and right arrows
to select one of the four
options.
View the DHM terminal chart
below for an explanation of
these options.
1
1
DHM
Terminal
(Only displayed if
dehumidify is
set to“ON”) DHM
TERMINAL
You can congure the D terminal
as Normally-Open or
Normally-Closed.
NO = Normally Open
NC = Normally Closed
Dehumidify
Relay
(Only displayed if
Dehumidify is set
to“ON”)
Use the or key to select NO
or NC. If NO is selected D will
energize to dehumidify.
If NC is selected D will be
normally energized. D will
de-energize to dehumidify.
DHM RELAY
O/C
NO
Tech Setup Steps Adjustment Options Default
LCD Will Show
This feature forces the A/C to run
longer to remove humidity when
needed.The A/C will“over cool”
the room a few degrees until
humidity reaches the desired
setpoint.The numbers below
are the maximum number of
degrees the thermostat will
overcool to satisfy humidity. For
example, If temperature set point
is 70 and humidity set point is
50 and swing is 1 degree and
“Dehumidify with AC”is set to
3 and the ambient is 68 and
indoor humidity is 60 … the
thermostat will continue to run
air conditioning until 67 degree
to try to satisfy the humidity set
point of 50
Dehumidify
With AC
(Only shows if
dehumidify is
displayed to
“ON”)
DEHUMIDIFY
AC
0FF
Use the and buttons
to select On or O.
This feature allows the installer
to change the calibration of the
ambient humidity displayed.
Humidity
Calibration
(Only displayed
if Humidify or
Dehumidify is set
to“ON”)
Use the left and right arrows
to adjust the calibration +/-3.
Each one unit of adjustment
amounts to approximately 5%.
O
HUMIDITY CAL
O
The amount of over cooling
allowed when using A/C to
remove humidity. This screen is
only shown when ON is selected
in the Dehumidify with AC tech
setup step.
Over Cool
Limit
(Only displayed if
Dehumidify with
AC is set to“ON”)
Use the and left and right
arrows to select the
maximum number of
degrees of over cool.
Options are: 2,3,4,5
3
OVER COOL
LIMIT
This feature will adjust the
indoor humidity as the outdoor
temperature changes. When OFF
is selected, the humidity setpoint
is controlled by the user.
When ON is selected,
the humidity setpoint will
uctuate. When ON is selected,
the indoor humidity will uctuate
based on outdoor temperature.
Use the and buttons
to select OFF, ON 1 or ON 2.
When ON 1 or ON 2 is
selected and humidity level
is adjusted, the thermostat
will revert to the original
humidity level after four
hours. See Automatic
Humidity Adjusting chart for
humidity ranges.
Please see page 32 for chart.
OFF
Automatic
Humidity
Adjusting
(Only displayed if
an outdoor remote
sensor is paired
to the equipment
module and
Humidity is set to
“ON”)
AUTO
HUMIDITY
Set the level of sensitivity of
the occupancy sensor. Lowering
the sensitivity will cause the
sensor to respond only to larger
movements.

3635
Tech Setup Steps Adjustment Options Default
LCD Will Show Tech Setup Steps Adjustment Options Default
LCD Will Show
Duration of
Occupancy
(Only displayed if
Occupancy Control is
set to“ON”)
Set the heating temperature that
you would like the system to be
while the space is occupied.
Full temperature range dened
by setpoint limits.
Adjust the temperature using
the + and – buttons.
Set the cooling temperature that
you would like the system to be
while the space is occupied.
When the occupancy sensor is
turned on you have the ability
to set how long the thermostat
will go into occupancy mode
everytime a person is sensed.
30 = 30 minutes, 1 = 1 hour,
2 = 2 hours, 3 = 3 hours, 4
= 4 hours, 5 = 5 hours, 6 =
6 hours, 7 = 7 hours, 8 =8
hours, 9 = 9 hours, 10 = 10
hours, 11 = 11 hours, and 12
= 12 hours.
8
Full temperature range
dened by setpoint limits.
Adjust the temperature using
the + and – buttons.
Set the cool temperature that you
would like the system to be while
the space is unoccupied.
Full temperature range dened
by setpoint limits.
Adjust the temperature using
the + and – buttons.
Occupied
Cool Setting
(Only displayed if
Occupancy Control is
set to“ON”)
75˚
Occupied
Heat Setting
(Only displayed if
Occupancy Control is
set to“ON”)
70˚
Unoccupied
Cool Setting
(Only displayed if
Occupancy Control is
set to“ON”)
75˚
OCC
DURATION
CO
OCC COOL
OCC HEAT
UNOCC COOL
Tech Setup Steps Adjustment Options Default
LCD Will Show
Setting The Humidity
Setting The Humidity
Follow the steps below to change your
target humidity setpoint.
Press the humidity button.
Use the or button to
select the target humidity
setpoint. Press Done when
completed.
Humidity Key
Target humidity setpoint keys
Note:
Humidity is only energized during
heat. Dehumidity is only energized
during cool. HUMIDITY and
DEHUMIDITY each have their own
target setpoints.
Ambient Humidity Display
Ambient humidity will ash opposite the day and time, if the optional
outdoor temperature sensor is installed the ambient outdoor temperature
will also cycle in the display.
Ambient Humidity Day & Time Outdoor Temperature
Increasing Humidity
The table on the right shows
recommended indoor humidity
levels in relation to outdoor
temperatures during heating
(adding humidity).
Outside
Temperature (0°)
Recommended
Relative Humidity
+20° and above
+10°
0°
-10°
-20°
35% to 40%
30%
25%
20%
15%
Consult your professional HVAC
technician for recommended
settings for your climate.
Technician Setup
Technician Setup
32
31
Two methods are available for
using occupancy sensing to run
the HVAC system providing
exibility to the homeowner
based on their family and
lifestyle.
In both methods, once the
Duration of Occupancy has
expired for all remotes, the
system will enter the
Unoccupied Mode.
NOTE: Enabling
either type of occupancy
control will enable the occupancy
sensor on all remote sensors as
well (if applicable).When no
remote sensors are connected,
available options are“OFF”and
“ON”(System Average).
OF=OFF
The occupancy sensor is o
and the thermsotat
defaults to a traditonal
programmable or
nonprogrammable
thermostat.
LS = Last Seen
This option only allows one
sensor to be in control at
a time. Any time a person
enters a new room, the entire
system will prioritize that
remote’s settings to condition
the entire home until another
remote takes control or
the Duration of Occupancy
expires, entering Unoccupied
Mode.This is a great solution
for a household with a single
occupant.
SA = System Average
This option allows multiple
sensors to be in control at
a time. If multiple remotes
sense occupancy
simultaneously, the system
will average all remotes
currently in Occupied Mode
together. Each remote will
drop o individually as
its Duration of Occupancy
expires. This is a great option
for a household with
multiple occupants.
OFF
OCCUPANCY
Occupancy
Mode
Humidity %
Enables a reminder for the user to
change the humidity pad.
Humidity
Pad
Reminder
Use the or key to
select OFF, 500, 1000, 1500,
or 2000. These represent
hours of heat operation.
Enables a reminder for the user to
change the UV light bulb.
UV Lamp
Reminder
Use the or key to
select OFF, 1 YR, 2YR
OFF
UV LAMP 0
OFF
HUM PAD 0
Enables a reminder for the user
to change the IAQ Cell after
25,000 hrs.
IAQ Cell
Reminder
Use the or buttons to
select OFF, or 25 (stands for
25,000 hours).
IAQ CELL 0
OFF
OFF
OFF
OFF
FWVersion
This displays the current rmware
version installed on the Main
Thermostat. This can be helpful
for troubleshooting if you ever
need to call customer service.
N/A
T755WHO-001
Automatic Humidity Adjusting Index
When The Outdoor Temperature Is: On 2
> +40˚F
+30˚F to 40˚F
+20˚F to 29˚F
50%
On 1
45%
+10˚F to 19˚F
0˚F to 9˚F
-1˚F to -10˚F
-11˚F to -20˚F
<-20
45%40%
40%35%
35%30%
30%25%
25%20%
20%15%
15%10%
Technician Setup
CO
Force Unoccupied Setting
To set your system to the unoccupied temperature immediately, press
and hold the Light and Minus buttons on any indoor sensor or the main
thermostat. Your thermostat or sensor should say “Unoccupied”. The
system will ignore occupancy changes for 5 minutes to allow you time to
leave.

41 42
Programming
Temporary Hold: The thermostat will display HOLD and
Run Schedule on the bottom of the screen when you press the
or key. If you do nothing, the temperature will remain at this
setpoint temporarily for 4 hours. The program setpoint will then
replace the temporary setpoint.
Permanent Hold: With a temporary hold set, If you press the HOLD
key at the bottom of your screen, you will see HOLD appear next to
the setpoint temperature in the display. The thermostat will now
permanently stay at this setpoint and can be adjusted using the
or keys.
To Return To Program: Press the Run Schedule key at the bottom of
the screen to exit temporary and permanent holds.
Temporary & Permanent Hold Feature
Filter Change Reminder
If your installing contractor has congured the thermostat to remind
you when the air lter needs changed, you will see CHANGE FILTER
in the display when your air lter needs changed. The reminder will
be shown in the display after your system has run long enough to
require an air lter change.
To reset the timers for Prosync, user must hold the “Run Schedule”
button (2nd button down on the left) on either the main screen, or
the related timer tech settings.
Set Program Schedule For Four Time Periods
Programming Programming
37 38
1. Repeat steps 4 through 6 for the Sunday WAKE time period, LEAVE
time period, RETURN time period, and for the Sunday SLEEP time
period.
Sunday:
Programming
Programming
1. Repeat steps 4 through 6 for the Saturday WAKE time period,
LEAVE time period, RETURN time period, and for the Saturday
SLEEP time period.
Saturday:
Default Programming
Factory Default Program
Day of
the Week Events Time Setpoint
Temperature
(HEAT)
Setpoint
Temperature
(COOL)
Weekday
Saturday
Sunday
Wake
Leave
Return
Sleep
Wake
Leave
Return
Sleep
Wake
Leave
Return
Sleep
6 AM
8 AM
6 PM
10 PM
6 AM
8 AM
6 PM
10 PM
6 AM
8 AM
6 PM
10 PM
70˚F (21˚C)
62˚F (17˚C)
70˚F (21˚C)
62˚F (17˚C)
70˚F (21˚C)
62˚F (17˚C)
70˚F (21˚C)
62˚F (17˚C)
70˚F (21˚C)
62˚F (17˚C)
70˚F (21˚C)
62˚F (17˚C)
78˚F (26˚C)
85˚F (29˚C)
78˚F (26˚C)
82˚F (28˚C)
78˚F (26˚C)
85˚F (29˚C)
78˚F (26˚C)
82˚F (28˚C)
78˚F (26˚C)
85˚F (29˚C)
78˚F (26˚C)
82˚F (28˚C)
Set Time
Follow the steps below to set the day of the week and current time:
1. Press the Menu button.
2. Press Set Time.
3. Day of the week is ashing. Use the or key to
select the current day of the week.
4. Press Next.
5. The current hour is ashing. Use the or key to
select the current hour. When using 12-hour time, make sure
the correct a.m. or p.m. choice is selected.
6. Press Next.
7. Minutes are now ashing. Use the or key to
select current minutes.
8. Press Done when completed.
(If using programming)
All our programmable thermostats are shipped with an energy saving default
program. You can customize this default program by following the
instructions in the set program schedule section starting on page 38.
Programming
Your thermostat can be programmed to have each day of the week
programmed uniquely (7 days), all the weekdays the same with a separate
program for Saturday and a separate program for Sunday (5+1+1), or
non-programmable.
A Note About Programmable Fan:
The programmable fan feature will run the fan continuously during any
time period it is programmed to be on. This is the best way to keep the
air circulated and to eliminate hot and cold spots in your building.
Programming

Specications
The display range of temperature ... 41˚F to 95˚F (5˚C to 35˚C)
The control range of temperature.... 44˚F to 90˚F (7˚C to 32˚C)
Load Rating............................................... 1 amp per terminal, 1.5 amp
maximum all terminals combined
Swing (cycle rate or dierential) ...... Heating is adjustable from 0.2˚ to 2.0˚
Cooling is adjustable from 0.2˚ to 2.0˚
Power source ...........................................18 to 30 VAC, NEC Class II, 50/60 Hz
for hardwire
Battery power from 2 AA Alkaline
batteries
Operating ambient ............................... 32˚F to +105˚F (0˚C to +41˚C)
Operating humidity .............................. 90% non-condensing maximum
Dimensions of thermostat ................. 4.7”W x 4.3” H x 1.1” D
Frequency ................................................ 916 MHz
Base module
Load rating ............................................... 1 amp per terminal, 1.5 amp
maximum all terminals combined
Power source ........................................... 18 to 30 VAC, NEC class II, 50/60 Hz
43 44
This device complies with part 15 of the FCC Rules. Operation is subject to
the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
Any changes or modications not expressly approved by the party
responsible for compliance could void the user’s authority to operate this
equipment.
Note: This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not
occur in a installation. If this equipment does cause harmful interference
to radio or television reception, which can be determined by turning the
equipment o and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
· Reorient or relocate the receiving antenna.
· Increase the separation between the equipment and receiver.
· Connect the equipment into an outlet on a circuit dierent from that to
which the receiver is connected.
· Consult the dealer or an experienced radio/TV technician for help.
FCC RF Exposure Statement
The device shall be used in such a manner that the potential for human
contact normal operation is minimized. This equipment complies with FCC
radiation exposure limits set forth for an uncontrolled environment. This
equipment should be installed and operated with a minimum distance of
20cm between the radiator and your body. This device and its antenna(s)
must not be co-located or operating in conjunction with any other antenna
or transmitter.
4039
Programming Programming
Set Program Schedule For Four Time Periods
1. Select HEAT or COOL with the System Key.
Note: You have to program heat and cool each separately.
2. Press the MENU button (If menu does not appear rst, press
RUN SCHED).
3. Press SET SCHEDULE. Note: Monday-Friday is displayed, and the
WAKE icon is shown. You are now programming the WAKE time
period for the weekday setting.
4. Time is ashing. Use the or key to make your time
selection for the weekday WAKE time period.
Note: If you want the fan to run continuously during this time period,
select ON with the FAN key. AUTO will cycle the fan when there is a
call for heat or cool. IAQ will cycle the fan intermittently based on the
IAQ tech settings.
5. Press Next.
6. The setpoint temperature is ashing. Use the or key to
make your setpoint selection for the weekday WAKE period.
7. At any point use the ZONE button to select the remote you want to
be in control for that time period. If you want the system to average
all remotes, select System Average.
Note: This setting only applies if you are using multiple remote sensors.
8. Press Next.
9. Repeat steps 4 through 8 for the weekday LEAVE time period, for
the weekday RETURN time period, and for the weekday SLEEP time
period.
To customize your 5+1+1 Program schedule, follow these steps:
Weekday:
(WAKE, LEAVE, RETURN, SLEEP)
Specications
If you intend to use additional Remote Sensors in addition to the
Main Thermostat you must install, link and name all of the remotes in
the system before you begin the scheduling process.
Custom Programming (Fill out before starting the process)
Custom Program
Day of
the Week Events Time Setpoint
Temperature
(HEAT)
Setpoint
Temperature
(COOL)
Weekday
Saturday
Sunday
Wake
Leave
Return
Sleep
Wake
Leave
Return
Sleep
Wake
Leave
Return
Sleep
Specications
Table of contents
Other EWC Controls Thermostat manuals

EWC Controls
EWC Controls EWT-3611 Service manual

EWC Controls
EWC Controls EWT-3707 Service manual

EWC Controls
EWC Controls EWT-3900 Ultra-Zone User manual

EWC Controls
EWC Controls EWT-3102 User manual

EWC Controls
EWC Controls EWT-3900 Ultra-Zone Service manual

EWC Controls
EWC Controls EWT-601-2 User manual

EWC Controls
EWC Controls EWT-955WH User manual

EWC Controls
EWC Controls EWT-955WH User manual

EWC Controls
EWC Controls EWT-725 User manual

EWC Controls
EWC Controls Ultra-Zone IZT-100 User manual