Exhausto MCCW User manual

EXHAUSTO A/S
Odensevej 76
DK-5550 Langeskov
Tel. +45 65 66 12 34
Fax +45 65 66 11 10
exhausto@exhausto.dk
www.exhausto.dk
3006026-2018-11-22.fm Product Instruction
Cooling control with water coil
Styring af køling med vandflade
Kühlregelung mit Wasserregister
Styring av kjøling med vannbatteri
Styrning av kylning med vattenbatteri
Regeling van koeling met waterelement
Vesipatterilla jäähdyttämisen ohjaaminen
MCCW Module

3006026-2018-11-22.fm
2/88
1. GB - Product instruction
1.1 Description of MCCW (Modbus Coil Cold Water) ...........................................................................4
2. Fitting and connection
2.1 Positioning and fitting of the MCCW module ..................................................................................6
2.2 Positioning the temperature sensor (TE-SUPPLY).........................................................................6
2.3 Correct fitting of feed water temperature sensor ...........................................................................7
2.4 Cooling coil ........................................................................................................................................8
3. Electrical installation
3.1 Connection diagrams ......................................................................................................................10
3.2 Connection of Modbus devices......................................................................................................12
4. Commissioning
4.1 Commissioning ................................................................................................................................ 14
5. Troubleshooting
5.1 HMI panel error messages ..............................................................................................................15
1. DK - Produktvejledning
1.1 Beskrivelse af MCCW (Modbus Coil Cold Water) .........................................................................16
2. Montage og tilslutning
2.1 Placering og montage af MCCW-modulet .....................................................................................18
2.2 Placering af temperaturføler (TE-SUPPLY) ...................................................................................18
2.3 Korrekt montage af fremløbstemperaturføler ...............................................................................19
2.4 Køleflade...........................................................................................................................................20
3. El-installation
3.1 Tilslutningsdiagram for spændingsforsyning og styreboks .......................................................22
3.2 Tilslutning af modbus-enheder ......................................................................................................24
4. Idriftsættelse
4.1 Idriftsættelse ....................................................................................................................................26
5. Fejlsøgning
5.1 Fejlmeddelelser i HMI-panel............................................................................................................27
1. DE - Betriebsanleitung
1.1 Beschreibung von MCCW (Modbus Coil Cold Water) ..................................................................28
2. Montage und Anschluss
2.1 Anordnung und Montage des MCCW-Moduls...............................................................................30
2.2 Anordnung des Temperaturfühlers (TE-SUPPLY) ........................................................................30
2.3 Korrekte Montage des Temperaturfühlers für Vorlaufwasser .....................................................31
2.4 Kühlregister......................................................................................................................................32
3. El-Installation
3.1 Anschlussdiagramm für Spannungsversorgung und Steuergerät .............................................34
3.2 Anschluss von Modbus-Einheiten: ................................................................................................36
4. Inbetriebnahme
4.1 Inbetriebnahme ................................................................................................................................38
5. Fehlersuche
5.1 Fehlermeldungen im HMI-Panel .....................................................................................................39
1. NO - Produktveiledning
1.1 Beskrivelse av MCCW (Modbus Coil Cold Water) ........................................................................40
2. Montering og tilkobling
2.1 Plassering og montering av MCCW-modulen ...............................................................................42
2.2 Plassering av temperaturføler (TE-SUPPLY).................................................................................42
2.3 Korrekt montering av turvannstemperaturføler............................................................................43
2.4 Kjølebatteri .......................................................................................................................................44
3. Elektrisk installasjon
3.1 Koblingsskjema for matespenning og styreboks.........................................................................46
3.2 Tilkobling av Modbus-enheter ........................................................................................................48
4. Idriftsettelse
4.1 Idriftsettelse......................................................................................................................................50
5. Feilsøking
5.1 Feilmeldinger i HMI-panelet ............................................................................................................51

3006026-2018-11-22.fm
3/88
1. SE - Handbok
1.1 Beskrivning av MCCW (Modbus Coil Cold Water)........................................................................52
2. Montering og anslutning
2.1 Placering och montering av MCCW-modulen ...............................................................................54
2.2 Placering av temperaturgivare (TE-SUPPLY)................................................................................54
2.3 Korrekt montering av tilloppsvattentemperaturgivare.................................................................55
2.4 Kylbatteri ..........................................................................................................................................56
3. Installation
3.1 Kopplingsschema för spänningsförsörjning och styrbox...........................................................58
3.2 Anslutning av modbus-enheter:.....................................................................................................60
4. Driftsättning
4.1 Driftsättning......................................................................................................................................62
5. Felsökning
5.1 Felmeddelanden i manöverpanelen ...............................................................................................63
1. NL - Handleiding
1.1 Beschrijving van de MCCW (Modbus Coil Cold Water)................................................................64
2. Montage en aansluiting
2.1 Plaatsing en montage van de MCCW module ...............................................................................66
2.2 Plaatsing van temperatuursensor (TE-SUPPLY) ..........................................................................66
2.3 Korrekt montage af fremløbstemperaturføler ...............................................................................67
2.4 Koelelement......................................................................................................................................68
3. Elektrische installatie
3.1 Ansluitschema voor voedingsspanning en aansluitkast.............................................................70
3.2 De modbus units aansluiten ...........................................................................................................72
4. Inbedrijfstelling
4.1 Inbedrijfstelling ................................................................................................................................74
5. Fouten opsporen
5.1 Foutmeldingen in het HMI paneel...................................................................................................75
1. FI - Tuote-esite
1.1 MCCW:n kuvaus (Modbus Coil Cold Water)..................................................................................76
2. Montage og tilslutning
2.1 MCCW-moduulin sijoitus ja asennus.............................................................................................78
2.2 Placering af temperaturføler (TE-SUPPLY) ...................................................................................78
2.3 Korrekt montage af fremløbstemperaturføler ...............................................................................79
2.4 Jäähdytyspatteri ..............................................................................................................................80
3. Asennus
3.1 Syöttöjännitteen ja ohjausrasian kytkentäkaavio.........................................................................82
3.2 Modbus-yksiköiden kytkentä..........................................................................................................84
4. Käyttöönotto
4.1 Käyttöönotto.....................................................................................................................................86
5. Vianetsintä
5.1 HMI-paneelin vikailmoitukset..........................................................................................................87

3006026-2018-11-22.fm
4/88
1.GB - Product instruction
Functional
description
The MCCW module is able to control a water coil used for cooling. Together with the
EXact2 control system, the module is able to regulate the output from the water coil. If
necessary, a circulation pump can be started up.
NB The module is supplied as an MCOCW module.
It must be converted to an MCCW module by changing the following:
• Adding a jumper (supplied) to the module.
• Removing TE-RPT and TE-RPT-X sensors from the module.
See diagram in the section "Electrical installation" for further information.
The MCCW module can be used together with the following VEX/CX types:
• VEX100
• VEX200
• VEX320-370
• CX340-350
• VEX310T-VEX350T
Simplified
diagram
The MCCW module controls a 3-way motor valve connected to a water supply.
The water supply provides cold water.
.
Mixing loop Constant flow in the primary circuit (Supply) and in secondary circuit (Coil Cold Water)
1.1 Description of MCCW (Modbus Coil Cold Water)

3006026-2018-11-22.fm
5/88
Explanation of
simplified diagram
*) not EXHAUSTO delivery
Term Description input/output
TE-SUPPLY Measures air temperature after cooling coil. Temperature input
Capacity 0-10V Analogue outputs 0–10 V for setting of
0–100% cooling.
The MCCW module, via a temperature
regulator in EXact, sends an adjustable
0–10 V signal to the regulation valve (MVM).
Thus the setpoint for the supply air
temperature or room temperature is
maintained.
Analogue output
CP* Circulation pump 1x230V
MVM 3-way motor valve
Pump ON/OFF 230V supply to circulation pump Analogue output
TE-SPT Temperature sensor measures the feed
temperature to the cooling coil.
Temperature input
Coil Cold Water
(CCW)
Water coil (cooling)
Line regulating valve*
When there is no cooling requirement, valve adjustment must be
based on the required primary circuit water flow.
Shut off valve*

3006026-2018-11-22.fm
6/88
2.Assembly and connection
Fitting the MCCW
module
The temperature
sensor is
positioned here
2.1 Positioning and fitting of the MCCW module
Step Action
1 Fit the module using the screw holes in each corner of the module's
mounting box
2 Position the module in the vicinity of:
- regulation valve and pipes
3 Position the temperature sensor in the supply air duct as shown below
(Example from VEX200).
2.2 Position of temperature sensor (TE-SUPPLY)
P
5'
7(6833/<

3006026-2018-11-22.fm
7/88
How to mount the temperature sensor correctly on the feed water pipe to the water coil:
2.3 Correct fitting of feed water temperature sensor
Step Action
1 Use heat paste to ensure good
contact between the pipe and the
sensor. Use strips to secure the
sensor in position.
2 Ensure there is sufficient
insulation around the sensor.

3006026-2018-11-22.fm
8/88
2.4.1 Connection of cooling coil
The dimensioning of valves, pipes, etc. and cooling coil connection must always be
carried out by authorised fitters in accordance with applicable regulations and
legislation.
Mixing loop See the simplified diagram.
Connecting an
insulated CCW
With an insulated CCW, the connection must be made with stopcocks and unions, in
order to allow easy release, extraction and cleaning of the coil.
NB
Do not connect the water coil like this!.
Connection without circulation pump risks frost damage!
Bleeding Following connection of water supply to the unit:
• Bleed the system thoroughly usin the upper bleed screw on the water coil.
Insufficient
bleeding Insufficient bleeding can result in still water forming in the system,
which may result in frost-induced leaks during the winter.
Fitting motor valve
The valve must not be fitted with the motor facing down.
Insulate supply
pipe and water coil The pipes and water coil must be insulated according to applicable
regulations.
Frost protection
The cooling coil can be protected against frost by mixing 25% ethylene
glycol. This provides frost protection down to -13°C.
2.4 Cooling coil
RD12900-03

3006026-2018-11-22.fm
9/88
2.4.2 MVM valve
Shielding Shield the valve motor from direct sunlight. Due to heat emission, the valve motor must
not be encapsulated (max. ambient temperature: 50°C).
Insulating the valveTo ensure normal operation at ambient temperatures below 0°C, it is very important that
the valve section is insulated according to current standards/procedures.
MVM-OD, valve for
outdoor fitting
IIf MVM-OD used, then shielding is part of the delivery - if the valve has a K vs value
below 6.3.
Regulating
properties
Optimal regulation is achieved when the differential pressure is between 5–20 kPa.
If the differential pressure is higher than 20 kPa, the installation of a pressure difference
regulator is recommended.
2.4.3 Cold water supply
The cold water supply must be constant.
2.4.4 Operation of circulating pump
The circulation pump is operated by the EXact control system, as described below:
1. When no cooling is required, the MVM valve operates at 0%.
2. The circulation pump runs for another 5 minutes and then stops.
3. EXact starts the 24-hour timer.
4. When the 24 hours have passed, the circulation pump runs for 5 minutes.
5. The exercise cycle is repeated once a day until a cooling requirement
occurs.

3006026-2018-11-22.fm
10/88
3.Electrical installation
Diagram The following diagram shows the connection of supply voltage (1 x 230 V) and the
cooling coil control box (MCCW).
3.1 Connection diagrams

3006026-2018-11-22.fm
11/88
Key to diagram
NB
Power Supply
Term Description Supplied by...
-A1 Voltage supply/modbus terminal in VEX EXHAUSTO
-A2 MCCW module EXHAUSTO
-F1 Distribution board fuse Costumer25
-T2 TE-SUPPLY Supply air temperature sensor EXHAUSTO
-T4 Temperature sensor, supply EXHAUSTO
-M1 MVM Motor valve EXHAUSTO
CP Cirkulation pump Costumer
-Q1 Distribution board group switch Costumer
-Q2 Isolation switch (disconnects all poles) Costumer
* Not supplied by EXHAUSTO Costumer
CN12
Terminals 1 and 3
It is possible to invert the control signal to MVM,
i.e. 0V→10V becomes 10V→0V. This is done by
fitting a jumper across terminals 1 and 3 of
CN12. The change will be registered the next
time the unit is powered up.
EXHAUSTO
**24VDC Strip connector for continuation of 24VDC EXHAUSTO
Term Description
CN5 The TE-RPT sensor between terminals 5 and 6 must be removed.
CN6 The jumper between terminals 4 and 6 must be added to change
from MCOCW to MCCW.
The TE-RPT-X sensor between terminals 2 and 3 must be
removed.
VEX size Maximum load of terminal in main board
VEX140 1,4A
VEX150-170 2A
VEX240 1,4A
VEX250-260-270-280 2A
VEX340-350-360 2A
VEX320C-330C-330H must be separately powered
VEX310T-350T 2A

3006026-2018-11-22.fm
12/88
Diagram Connection must be carried out according to the following diagram. Refer to the
Electrical Installation Guide for the relevant VEX. (supplied with the VEX unit) for further
details of how to connect standard components to the connection box.
3.2.1 Cable (type, max. length and termination)
Cable EXHAUSTO recommends the use of 4-core, twisted pair, shielded cable. To limit
voltage drop across the cable, 0.25 diameter conductor is recommended. For
correct connection of shielded cable to Modbus units, refer to the Electrical
Installation Guide for the relevant VEX.
Max. cable length The overall cable length of a complete installation may not exceed 200 m.
3.2 Connection of Modbus devices
MHCW/MHCE Module for controlling heating coil (water or electric)
MXCU/MCCW Module for control of coil with cold water supply.
MPT DUCT Pressure measurement in duct
XXXXX Can be different modules, e.g. MIO module or additional MPTDUCT
HMI Control panel
*Not supplied by EXHAUSTO

3006026-2018-11-22.fm
13/88
Modbus,
termination or
daisy chaining
The first and last devices on the bus must be terminated. The PCB contains a jumper
JP1, which can be used for termination.
If Then See diagram no.
MCCW is the first or last device on
the bus
it must be terminated by use of jumper
JP1 (jumper nearest terminal 1 on
CN7).
1
MCCW is not the first and last
device on the bus
it must be daisy-chained to the next
device = default setting
2
1.
2.

3006026-2018-11-22.fm
14/88
4.Commissioning
HMI panel Refer to the VEX unit HMI panel for menu items displayed during commissioning of the
MCCW module.
See the following section for further information about the individual menu items or in
the Exact Control System Basic Instructions for the relevant VEX.
4.1.1 Detection of MCCW
Menu 3.4
Accessories
• Select CCW under cooling unit in menu 3.4.
NB Cold recovery must be active when operating with MCCW (menu 3.1.6)
4.1.2 Operating readings, MCCW
Menu 2.4 Temp.
reg. units
The menu will show, e.g.,
• output of cooling unit (A) and whether cooling is active = value > 0%
4.1 Commissioning
Ice-detect. >
De-icing method >
Heating coil >
Cooling unit >
Filter detect. >
PIR >
TS >
CO2 >
RH >
3.4 Accessories
Pressure
0
IHCW
CCW
Press.
None
None
CO2B
None
Dining solution > No
3 Settings
Unit >
General >
Configuration >
Accessories >
BMS >
Web server >
Backup/restore >
2 Operating readings
Air temperature >
Airflows >
MC parameters >
Temp. reg. units >
Pressure >
Heating coil >
CH cooling unit
CCW
CU cooling unit
MXCU
MXHP
Timers >
CO2/RH sensors >
2.4 Temp. reg. units
Heat recovery
Heating coil
Heat pump unit
Cooling unit
Cooling recovery
0.0
0.0
0.0
0.0
0.0
%
%
%
%
%
A

3006026-2018-11-22.fm
15/88
Menu 2.8 Cooling
coil (CCW)
The menu shows:
• Supply temperature for CCW cooling coil
• Pump - if the circulation pump in the heating cycle is in operation
4.1.3 Forced start, MCCW (CCW)
Conditions for use To use the forced start menu, the unit must be set to OFF in the user menu (Ventilation).
Menu 8.3.3
Cooling unit
If there are no current errors for the cooling coil("Error on unit" shown as "No"),
forced start may be activated:
• Set output for CCW. The pump starts up at an output greater than 0%.
NB When Menu 8.3 "Forced start" is exited, forced start is reset and normal operation can
be resumed. When a submenu is exited, the values in the submenu are reset.
5.Troubleshooting
NB An error will be displayed on the HMI panel in the event of a fault or irregular operation.
To resolve the problem, refer to EXact Basic instructions for the relevant VEX.
2 Operating readings
Air temperature >
Airflows >
MC parameters >
Temp. reg. units >
Pressure >
Heating coil >
CH cooling unit
CCW >
CU cooling unit
MXCU
MXHP
Timers >
CO2/RH sensors >
2.8 CCW
Supply
Pump
25.0
Off
°C
8.3.3 Cooling unit
CCW
Error on unit
0%
No
8 Service
Filter >
VDI 6022 >
Forced start >
Calibration of MPT >
Light > Off
8.3 Forced start
Fans >
Heating coil >
Cooling unit >
Dampers and relays >
EXEB relays >
5.1 HMI panel error messages

3006026-2018-11-22.fm
16/88
1.DK - Produktvejledning
Funktions-
beskrivelse
MCCW-modulet kan styre en vandflade, som kan bruges til at køle. Sammen med
EXact2 styringen kan modulet regulere ydelsen på vandfladen. En cirkulationspumpe
kan startes ved behov.
Bemærk Modulet er leveret som MCOCW-modul. Det skal ombygges til et MCCW modul ved at
ændre følgende:
• Tilføje en lus (medleveret) i modulet.
• Fjerne TE-RPT og TE-RPT-X følere i modulet.
Se diagram i afsnittet “El-installation” for yderligere information.
MCCW-modulet kan benyttes sammen med følgende VEX/CX-typer:
• VEX100
• VEX200
• VEX320-370
• CX340-350
• VEX310T-VEX350T
Principskitse MCCW-modulet styrer en 3-vejs motorventil, som er tilsluttet en vandforsyning.
Vandforsyningen leverer koldt vand.
.
Blandesløjfe Der er konstant flow i primærkreds (forsyning) og i sekundærkreds (Coil Cold Water).
1.1 Beskrivelse af MCCW (Modbus Coil Cold Water)

3006026-2018-11-22.fm
17/88
Forklaring til
principskitse
*) ikke EXHAUSTO leverance.
Betegnelse Forklaring input/output
TE-SUPPLY Måler lufttemperatur efter kølefladen. Temperatur input
Capacity 0-10V Analog udgang 0-10V, for indstilling af
0-100% køl.
MCCW-modulet afgiver via temperatur-
regulator i EXact, et indstilleligt 0-10V signal
til regulerings-ventilen. (MVM)
Således kan setpunktet for tilluft- eller
rumtemperatur holdes.
Analog output
CP* Cirkulationspumpe 1x230V
MVM 3-vejs motorventil
Pump ON/OFF 230V forsyning til cirkulationspumpe Analog output
TE-SPT Temperaturføler måler
fremløbstemperaturen til kølefladen.
Temp. input
Coil Cold Water
(CCW)
Vandflade (køling)
Strengreguleringsventil*
Ventilen skal indstilles på basis af den vandmængde som ønskes
i primærkredsen, når der ikke er kølebehov.
Kontraventil*

3006026-2018-11-22.fm
18/88
2.Montage og tilslutning
Sådan fastgøres
MCCW-modulet
Her placeres
temperaturføleren
TE-SUPPLY
2.1 Placering og montage af MCCW-modulet
Trin Handling
1 Fastgør modulet ved hjælp af skruehullerne i hjørnerne af modulets
montageboks.
2 Placer modulet i nærheden af:
- reguleringsventil og rørføring
3 Placer temperaturføleren i tilluftkanalen som anvist herunder.
(Eksempel fra VEX200 er vist)
2.2 Placering af temperaturføler (TE-SUPPLY)
P
5'
7(6833/<

3006026-2018-11-22.fm
19/88
Sådan monteres temperaturføleren korrekt på fremløbsrøret til vandfladen:
2.3 Korrekt montage af fremløbstemperaturføler
Trin Handling
1 Benyt varmeledende pasta for at
opnå en god kontakt mellem rø-
ret og føleren.
Fastgør føleren med strips.
2 Sørg for tilstrækkelig isolering
omkring føleren.

3006026-2018-11-22.fm
20/88
2.4.1 Tilslutning af køleflade
Dimensionering af ventiler og rør mv. samt tilslutning af fladen skal altid udføres af
autoriseret personale iht. gældende love og regler.
Blandesløjfe Her henvises til pricipskitse.
Tilslutning af
isoleret CCW
For isoleret CCW skal tilslutningen ske med stophaner og unioner, sådan at fladen let
kan løsnes, trækkes ud og rengøres.
Bemærk
Sådan må fladen ikke tilsluttes.
Tilslutning uden cirkulationspumpe medfører risiko for frostsprængning.
Udluftning Efter tilslutning af vand på aggregatet:
• Udluft systemet grundigt via den øverste udluftningsskrue på vandfladen.
Manglende
udluftning Ved manglende udluftning er der risiko for stillestående vand i systemet,
hvilket kan medføre frostsprængninger i kolde perioder.
Montage af
motorventil Ventilen må ikke monteres med motoren nedad.
Isoler fremløbsrør
og vandflade Rør og vandflade skal isoleres i henhold til gældende krav.
Frostsikring
Kølefladen kan frostsikres ved at iblande kølevandet 25% ethylen-glycol.
Herved opnås frostsikring ned til -13°C.
2.4 Køleflade
RD12900-03
Table of contents
Languages:
Other Exhausto Control Unit manuals

Exhausto
Exhausto VEX260 User manual

Exhausto
Exhausto OJ GreenZone Module A User manual

Exhausto
Exhausto EBC12 Series User manual

Exhausto
Exhausto OJ GreenZone Module M User manual

Exhausto
Exhausto EBC 10-P Installation instructions

Exhausto
Exhausto VEX200 series User manual

Exhausto
Exhausto OJ GreenZone User manual
Popular Control Unit manuals by other brands

Crestron
Crestron C2N-FT-TPS4 Operations & installation guide

Landis+Gyr
Landis+Gyr WZU-M Series Installation and operating guide

Komfovent
Komfovent ping installation manual

Eaton
Eaton Vickers CM2 Series Overhaul manual

Anadigm
Anadigm Servenger PAM-5002R Series quick start guide

Ksenia
Ksenia lares 4.0 - 40 wls Installation and use manual