QuickSet Pro
Programming Instructions
(for MS, MLS and CDH/W products only)
Energy Conservation Solutions Pty Ltd - Exclusive Distributor - Australian and New Zealand
Locations: VIC/TAS, NSW, QLD, FNQ, ACT, SA/NT, WA, NZ. For Contact Details Visit: www.ecs.net.au
COMMUNICATING WITH
A SENSOR
ADJUSTING THE
TIME DELAY SETTINGS
‘Downloading’ the settings from a
sensor copies the contents of the
sensor’s memory onto the screen and
memory of the programmer.
Caution: ‘Uploading’ new settings
into the sensor over-writes the
memory of the sensor with the
contents of the programmer.
Always download sensor settings
prior to commencing.
Note: If programmed incorrectly,
repeat steps below.
To perform a download from a
sensor:
1 Turn the programmer on by
pressing any key. (Fig.3)
2 Point the programmer at the lens
of the sensor, ideally from directly
below and from 1 to 1.5 metres away.
(Fig.4 and 5)
3 Holding the programmer steady,
press and release the DOWNLOAD
key. (Fig.4) Continue to hold
the programmer still while the
programmer and sensor exchange
information (this may take up to
10 seconds). (Fig.6) If the lights
controlled by the sensor are ‘on’
prior to a download, they will switch
off then on while the download is
occurring. The download is complete
when the QuickSet Pro displays
information from the sensor. (Fig.7)
Note: If the exchange is disrupted,
typically due to the programmer being
moved too much, (Fig.5) the lights
will not come on. Simply repeat the
process, after adjusting the distance
or aim if necessary.
4 Use the right ARROW key to go
to the next screen, scroll DOWN to
highlight ‘off delay’, right ARROW so
the time delay parameter is highlighted
e.g. 20 mins (Fig.8) then press OK.
If information about this parameter is
required, press the OPTION key (Fig.9)
scroll DOWN to highlight help, then press
the OK key. Press the left ARROW key to
return to the previous menu.
5 Scroll UP or DOWN to select
the desired time delay. Then press
OK (Fig.10). The new time will be
highlighted. This will be the new ‘off
delay’ setting to control the length
of time the lights remain on once
movement is no longer detected by
the sensor.
6 To upload the new setting to the
sensor use the UPLOAD key pointing
the QuickSet Pro directly towards the
sensor (Fig.11). The lights will turn off
then on to acknowledge a successful
upload. (Fig.12) Press LEFT key to go
back to Home Menu
Note: To establish the current
settings of a sensor, at anytime,
perform a download (Repeat Steps
1, 2 & 3). Press the right arrow for
the current parameters.This will not
alter the settings in the sensor. This
simply allows the settings within the
sensor to be read on the screen of
the programmer.
FIG.4
Download Button
FIG.6 Download
Download in progress...
Download Download Summary
FIG.5
FIG.12
MS2000D Mk2.1 v20
Ballast = DALI 1%
Burn in Hrs = 0
Illumination 59
Replies = 32
Comms = 30kHz
Upload
FIG.11
Upload Button
FIG.7
Download
MS2000D Mk2.1 v20
Illumination113
Replies = 32
Comms = 30kHz
FIG.8
MLS2000DI Mk5
Common Parameters
Power Up
Response
Off Delay
On Sensitivity
Bus Connect
1st Zone
2nd Zone
3rd Zone
4th Zone
ON
AUTO
20 mins
80
YES
--
--
--
--
Next View Options
MLS2000DI Mk5
Common Parameters
Power Up
Response
Off Delay
On Sensitivity
Bus Connect
1st Zone
2nd Zone
3rd Zone
4th Zone
ON
AUTO
20 mins
80
YES
--
--
--
--
Next View Options
FIG.10
MLS2000DI Mk5
Common Parameters
Power Up
Response
Off Delay
On Sensitivity
Bus Connect
1st Zone
2nd Zone
3rd Zone
4th Zone
ON
AUTO
15 mins
80
YES
--
--
--
--
Options
MLS2000DI Mk5
Common Parameters
Power Up
Response
Off Delay
On Sensitivity
Bus Connect
1st Zone
2nd Zone
3rd Zone
4th Zone
ON
AUTO
20 mins
80
YES
--
--
--
--
10 secs
1 min
2 min
5 min
10 mins
15 mins
20 mins
25 mins
30 mins
35 mins
40 mins
Options
FIG.9
Help
Off Delay: Thois is the
time it takes since the last
occupancy was detected
for the lights to turn off or
go to the exit condition.
You may set this time to 10
seconds for walk testing.
Check the rmware version
No. before selecting •
DISABLED • - it may not
work with older detectors.
MLS2000DI Mk5
Common Parameters
Power Up
Response
Off Delay
On Sensitivity
Bus Connect
ON
AUTO
20 mins
80
YES
Next View Options
Load From Favourite...
Store as Favourite
Upload Selected
Help
Switch Off
Exit to Home