ExTox ET-1D Series User manual

Instruction Manual
ExTox Control Unit
ET-1D Series

Instruction Manual
ExTox Control Unit ET-1D Series
Page 2 of 17
Foreword
We thank you very much for your confidence in our products and us, the ExTox Gasmess-
Systeme GmbH.
The Control Unit ET-1D as well as all other ExTox-Products and services stand for our high
quality targets. Our business is the health protection of mankind, protection of the environ-
ment and installations. We are glad to take this responsibility. Our Quality Management
System therefore follows ISO 9001 and our Production Monitoring is to keep the European
Directives 94/9/EC („ATEX“). You profit of the high reliability due to modern sensor tech-
niques and consequent interpretation acc. to the requirements of the regulations and stan-
dards valid for industrial application.
The Control Unit of the ET-1D series is a compact and easily understandable system for sin-
gle transmitters. It is completely configurable at the control unit to be easily in line with the
different requirements and applications. By means of its interfaces it is easy to integrate
even in higher control and management systems. It could be used in combination with all
ExTox Transmitters ExSens (-I) and Sens (-I).
Please do not hesitate to contact anytime in case of questions or if you require information:
ExTox Gasmess-Systeme GmbH
Max-Planck-Straße 15 a
59423 Unna
Germany
Telefon: +49(0)2303 33 247 0
Fax: +49(0)2303 33 247 10
Internet: www.ExTox.de
BA_ET-1_e_2011-12-16.doc, Rev.: 16.12.2011
Software Version ET-1D: REV61207
(Subject to technical changes)

Instruction Manual
ExTox Control Unit ET-1D Series
Page 3 of 17
Content
1Introduction 4
2Features of the Control Unit of the ET-1D Series 5
3Indications and Facilities of the Control Unit 6
4Configuration 7
5Operation of the Control Unit 11
5.1 Measuring Mode 11
5.2 Alarms 11
5.3 Under-Scale and Over-Scale of Measuring Range 12
5.4 Channel Fault 12
5.5 Fault of Control Unit 13
5.6 Programme Run Monitoring (Watchdog) 13
5.7 Initialisation 13
5.8 Service Mode 13
5.9 Analogue Outputs 4…20 mA (Type ET-1DA only) 13
6Application 14
6.1 Measuring Function 14
6.2 Use in combination with hazardous Areas 14
7Installation 15
7.1 Mechanical Installation 15
7.2 Electrical Installation 15
8Maintenance of Gas Detection Systems 16
8.1 Basic Information 16
8.2 Visual Check 16
8.3 Functional Check 16
8.4 System Check 17
9Technical Data and Declaration of Conformity 17

Instruction Manual
ExTox Control Unit ET-1D Series
Page 4 of 17
1Introduction
This Instruction Manual generally describes operation, installation and maintenance of the
following ExTox-Products:
Wall mounted DIN-Rail Control Panel 19''-Rack
Artikel-Nr. 230 V / 24 V 230 V / 24 V 230 V / 24 V 230 V / 24 V
ET-1D 303010 303011 303014 303015
ET-1DA 305010 305011 305014 305015
Type specific data for each device should be taken from a corresponding separate and spe-
cific Data Sheet. This Data Sheet forms consequently part of this Instruction Manual. Refer-
ences on the Data Sheet within this text are marked with )DB.
Please read this Instruction Manual carefully before installation and initial operation of the
control unit. We kindly ask you to pay attention to all details and cross-references.
We kindly ask you not to repair the control unit or to perform any changes which go beyond
the measures described herein. Otherwise you endanger your own safety and your warranty
claims of merchantability. In such cases please contact ExTox or authorised ExTox Service
Partner. Third parties take the responsibility for correct performance of work when mainte-
nance and repairs are done by them.
On receipt of goods please take care that packing and consignment are not damaged and
the goods supplied correspond to the articles described in the delivery note. Please do also
compare with your order. In case of any damage please inform your forwarding agent and
your supplier. Please keep the damaged packing.
Please keep in mind that control units are sensitive measuring devices and take special care
when unpacking and installing them.

Instruction Manual
ExTox Control Unit ET-1D Series
Page 5 of 17
2Features of the Control Unit of the ET-1D Series
Concentrations of flammable and toxic gases as well as of oxygen are centrally evaluated by
the Control Units of the ET-1D Series after measuring them safely with our ExTox transmit-
ters. Control Units of the ET-1D Series could be combined with all ExTox-Transmitters Ex-
Sens (-I) and Sens (-I).
Other measurands such as for example temperature or pH-value can be evaluated with
suitable transmitters (4-20 mA, 3-wires).
The control units are available in wall mounted housing, for DIN-Rail installation and for
installation in 19''-Rack or Control Panel. The power supply can flexibly be done with 230 V
or 24 V DC. On request we could supply you with corresponding uninterruptible power sup-
plies for our control units.
The control units in combination with ExTox transmitters comply with EN 60079-29-1 and
EN 45544 for Gas Detection Systems. Furthermore they are in conformity with the European
Directives 94/9/EC (ATEX), 2004/108/EEC (EMC) and 2006/95/EEC (LVD).
Survey on the Control Unit of the ET-1D Series:
1 input channels for transmitter (4-20 mA, 3-wire)
Adjustment to be done directly at the control unit without any work at the transmitter
2 digital inputs, potential free
2 freely adjustable alarm levels per channel, latching adjustable
integrated acoustic signalling device
1 fault indication per transmitter/channel
4 relays outputs, potential free, for indication of Alarm 1, Alarm 2, horn and device fault
illuminated LC-display (4 x 20 signs) for indication of measured values, messages and
alarms
menu oriented configuration of the device without further tools needed
LEDs for alarms, operation, channel fault, device fault and service mode
Service mode
horn reset
1 analogue output (Type ET-1DA only)

Instruction Manual
ExTox Control Unit ET-1D Series
Page 6 of 17
3Indications and Facilities of the Control Unit
F2 F3 F4F1
ET-1D
Gasmess-Systeme GmbH
ExToxGasmess-Systeme GmbH Tel. +49 (0)231/589409-0 www.extox.de
Störung
Fault
Alarm
1
Betrieb
Power
2
Cl2 Chlor
7.0 ppm
Alarm1=ON Alarm2=ON
The display indication and the assignment of the selection keys F1 to F4 varies in the differ-
ent operation modes of the ET-1D. The corresponding assignment of the functional keys is
indicated in the line at the bottom of the graphic display.
The selection keys dispose of a repeating function that means on longer operation the selec-
tion list is quickly leafed through.
Under normal operation (Chapter 5) the display gives the following information:
1. Line: measured gas and/or measurand, actual measured value with unit
2. Line: bar graph indication of the actual measured value. The indicated values range
from 0 to 100 % of measuring range.
3. Line: setting of alarm levels 1 and 2
4. Line: setting of the functional keys F1 to F4. The menus for configuration of the pa-
rameters (Chapter 4) could be reached via F1 (NEXT). Functional key F2 serves to quit
the alarms (see Chapter 5.2). Functional key F3 can be used to quit the integrated
acoustic signalling device and horn relay. Under normal operation the functional key F4
is not set.
If you leave indication under normal operation by pressing F1 (NEXT) you reach the configu-
ration menus. The evaluation of measured values is continued unaffected. The configuration
menus are always passed cyclically in rotation. Therefore you have to press functional key
F1 that often until you reach the required menu or the normal display indication again. You
could see all settings, but you could not change them until you have not activated the
password protected access level (see Chapter 4).
As soon as the access level is passed you can change the parameter settings by means of
keys F2 and F3. With the keys F2 (^) and F3 (v) you can stepwise increase or decrease the
values or leaf through a given list. In case only key F2 is set with (^v), the settings change
between two alternatives. Made changes are stored by pressing F4 (SAVE). The changes are
activated after leaving the menu. If you leave the menu without pressing F4 (SAVE) the
former stored values remain valid and all made changes get lost.
If there is no setting done for more than 10 minutes the display automatically changes to
the indication under normal operation (except the service mode is activated).
LEDs:
Alarm 2 (red)
Alarm 1 (red)
LEDs:
Operation
(green)
Fault (yellow)
Display
Functional Keys

Instruction Manual
ExTox Control Unit ET-1D Series
Page 7 of 17
4Configuration
Configuration of the ET-1D comprises all parameter settings to customise the functionality
of the device to the requirements of your application. This covers for example measured
gas, measuring range, alarm levels, etc.
If not otherwise indicated, evaluation of measured values, alarms and faults is done during
configuration as per under normal operation.
You will find the description of the configuration possibilities in the below mentioned table.
It follows the menu structure of the ET-1D.
The following information is given for each parameter:
Menu text: denomination in the menu on the display
Selection: setting of the parameters
Function: description of the impacts on the condition of the gas detection system.
Attention: to be able to perform any changes you have to activate the code protected ac-
cess level first.
Menu text Selection Function
Password ----
(Inputs
locked)
O.K.
Password re-
leased
Release is done by pressing the functional keys F3 and
F4 simultaneously for ca. 5 s.
Pressing the two keys for ca. 5 s again cancels the
release.
Release is automatically reset if the keys are not used
for more than 10 minutes.
Attention: During service mode (Service = On) the
release remains permanently.
Password GB, D In the release menu it could be switched between the
languages German (D) and English (GB). Please press
the key F2 until the indication on the display changes.
GB →D: English activated
D →GB: German activated
Service Off, On Alarm and fault messages as well as especially the
relay outputs are locked during service mode. The ser-
vice condition is indicated by a blinking operation LED
and the service relay (see Chapter 5.8).
Gas List of gases
and meas-
urands
Displays the chemical totals formula belonging to the
measured gas or the denomination of other meas-
urands. The selected denomination is indicated on the
display during measuring operation.
Dimension ppm, % (v/v),
% LEL, pH,
degrees
Unit for the measuring range. The selected denomina-
tion is indicated on the display during normal opera-
tion.
Dec. Point 0,
0.0 It is fixed whether the measured value is displayed
with decimal point.
Attention: The change of this parameter affects also
the settings of end value of measuring range and
alarm levels.
Range 0.0 bis 3000.0,
0 bis 30000 Fixes the end value of measuring range.

Instruction Manual
ExTox Control Unit ET-1D Series
Page 8 of 17
Menu text Selection Function
Alarm 1,
Alarm 2 0
to range Fixes the two alarm thresholds and the direction of
exceeding for triggering of alarms.
a. Values of alarm thresholds are in ascending order:
alarms are triggered on exceeding.
Example flammable gases:
Alarm 1: 20 % LEL, Alarm 2: 40 % LEL
b. Values of alarm thresholds are in descending or-
der: alarms are triggered on under-run.
Example Oxygen Monitoring:
Alarm 1: 19 % (v/v) O2, Alarm 2: 17 % (v/v) O2
Please note that due to that reason both alarm levels
have to differ at least for a minimum.
Quit A1,
Quit A2 On,
Off Indicates whether the alarm and the corresponding
relay is latching (ON) or not latching (OFF). See Chap-
ter 5.2.
A non latching alarm stops if the alarm condition is no
longer present. Please keep in mind the alarm hys-
teresis (see below).
A latching alarm has always to be reset manually via
key F2 (QUIT).
Horn A1,
A2,
---
Indicates whether the horn relay (and the linked inte-
grated acoustic signaller) is connected to Alarm 1 or 2.
On indication "---" both are deactivated.
The horn relay can be reset via key F3 (HORN), even if
the alarm condition is still present.
Attention: This function should only be used for exter-
nal acoustic signallers.
Hint: The horn is triggered again, if the alarm level is
reached again after an interruption in the meantime
("re-triggering of alarms). This is also valid if a latch-
ing alarm has not been quit in the meantime.
Relay mode A1,
Relay mode A2,
Relay mode F,
Relay mode H
Closed,
Opened Indicates whether the alarm, fault or horn relay closes
(Closed) or opens (Opened) on presence of triggering
conditions.
Closed: the relay is closed during measuring operation
without alarm or fault activated (5.1).
Opened: the relay is open during measuring operation
without alarm or fault activated (5.1).
With the setting you choose whether an interruption of
power supply at the ET-1D will release an alarm
(Closed) or not (Opened). Independently the choice of
the two-way contact of the relays determines whether
you use the open or closed current principle.
In safety-related circuits the mode Closed in conjunc-
tion with the closed-current principle will be used in
principle normally. But to active optical or acoustic
indication the mode Opened is provided in most of the
applications

Instruction Manual
ExTox Control Unit ET-1D Series
Page 9 of 17
Menu text Selection Function
Hyst. 0 % to 10 % Fixes the alarm hysteresis in percent of the measuring
range. A non-latching alarm lapses only if it is the
value of hysteresis below the alarm level. By means of
this permanent repetition of alarm triggering due to
slight fluctuation of measuring values near the alarm
level are avoided. Example: Measuring range 100
ppm, Hysteresis 3 %, Alarm level 10 ppm. Alarm will
deactivated when the measuring value is below 7 ppm.
Standard setting: 0 %
Attention: Combination of low alarm levels with great
hysteresis may involve that alarms will be deactivated
never or very late.
NPC 0 to 5 % Zero point attenuation can be adjusted. The range of
values from 0 to + NPC of measuring range is indi-
cated as zero. In the subsequent range up to + 2·NPC
of measuring range a fluent approach to a linear curve
takes place.
This function enables the suppression of small indica-
tion changes in the display without affecting the indi-
cation behaviour around the alarm levels. But alarm
levels shall not
Standard setting: 0 %, that means, deactivated.
Iist: The actual unevaluated value of the transmitter
output current which rests at the input of the control
unit is displayed.
The two last menu items serve for the adjustment of the control unit without any work to be
necessary at the transmitter.
Adjustment is done in two steps:
1. When applying zero gas first the zero point (NP) is as long changed as the value indi-
cated on the display is ISTWERT 0. Please note that negative values are described as "<
0". If the adjustment is done correctly the preset "<" disappears and exactly 0 is de-
scribed.
2. Then when applying test gas GAIN is adjusted until the actual value indicated on the
display corresponds to the nominal value.
Zero 2.000 to 6.000 State of the zero point. In case of value 4.000 [mA]
there is no correction done.
ACTVALUE: the measured value corrected in ZERO and
eventually GAIN is displayed.
Gain 0.500 to 2.000 Correction value for the gain. For explication please
see text above. In case of value 1.000 there is no cor-
rection done.
ACTVALUE: the measured value corrected in ZERO and
eventually GAIN is displayed.
Remarks for calibration/ adjustment at the control unit
The ET-1D is usually used with transmitter which dispose of a 4-20 mA output with linear
curve, that means an input current of 4 mA is interpreted as zero point and an input current
of 20 mA is interpreted as end value of measuring range. In between conversion is done
linearly according to the following formula:

Instruction Manual
ExTox Control Unit ET-1D Series
Page 10 of 17
rangemeasuringofvalueEnd
mA16 mA4currentmeasured
valueMeasured ⋅
−
=
Corrections of the settings are usually done at the transmitter itself and not at the control
unit.
In case this is impossible, such as for example due to the fact that the transmitter is hardly
accessible for maintenance purposes or it should not be opened during operation, the ET-1D
offers the possibility of a device internal adjustment. Therefore the determined current
value is converted with an offset factor and a gain factor directly after recording of the
transmitter signal. After that formation and evaluation of measured values are done. All
necessary settings can be done in the menus ZERO and GAIN.
Attention: The range of correction values is limited to restrict the adjustment to convenient
tolerance range as far as measuring techniques are concerned. Further corrections have to
be performed directly at the corresponding transmitter.

Instruction Manual
ExTox Control Unit ET-1D Series
Page 11 of 17
5Operation of the Control Unit
Features which are characteristic for the specific operation mode are printed in bold.
5.1 Measuring Mode
There are no faults and alarms. The measured value is within the range between 0 % and
100% of the end value of measuring range.
Please note that evaluation of the measured value is only done after zero point attenuation
NPC has been carried out (unless activated). Values near zero are inside the unavoidable
tolerance range for transmitters and are therefore attenuated to avoid misinterpretation.
The real transmitter output current and with it the unprocessed raw signal can always be
seen by selecting the configuration menu NPC.
Status LEDs
Alarm 1, 2 (red): off
Operation: on
Fault: off
Display
Actual Value: actual measured value within the range 0 to end value of
measuring range
Bar Graph: actual value within the range 0 to end value of measuring range
Alarm A1, A2: alarm value settings are permanently displayed
Relays
Alarm 1 and 2 (K1, K2): not triggered
Fault (K3) : not triggered
Horn (K4): not triggered
Integrated Signaller: mute
5.2 Alarms
Minimum one configured alarm level is triggered.
If the alarm is configured as non-latching, it stops automatically if the alarm condition is no
longer present. Please pay attention to the alarm hysteresis.
If the alarm is configured as latching, it has to be reset manually via key F2 (QUIT) in case
the alarm condition is no longer available. This is possible only if you are outside of any con-
figuration menu.
The horn relay and the internal signaller can be connected to Alarm 1 or 2 or deactivated
depending on parameter setting (Chapter 4: Horn). Different from the alarm relays these
can be reset via key F3 (HORN), even if the alarm condition is still present.
Status LEDs
Alarm 1, 2 (red): on for the triggered alarm
Operation: on
Fault: off
Display
Actual Value: actual measured value within the range 0 to end value of
measuring range
Bar Graph: actual value within the range 0 to end value of measuring range
A1, A2: alarm value settings are blinking
Relays
Alarm 1 and 2 (K1, K2): triggered, if alarm level is reached
Fault (K3): not triggered

Instruction Manual
ExTox Control Unit ET-1D Series
Page 12 of 17
Horn (K4): triggered, if set alarm level is reached
Integrated Signaller: sounds, if set alarm level is reached.
5.3 Under-Scale and Over-Scale of Measuring Range
The measured value is within the range below 0 % and above 100% of the end value of
measuring range.
In case of Under-Scale of measuring range measures for correction of Zero Point should be
taken. The deviation value could always be evaluated more precisely in the menu NPC by
means of the transmitter output current.
In case of Over-Scale of measuring range due to high gas concentrations corresponding
measures for the individual transmitter should be taken, such as for example calibration and
adjustment.
Status LEDs
Alarm 1, 2 (red): corresponding to measuring operation (5.1) or Alarm (5.2)
Operation: corresponding to measuring operation (5.1) or Alarm (5.2)
Fault: off
Display
Actual Value: < 0 or > End Value of Measuring Range
Bar Graph: 0 or end value of measuring range
A1, A2 corresponding to measuring operation (5.1) or Alarm (5.2)
Relays
Alarm 1 and 2 (K1, K2): corresponding to measuring operation (5.1) or Alarm (5.2)
Fault (K3) : not triggered
Horn (K4): corresponding to measuring operation (5.1) or Alarm (5.2)
Integrated Signaller: corresponding to measuring operation (5.1) or Alarm (5.2)
5.4 Channel Fault
The input current of the transmitter is outside the limits fixed in the system parameters,
that means below Imin = 1.5 mA or above Imax = 22.5 mA.
Reason for that might in general be a transmitter fault, interruption of transmitter power
supply, interruption or short circuit of transmitter cable.
Attention: Please keep in mind that in case of channel fault the respective alarms are acti-
vated. This happens when passing the limit Imax if the exceeding of alarm levels is moni-
tored. It happens when passing the limit Imin if the under-run of alarm levels is monitored.
In both cases the following details as well as the additional information as per Chapter 5.2
are valid.
Status LEDs
Alarm 1, 2 (red): corresponding to measuring operation (5.1) or Alarm (5.2)
Operation: on
Fault: on
Display
Actual Value: << 0 or >> end value of measuring range
Bar Graph: 0 or end value of measuring range
A1, A2 corresponding to measuring operation (5.1) or Alarm (5.2)
Relays
Alarm 1 and 2 (K1, K2): corresponding to measuring operation (5.1) or Alarm (5.2)
Fault (K3) : triggered
Horn (K4): corresponding to measuring operation (5.1) or Alarm (5.2)
Integrated Signaller: corresponding to measuring operation (5.1) or Alarm (5.2)

Instruction Manual
ExTox Control Unit ET-1D Series
Page 13 of 17
5.5 Fault of Control Unit
A fault of Control Unit is indicated in case the internal power monitoring or memory test
issues a fault. The device tries to keep normal operation, especially messages and relays
are not reset. It cannot be excluded that the ET-1D is able to go into undefined condition
depending on the cause of fault.
The fault of control unit is non-latching, that means the ET-1D continues normal operation
in case of return to the admissible voltage range or in case of faultless passing the memory
test.
Please check the power supply of the device. In case of a memory fault please contact the
ExTox-Service.
Status LED
Fault Control Unit: on
Relays
Fault (K3) : triggered
(With the exception of the described reactions the system status can be undefined.)
5.6 Programme Run Monitoring (Watchdog)
The ET-1D disposes of a programme sequence monitoring by means of a Watchdog element
working independently. In case this watchdog recognizes an interruption of the regular
course it triggers a reset of the ET-1D. Then the initialisation (5.7) is passed.
If the ET-1D does not enter normal operation again, please contact the ExTox-Service.
5.7 Initialisation
After connection of the ET-1D to the power supply it is passing an initialisation phase. The
installed software version and the Internet Address of ExTox are indicated on the start
screen for 120 seconds. The remaining time (in seconds) until starting normal operation a
countdown is displayed.
During initialisation all LEDs are periodically switched on and off so that their functionality
could be checked. At the same time the complete memory (RAM/ROM/EEPROM) is checked.
This test is cyclically repeated during the measuring mode.
5.8 Service Mode
Alarm and fault messages as well as especially the relay outputs are locked during service
mode. The service condition is indicated by a blinking operation LED. The service mode can
be activated in the configuration menu (see Chapter 4).
During service mode the release remains permanently.
5.9 Analogue Outputs 4…20 mA (Type ET-1DA only)
A current corresponding to the transmitter measured value is issued at the analogue out-
puts as long as it is in the range between Imin = 1.5 mA to Imax = 22.5 mA. Transmitter out-
put currents < Imin or > Imax are indicated at the analogue outputs of the ET-1DA on Imin or
Imax.

Instruction Manual
ExTox Control Unit ET-1D Series
Page 14 of 17
6Application
6.1 Measuring Function
The use of Gas Detection Systems for explosion and health protection requires special care.
Besides qualified support of ExTox and the detailed information in the Instruction Manuals
as well as Technical Data Sheets ()DB) there are several guides to assist you for the safe
use and operation of Gas Detection Systems. These guides deal with the selection, installa-
tion, initial operation and regular maintenance.
Furthermore there could be national regulations. In Germany there are for example the
guidelines of the Berufsgenossenschaften BGI 518 and BGI 836 obligatory for certain appli-
cations.
Denomination Title
EN 60079-29-2 Explosive atmospheres – Part 29-2: Gas detectors – Selection, installa-
tion, use and maintenance of detectors for flammable gases and oxygen
Merkblatt T023,
BGI 518 Gaswarneinrichtungen für den Explosionsschutz - Einsatz und Betrieb
Merkblatt T055,
BGI/GUV-I 8617 Mess- und Warngeräte für den Explosionsschutz – Antworten auf häufig
gestellte Fragen
EN 45544-4 Electrical devices used for the direct detection and direct concentration
measurement of toxic gases and vapours - Part 4: Guide for selection,
installation, use and maintenance
Merkblatt T021,
BGI 836 Gaswarneinrichtungen für toxische Gase/Dämpfe und Sauerstoff - Einsatz
und Betrieb
EN 50292 Electrical apparatus on the detection of carbon monoxide in domestic
premises – Guide for the selection, installation, use and maintenance
EN 50244 Electrical apparatus on the detection of combustible gases in domestic
premises – Guide for the selection, installation, use and maintenance
DIN-Standards available at VDE-Verlag, Frankfurt or Beuth-Verlag, Berlin
BGI available at Jedermann-Verlag, Heidelberg
6.2 Use in combination with hazardous Areas
The Control Unit itself may not be installed in hazardous areas, but it is allowed to use the
control unit in combination with explosion protected transmitters. Please note the corre-
sponding installation hints for each individual transmitter.
All types of control units can be used in combination with hazardous areas of Zone 2.
Please pay attention to the remarks regarding configuration of the control unit and its func-
tion in the safety system when using the detection system in combination with hazardous
areas.

Instruction Manual
ExTox Control Unit ET-1D Series
Page 15 of 17
7Installation
7.1 Mechanical Installation
The control unit should be installed at an easily accessible place to enable the reading out of
messages at every time and to ensure an easy maintenance.
Please note the indicated operation temperature ()DB). The ET-1D should be installed pro-
tected against weather conditions and bigger climatic fluctuations. A separate weather pro-
tection may be provided in some cases.
The dimensions for assembly and further installation dimensions to be taken from the Tech-
nical Data Sheet ()DB).
The type in wall mounted housing and for installation in control panels or 19''-Rack are fix
screwed up. The type for DIN-Rail installation disposes of four fixtures with which the hous-
ing is snapped on the DIN-Rail. By pulling the handles standing out of the backside of the
device the connection can easily be untied and the device can be taken off.
The Control Unit ET-1D may not be installed in hazardous areas.
7.2 Electrical Installation
The electrical installation may only be done by electro specialists according to the installa-
tion regulations on the subject. There are especially regulations for the Installation of In-
formation Engineering IEC 60364 (in Germany VDE 0800) and for lightning protection ac-
cording to EN 62305 (in Germany DIN V VDE V 0185). The power supply of the control unit
has to meet the requirements of an arrester of Class C or of Type 2. Please make sure that
there might be special requirements in case control unit and transmitters are installed in
separated rooms.
The ET-1D is provided for commercial use. Attention: ET-1D is a class A device. It can cause
radio interference in domestic premises. In this case suitable measures may be provided by
the user.
When running the cable you should pay attention to the fact that the cables for the gas sen-
sors should better be run separately.
On the type in wall mounted housing and for DIN-Rail installation the housing has to be
opened. To do this you have to remove the blind plates on the left and right side of the
front and unscrew the four screws. The cover can now be opened and tucked up. The con-
nections are in the bottom part of the housing. The big cable gland M20x1.5 serves for the
power supply cable.
On the types for installation in control panel or 19''-Rack the connection board will be
mounted in a separated vat, which may be installed in the cabinet at a suitable place. Both
components will be electrical connected by the included ribbon cable. If you need a lcable
which is longer than the standard dimension mentioned in the ()DB), please contact ExTox.
As option the device may delivered as a combined "Sandwich"-version. In this case the
clamps are freely accessible on the backside of the device.
The control unit starts operation automatically with connection to the power supply.
You could find the connection scheme for input and output in the Data Sheets ()DB) and
also marked on the PCB. Connection is done via plug clamps. Remove the plug before con-
necting the cable to avoid mechanical damage. After the assembly is done you could con-
nect the plug again.
The connection PCB shows a spacial separation of the transmitter inputs and the relay out-
puts. The overlapping of lines between these two areas within the housing and on the PCB
should be avoided. It should especially be ensured that correct isolation is kept in case ca-
bles of different voltage get in contact. We recommend not removing the protection isola-
tion directly after the cable gland but only close to the corresponding clamp.
Normally the shielding of transmitter cables shall not be feed into the ET-1D-housing. PE-
wires my be connected to the corresponding clamps.
Please bear in mind that the cable glands have to be firmly tightened to ensure the suffi-
cient strain-relief. Not used cable glands have to remain closed with already installed plugs.

Instruction Manual
ExTox Control Unit ET-1D Series
Page 16 of 17
8Maintenance of Gas Detection Systems
The following descriptions are generally valid for Gas Detection Systems of the company
ExTox GmbH consisting of the herein described control units and connected transmitters.
8.1 Basic Information
Maintenance done by specialists is an indispensable measure for checking and keeping the
functionality of gas detection systems. Maintenance comprises inspection, calibration and
adjustment as well as functional test of the complete system.
Most important is the testing of the connected transmitters. Control of the gas detection
system and its correct functionality are also checked.
ExTox recommends for all of her supplied transmitters regular calibration and adjustment
with test gas during functional and system checks. Please see also the details in the corre-
sponding Technical Data Sheets ()DB). An extension to 12 months might eventually be
possible in case of existing experiences on similar applications. The functionality of the Con-
trol Unit has to be tested as well.
Furthermore national valid regulations to define maintenance intervals may exist. In Ger-
many it is for example necessary in certain applications to keep Betriebssicherheitsverord-
nung (BetrSichV) and the information of the professional associations T 023 und T 021 (vgl.
6.1). ExTox recommends generally speaking the application of the measures described in
the information of the professional associations as well as the maximum calibration intervals
even if the application does not fit into their scope.
Maximum Intervals
Explosion Protection (T 023) Toxic Gases/Vapours and Oxygen (T 021)
1 Month (Visual Check)
4 Months (Functional Check)
1 Year (System Check)
1 Month (Visual Check)
6 Months (Functional Check)
1 Year (System Check)
You as user of the gas detection system bear the responsibility for the correct performance
of the maintenance. ExTox as manufacturer can only place all necessary details to build up
your specific maintenance concept at your disposal. We are glad to support you with this
task and to submit a maintenance quotation acc. to your special requirements.
The results of each maintenance should be documented even if it is not specifically required.
Hereafter the main contents of the intended checks are described. You will find details in the
above mentioned bulletins.
8.2 Visual Check
You have to check your system on mechanical damages, dust, dirt, state of a sampling sys-
tem if included. Furthermore indications and status messages have to be checked.
8.3 Functional Check
The functional check also comprises calibration by means of application of test gases and a
suitable system for application of test gas. When calibrating the indication of measured val-
ues at application of test gas is determined and compared with the nominal values. In case
the settings are corrected additionally the process is called adjustment. In case of combina-
tion with sampling systems their correct function has also to be checked. It is not necessary
to trigger the switching functions.
A functional check should only be done, if there is no alarm present. You should ensure the
same environmental conditions during this process as valid for the measuring process. For
example a transmitter used in cold storage houses should not be adjusted under normal
ambient temperatures, as there might be more or less remarkable deviations depending on
sensor type.

Instruction Manual
ExTox Control Unit ET-1D Series
Page 17 of 17
Make sure that measures have been taken to avoid unintended triggering and transmission
of alarms before applying test gas. Activate the alarm bypass in service mode at your ExTox
Control Unit, deactivate automatically triggering protection measures or inform the respon-
sible maintenance personnel. The measures corresponding to your application have to be
determined and the person in charge for maintenance has to be familiar with all details.
8.4 System Check
The system check additionally comprises the triggering of switching functions; check of sys-
tem parameters and of indication and recording facilities.
9Technical Data and Declaration of Conformity
The Data Sheet of the control unit contains all technical data ()DB).
Data sheets and Declaration of Conformity are added to the documentation separately.
This manual suits for next models
2
Table of contents
Other ExTox Control Unit manuals
Popular Control Unit manuals by other brands

Burkert
Burkert PTB 03 ATEX 1030 X operating instructions

Avnet
Avnet Qorvo Hardware user's guide

Electroline
Electroline Control Unit IV Reference manual

In2 Networks
In2 Networks Energy ICM quick start guide

maxxess
maxxess eMAX-MR62e Installation Guide and Specifications

H3C
H3C SecPath M9000-AI NSQM5MBSHA1 manual