F&F LE-03MW User manual

F&F Filipowski sp.j.
ul. Konstantynowska 79/81
95-200 Pabianice
Phone/Fax (42) 215 23 83, 227 09 71
e-mail: [email protected].pl
www.fif.com.pl
www.fif.com.pl
LE-03MW CT
Electricity consumption meter
3-phase, 2-way
tariff
User manual
v. 1.3 (201015)

LE-03MW CT – user manual
2
Table of contents
TABLE OF CONTENTS ................................................................................................................................... 2
1. PURPOSE .................................................................................................................................................. 3
2. DEVICE CHARACTERISTICS ....................................................................................................................... 3
3. MEASURED VALUES ................................................................................................................................. 4
4. OPERATOR PANEL .................................................................................................................................... 4
5. TECHNICAL SPECIFICATIONS .................................................................................................................... 9
6. COMPLIANCE AND MARKING ................................................................................................................ 10
7. DIMENSIONS .......................................................................................................................................... 11
8. CONNECTION ......................................................................................................................................... 11
9. COMMUNICATION PROTOCOL .............................................................................................................. 12
10. MANUFACTURER WARRANTY.............................................................................................................. 20

LE-03MW CT – user manual
3
1. Purpose
LE-03MW CT is an electronic, 2-way three-phase electricity meter, designed for measurement
in a semi-indirect system. A built-in real-time clock allows energy consumption to be measured
by different tariff zones. RS-485 with Modbus RTU protocol and optical port compliant with EN62056
(IEC1107) provide remote reading and configuration of the meter.
2. Device characteristics
3-phase, 2-way energy meter;
Semi-indirect current measurement (direct measurement up to 6 A);
Energy measurement in four tariff zones;
Built-in real-time clock with battery backup for switching tariff zones;
Registration of total and tariff-divided consumption of:
•total active and reactive energy;
•active and reactive energy divided into individual quadrants;
8 time schedules that divide the day into tariff zones;
Possibility of billing energy according to different weekday and weekend schedules;
Ability to divide the year into 8 time periods. In each period the energy (for working days) can
be billed according to a different schedule.
Indication of network parameters (voltage, currents, active power, reactive power, apparent
power, power factor, frequency);
Calculation of power demand for individual tariffs;
Additional resettable energy consumption meter;
RS-485 port, Modbus RTU protocol;
Optical communication port compliant with EN62056 (IEC1107);
2 SO pulse outputs with programmable number of pulses per kWh/kVarh;
Multifunctional LCD display.

LE-03MW CT – user manual
4
3. Measured values
Active energy consumed and exported
Inductive and capacitive reactive energy
Phase voltages
Phase currents
Active power (absolute value)
Reactive power (absolute value)
Apparent power
Power factor (absolute value)
Frequency
4. Operator panel
Front view of the device with display (buttons visible)

LE-03MW CT – user manual
5
4.1. Description of the display elements
Current tariff indicator.
Symbol – indicates which
parameter group the value displayed in the numeric
field is associated with. It may be a tariff (T1, T2, T3 T4)
or phase (L1, L2, L3)
indicator.
Unit of the value shown in the numeric field of the display.
Symbols have the following meaning:
kW – active power
kWh – active energy
kVarh – reactive energy
VA and kVA – apparent energy
V – voltage
A – current
The numeric field of the display indicates the value of the frequency.
Data exchange via the communication interface.
Low battery indicator for the internal clock battery.
4.2. Control elements
Control buttons for changing the displayed value.
A list of displayed parameters is shown in the following table.

LE-03MW CT – user manual
6
4.3. Data displayed on the LCD
Page
Parameter
Unit
Symbol
Format
1
Date
XX-XX-XX
2
Time
XX-XX-XX
3
Total active energy consumption
kWh
6+2 000000.00
4
T1 tariff – active energy consumption
kWh
T01
6+2 000000.00
5
T2 tariff – active energy consumption
kWh
T02
6+2 000000.00
6
T3 tariff – active energy consumption
kWh
T03
6+2 000000.00
7
T4 tariff – active energy consumption
kWh
T04
6+2 000000.00
8
Total reactive energy consumption
kVarh
6+2 000000.00
9
T1 tariff – reactive energy consumption
kVarh
T11
6+2 000000.00
10
T2 tariff – reactive energy consumption
kVarh
T12
6+2 000000.00
11
T3 tariff – reactive energy consumption
kVarh
T13
6+2 000000.00
12
T4 tariff – reactive energy consumption
kVarh
T14
6+2 000000.00
13
L1 – Phase voltage
V
L1
3+1 000.0
14
L2 – Phase voltage
V
L2
3+1 000.0
15
L3 Phase voltage
V
L3
3+1 000.0
16
L1 – Phase current
A
L1
4+2 0000.00
17
L2 – Phase current
A
L2
4+2 0000.00
18
L3 – Phase current
A
L3
4+2 0000.00
19
Total active power
kW
5+3 00000.000
20
L1 – active power
kW
L1
5+3 00000.000
21
L2 – active power
kW
L2
5+3 00000.000
22
L3 – active power
kW
L3
5+3 00000.000
23
Total apparent power
kVA
5+3 00000.000
24
L1 – apparent power
kVA
L1
5+3 00000.000
25
L2 – apparent power
kVA
L2
5+3 00000.000
26
L3 – apparent power
kVA
L3
5+3 00000.000
27
Total power factor
1+2 0.00
28
L1 – power factor
L1
1+2 0.00
29
L2 – power factor
L2
1+2 0.00
30
L3 – power factor
L3
1+2 0.00
Warning!
The meter records absolute values of power and power factor.

LE-03MW CT – user manual
7
Page
Parameter
Unit
Symbol
Format
31
Frequency
Hz
2+2 00.00
32
T1 tariff – power demand
kW
T-1
6+2 000000.00
33
T2 tariff – power demand
kW
T-2
6+2 000000.00
34
T3 tariff – power demand
kW
T-3
6+2 000000.00
35
T4 tariff – power demand
kW
T-4
6+2 000000.00
36
Resettable energy consumption
meter
kWh
The indication can
be reset by holding
down any button
(for approximately
10 s) while this
parameter is
displayed
.
000000.00
37
C11 XYZ
XYZ show the
presence of voltage
on the input lines.
0
– no voltage
1
– voltage
X
– phase L1
Y
– phase L2
Z
– phase L3
C 11 111
38
View display time
1- 30 s
The time can be
changed using the
control buttons.
When a parameter
is displayed, hold
down any button
for 10 s and then
set the desired
value by pressing
the button to the
left or right.
Lcd-t 05
39
Pulse output
12000, 1200, 120, 12
S0 12000
40
Parameter calculation option:
-
Total active energy
-
Total reactive energy
CodE 01 – total
energy = energy
consumed
CodE 05
– total
energy = energy
consumed + energy
exported
CodE 01

LE-03MW CT – user manual
8
CodE 09 – total
energy = energy
consumed
– energy
exported
41
Meter IR address
0
12345678
42
MODBUS address
0
Id 255
43
Baud rate
1200, 2400,
4800, 9600 bd 9600
44
Software version
V 1.01

LE-03MW CT – user manual
9
5. Technical Specifications
reference voltage
3×230/400 V
minimum current / base current
0.25 / 1.5 A
maximum current
6 A
minimum detection current
0.003 A
measured voltage
L-N
100÷289 V AC
L- L
173÷500 V AC
rated frequency
50 Hz
measurement accuracy
Class B
installation
3-phase, 4-wire
overload capacity
30×lmax / 10 ms
insulation
4 kV/1 min.; 6 kV/1 μs
meter power consumption
<10 VA; <2 W
meter display range
8 digits
pulse outputs
number of pulse outputs
2
type of pulse outputs
OC (open collector)
maximum voltage
30 V DC
maximum current
27 mA
pulse constant of output 1
12000, 1200, 120, 12 imp/kWh
pulse constant of output 2
12000 imp/kVar
communication
port
RS-485
communication protocol
Modbus RTU
baud rate
1200, 2400, 4800, 9600 bps
parity
EVEN
stop bits
1

LE-03MW CT – user manual
10
reading indication
2×LED
operating temperature
-25÷55°C
terminal
2.5 mm2screw terminals
dimensions
76×100×65 mm
(4.5 of the DIN module)
installation
on TH-35 mm rail
ingress protection
IP51
Insulation protection class
Class II
housing
self-extinguishing plastic UI94 V-0
6. Compliance and marking
The meter is marked with an individual serial number, which makes it possible to identify it
unambiguously. The marking is indelible (laser engraving).
The meter has the option of sealing the input and output terminals, preventing the meter from being
bypassed.

LE-03MW CT – user manual
11
7. Dimensions
8. Connection

LE-03MW CT – user manual
12
9. Communication protocol
The meter is equipped with an RS-485 interface that supports the Modbus RTU communication
protocol.
Default communication parameters:
Modbus address 1
communication rate 9600 bps
The current communication parameters (Modbus address, baud rate) can be read from the views on
the LCD display.
9.1. List of registers
Legend:
Table column
Description
Register
The address of the registry that stores the parameter.
Dec – address in decimal form
Hex – address in hexadecimal form
Feature
Parameter name
Type
Data recording format:
U16 – 16-bit unsigned integer
U32 – 32-bit unsigned integer
FLOAT – floating-point number stored in ieee 754 format
R/W
Read/write:
R – read-only data
W – write-only data
R/W – read and write data
Quantity
Number of registers holding the parameter
Settings
Range of parameter settings

LE-03MW CT – user manual
13
Register
Feature Type R/W Quantity
Settings
Dec
Hex
0
0
Serial number
U32
R
2
1
2
Meter Modbus address
U16
R/W
1
1÷247
2
3
Baud rate
U16
R/W
1
1200, 2400, 4800,
9600
3
4
Software version
Float
R
2
6
6
Hardware version
Float
R
2
8
8
Current transformer CT
U16
R/W
1
List of setting codes in
the table below
9
9
Configuration of the pulse output
Float
R/W
2
12000, 1200, 120, 12
11
B
Parameter calculation option:
- Total active energy
- Total reactive energy
U16
R/W
1
1 – total energy
= consumed energy,
5 – total energy
= consumed energy,
+ energy exported
9 – total energy
= consumed energy
- energy exported
13
D
View display time
U16
R/W
1
1÷30
14
E
L1 – Phase voltage
Float
R
2
16
10
L2 – Phase voltage
Float
R
2
18
12
L3 – Phase voltage
Float
R
2
20
14
Frequency
Float
R
2
22
16
L1 – Phase current
Float
R
2
24
18
L2 – Phase current
Float
R
2
26
1 A
L3 – Phase current
Float
R
2
28
1C
Total active power
Float
R
2
30
1E
L1 phase – active power
Float
R
2
32
20
L2 phase – active power
Float
R
2
34
22
L3 phase – active power
Float
R
2
36
24
Total reactive power
Float
R
2
38
26
L1 phase – reactive power
Float
R
2

LE-03MW CT – user manual
14
40
28
L2 phase – reactive power
Float
R
2
42
2 A
L3 phase – reactive power
Float
R
2
44
2C
Total apparent power
Float
R
2

LE-03MW CT – user manual
15
Register
Feature Type R/W Quantity
Settings
Dec
Hex
46
2E
L1 phase – apparent power
Float
R
2
48
30
L2 phase – apparent power
Float
R
2
50
32
L3 phase – apparent power
Float
R
2
52
34
Total power factor
Float
R
2
54
36
L1 phase – power factor
Float
R
2
56
38
L2 phase – power factor
Float
R
2
58
3 A
L3 phase – power factor
Float
R
2
60
3C
Time
Float
R/W
2
256
100
Total active energy
Float
R
2
Value dependent
on the set calculation
option
(see register 11)
258
102
L1 phase – total active energy
Float
R
2
260
104
L2 phase – total active energy
Float
R
2
262
106
L3 phase – total active energy
Float
R
2
264
108
Consumed active energy
Float
R
2
266
10 A
L1 phase – consumed active energy
Float
R
2
268
10C
L2 phase – consumed active energy
Float
R
2
270
10E
L3 phase – consumed active energy
Float
R
2
272
110
Exported active energy
Float
R
2
274
112
L1 phase – exported active energy
Float
R
2
276
114
L2 phase – exported active energy
Float
R
2
278
116
L3 phase – exported active energy
Float
R
2
280
118
Total reactive energy
Float
R
2
Value dependent
on the set calculation
option
(see register 11)
282
11 A
L1 phase – reactive energy
Float
R
2
284
11C
L2 phase – reactive energy
Float
R
2
286
11E
L3 phase – reactive energy
Float
R
2
288
120
Consumed reactive energy
Float
R
2
290
122
L1 phase – consumed reactive energy
Float
R
2
292
124
L2 phase – consumed reactive energy
Float
R
2
294
126
L3 phase – consumed reactive energy
Float
R
2
296
128
Exported reactive energy
Float
R
2

LE-03MW CT – user manual
16
Register
Feature Type R/W Quantity Settings
Dec
Hex
298
12 A
L1 phase – exported reactive
energy
Float
R
2
300
12C
L2 phase – exported reactive
energy
Float
R
2
302
12E
L3 phase – exported reactive
energy
Float
R
2
304 130 T1 tariff – total active energy Float R 2
Value dependent
on the set calculation
option
(see register 11)
305
132
T1 tariff – consumed active energy
Float
R
2
308
134
T1 tariff – exported active energy
Float
R
2
310 136 T1 tariff – total reactive energy Float R 2
Value dependent
on the set calculation
option
(see register 11)
312
138
T1 tariff – consumed reactive
energy
Float
R
2
314
13 A
T1 tariff – exported reactive
energy
Float
R
2
316 13C T2 tariff – total active energy Float R 2
Value dependent
on the set calculation
option
(see register 11)
318
13E
T2 tariff – consumed active energy
Float
R
2
320
140
T2 tariff – exported active energy
Float
R
2
322
142
T2 tariff – total reactive energy
Float
R
2
324
144
T2 tariff – consumed reactive
energy
Float
R
2
326
146
T2 tariff – exported reactive
energy
Float
R
2
328 148 T3 tariff – total active energy Float R 2
Value dependent
on the set calculation
option

LE-03MW CT – user manual
17
(see register 11)
330
14 A
T3 tariff – consumed active energy
Float
R
2
332
14C
T3 tariff – exported active energy
Float
R
2
334 14E T3 tariff – total reactive energy Float
R 2
Value dependent
on the calculation
option set
(see register 11)
336
150
T3 tariff – consumed reactive
energy
Float
R
2
338
152
T3 tariff – exported reactive
energy
Float
R
2
340 154 T4 tariff – total active energy Float
R 2
Value dependent
on the set calculation
option
(see register 11)
342
156
T4 tariff – consumed active energy
Float
R
2
344
158
T4 tariff – exported active energy
Float
R
2
346 15 A T4 tariff – total reactive energy Float
R 2
Value dependent
on the set calculation
option
(see register 11)
348
15C
T4 tariff – consumed reactive
energy
Float
R
2
350
15E
T4 tariff – exported reactive
energy
Float
R
2

LE-03MW CT – user manual
18
9.2 Current transformer
The current transformer ratio of the meter can be set remotely via the Modbus RTU interface or
locally using the PROG button.
To set it manually:
1) switch off and on the power supply of the meter;
2) press and hold down the PROG button;
3) release the PROG button after about 15 seconds;
4) the display will show a blinking CT value (for example 0005-5); the table of available settings is
shown below;
5) set the desired value of the current transformer ratio by pressing the button to the left or right;
6) wait until the transformer value disappears from the display.
Setting the transformer ratio via the RS485 interface requires the code value corresponding to the
selected current transformer to be written to register number 8.
Please note: The code designation of the transformer is created by writing the value of the
transformer primary current as a BCD number.
Transformer
Code designation
Hexadecimal
Decimal
5/5
0x0005
5
30/ 5(*)
0x0030
48
40/5
0x0040
64
50/5
0x0050
80
60/5
0x0060
96
75/5
0x0075
117
80/ 5(*)
0x0080
128
100/5
0x0100
256
125/5
0x0125
293
150/5
0x0150
336
200/5
0x0200
512
250/5
0x0250
592
300/5
0x0300
768
400/5
0x0400
1024
500/5
0x0500
1280
600/5
0x0600
1536
750/ 5(*)
0x0750
1872
800/5
0x0800
2048
1000/5
0x1000
4096

LE-03MW CT – user manual
19
Transformer
Code designation
Hexadecimal
Decimal
1250/5
0x1250
4688
1500/5
0x1500
5376
2000/5
0x2000
8192
2500/5
0x2500
9472
3000/5
0x3000
12288
4000/5
0x4000
16384
5000/5
0x5000
20480
6000/5
0x6000
24576
7500/5
0x7500
29952
(*) Transformer ratios 30/5, 80/5, 750/5 can only be set via the Modbus RTU interface.
Warning!
For advanced configuration of the LE-03MW CT meter (tariff zones, holidays, etc.) we
recommend the free configuration software LE Config.
Program available for download from the www.fif.com.pl website.

LE-03MW CT – user manual
20
10. Manufacturer warranty
1. The meter is covered by a 24-month warranty from the date of purchase.
2. The warranty valid only with proof of purchase.
3. A warranty claim should be submitted at the point of purchase or directly to the manufacturer:
4. During the warranty period, in the event of a justified complaint, the manufacturer undertakes, in
accordance with consumer rights legislation, to repair the device, replace it with a new one or
refund the payment.
5. Warranty claims will be processed within 14 days of delivery to the service centre.
6. The warranty does not cover:
- mechanical and chemical damage;
- damage caused by improper use or use not in accordance with the user manual instructions;
- post-sale damage resulting from accidents or other events for which the manufacturer, or the point
of sale is not responsible, such as damage during transport. etc.
7. The warranty does not cover activities that according to the instructions should be carried out by
the user, such as installation of the meter, electrical installation, installation of other required
electrical protection, checking etc.
Warning!
Do not make any changes to the unit by yourself. Doing so can result in damage to or improper
operation of the device, which in turn can lead to damage to the controlled device and pose a threat
to people operating it. In such cases, the manufacturer is not responsible for the resulting events and
may refuse the provided warranty in the event of a complaint.