F&F LE-03MW User manual

LE-03MW –user manual
2
Table of contents
1.
PURPOSE ...............................................................................................................................................3
2.
DEVICE CHARACTERISTICS.....................................................................................................................3
3. MEASURED VALUES...............................................................................................................................4
4.
OPERATOR PANEL .................................................................................................................................4
5.
TECHNICAL SPECIFICATIONS .................................................................................................................9
6. COMPLIANCE AND MARKING..............................................................................................................10
7. DIMENSIONS .......................................................................................................................................11
8.
CONNECTION ......................................................................................................................................11
9.
COMMUNICATION PROTOCOL............................................................................................................12
10. MANUFACTURER'S WARRANTY.........................................................................................................16

LE-03MW –user manual
3
1. Purpose
LE-03MW is an electronic bi-directional three-phase electricity meter, compliant with the MID
Directive, designed for direct measurement. The built-in real-time clock allows the measurement of
energy consumption divided into different tariff zones. Communication interfaces: RS-485 with
Modbus RTU protocol and optical port according to EN62056 (IEC1107) enable remote reading and
configuration of the meter.
2. Device characteristics
3-phase bi-directional energy meter;
Direct measurement up to 80 A;
Energy measurement in four tariff zones;
Built-in real-time clock with battery backup for switching tariff zones;
Total and tariff-divided consumption registration:
total active and reactive energy;
active and reactive energy divided into individual quadrants;
8 time schedules dividing the day into tariff zones;
The possibility of settling the energy according to different schedules for working days and
weekend;
The possibility of dividing the year into 8 time periods. In each period the energy (for
working days) can be settled according to a different schedule.
Indication of network parameters (voltage, currents, active power, reactive power,
apparent power, power factor, frequency);
Calculation of power demand for individual tariffs;
Additional, resettable energy consumption meter;
MID compliance;
RS-485 port, Modbus RTU protocol;
Optical communication port in accordance with EN62056 (IEC1107);
2 SO pulse outputs with programmable number of pulses per kWh/kvarh;
Multifunctional LCD display.

LE-03MW –user manual
4
3. Measured values
Active energy consumed and exported;
Inductive and capacitive reactive energy;
Phase voltages;
Phase currents;
Active power (absolute value);
Reactive power (absolute value);
Apparent power;
Power factor (absolute value);
Frequency.
4. Operator panel
Drawing of the front of the device with a screen (visible buttons)

LE-03MW –user manual
5
4.1.
Description of the display elements
Current tariff indicator
Symbol - indicates to which group of parameters the value displayed
in the numeric field is related. It may be a tariff (T1, T2, T3 T4)
or phase (L1, L2, L3) indicator.
Unit of the value shown in the numeric field of the display.
Symbols have the following meaning:
kW - active power
kWh - active energy
kvarh - passive energy
VA and kVA - apparent energy
V - voltage
A –current
The numeric field of the display indicates the value of the frequency.
Data exchange via the communication interface.
Low battery indicator for the internal clock battery.
4.2.
Control elements
Control buttons for changing the displayed value.
The list of displayed parameters is shown in the following table.

LE-03MW –user manual
6
4.3.
Data displayed on the LCD
Page
Parameter
Unit
Symbol
Format
1
Date
XX-XX-XX
2
Time
XX-XX-XX
3
Total active energy consumption
kWh
6+2 000000.00
4
Tariff T1 - active energy
consumption
kWh
T01
6+2 000000.00
5
Tariff T2 - active energy
consumption
kWh
T02
6+2 000000.00
6
Tariff T3 - active energy
consumption
kWh
T03
6+2 000000.00
7
Tariff T4 - active energy
consumption
kWh
T04
6+2 000000.00
8
Total reactive energy consumption
kVarh
6+2 000000.00
9
Tariff T1 - reactive energy
consumption
kVarh
T11
6+2 000000.00
10
Tariff T2 - reactive energy
consumption
kVarh
T12
6+2 000000.00
11
Tariff T3 - reactive energy
consumption
kVarh
T13
6+2 000000.00
12
Tariff T4 - reactive energy
consumption
kVarh
T14
6+2 000000.00
13
L1 –Phase voltage
V
L1
3+1 000.0
14
L2 –Phase voltage;
V
L2
3+1 000.0
15
L3 Phase voltage;
V
L3
3+1 000.0
16
L1 –Phase current;
A
L1
4+2 0000.00
17
L2 –Phase current;
A
L2
4+2 0000.00
18
L3 –Phase current;
A
L3
4+2 0000.00
19
Total active power
kW
5+3 00000.000
20
L1 - active power
kW
L1
5+3 00000.000
21
L2 - active power
kW
L2
5+3 00000.000
22
L3 - active power
kW
L3
5+3 00000.000
23
Total apparent power
kVA
5+3 00000.000
24
L1 - apparent power
kVA
L1
5+3 00000.000
25
L2 - apparent power
kVA
L2
5+3 00000.000
26
L3 - apparent power
kVA
L3
5+3 00000.000
27
Total power factor
1+2 0.00
28
L1 - power factor
L1
1+2 0.00
29
L2 - power factor
L2
1+2 0.00
30
L3 - power factor
L3
1+2 0.00
Warning!
The meter records absolute values of power and power factor.

LE-03MW –user manual
7
Page
Parameter
Unit
Symbol
Format
31
Frequency
Hz
2+2 00.00
32
Tariff T1 - power demand
kW
T-1
6+2 000000.00
33
Tariff T2 - power demand
kW
T-2
6+2 000000.00
34
Tariff T3 - power demand
kW
T-3
6+2 000000.00
35
Tariff T4 - power demand
kW
T-4
6+2 000000.00
36
Resettable energy consumption
meter
kWh
The display can be
reset by holding
down any button
(for approximately
10 s) at the time of
displaying this
parameter
000000.00
37
C11 XYZ
XYZ shows the
presence of
voltage on the
input lines.
0 - no voltage
1 - voltage
X - phase L1
Y - phase L2
Z - phase L3
C 11 111
38
View display time
1-30 s
The time can be
changed using the
control buttons.
While the
parameter is
displayed, press
any button for 10
seconds and then
press the button
to the left or right
to set the desired
value.

LE-03MW –user manual
8
39
Pulse output
1, 10, 100, 1000
S0 1000
40
Measuring mode of total energy
consumption
CodE 01 - total
energy = energy
consumed,
CodE 05 - total
energy = energy
consumed + energy
exported
CodE 09 - total
energy = energy
consumed - energy
exported
CodE 01
41
Meter IR address
0
12345678
42
MODBUS address
0
Id 255
43
Communication rate
1200, 2400,
4800, 9600
bd 9600
44
Software version
V 1.01

LE-03MW –user manual
11
5. Technical Specifications
reference voltage 3×230/400 V
minimum current/base current 0.25/5 A
maximum current 80 A
minimum detection current 0.04 A measured voltage
L-N 100÷289 V AC
L-L 173÷500 V AC
Rated frequency 50 Hz
accuracy of measurement class B
installation 3-phase, 4-wire
overload capacity 30×lmax/10 ms
insulation 4 kV/1 min; 6 kV/1 μs
Own energy consumption of the meter <10 VA; <2 W
counter display range 8 digits
pulse outputs
number of pulse outputs 2
type of pulse outputs OC (open collector)
maximum voltage 30 V DC
maximum current 27 mA
output 1 pulse constant 1, 10, 100, 1000 imp/kWh
output 2 pulse constant 1000 imp/kvar
communication
port RS-485
communication protocol Modbus RTU
transmission rate 1200, 2400, 4800, 9600 bps
parity EVEN
parity bits 2
reading signaling 2×LED
operating temperature -25÷55°C
terminal 2.5 mm² screw terminals
dimensions 76×100×65 mm
(4.5 of the DIN module)
installation on TH-35 rail
ingress protection IP51
insulation protection class Class II
housing self-extinguishing plastic UI94 V-0

LE-03MW –user manual
10
6. Compliance and marking
Directive 2004/22 /EC.
Certificate number: SGS 0120/SGS0306.
The meter is marked with an individual serial number, which makes it possible to identify it
unambiguously. The marking is indelible (laser engraving).
The meter has the option of sealing the input and output terminals, preventing the meter from being
bypassed.
miejsce plombowania osłony - the place where the cover is sealed
osłonki zacisków - terminal covers

LE-03MW –user manual
11
7. Dimensions
8. Connection

LE-03MW –user manual
12
9. Communication protocol
The meter is equipped with an RS-485 interface that supports the Modbus RTU communication
protocol.
Default communication parameters:
Modbus address 1
communication rate 9600 bps
The current communication parameters (Modbus address, baud rate) can be read from the LCD
display.
9.1.
List of registers
Legend:
Table column
Description
Register
The address of the registry that stores the parameter.
Dec - address in decimal form
Hex - address in hexadecimal form
Function
Parameter name
Type
Data recording format:
U16 - 16-bit number without character
U32 - 32-bit number without U32 character
FLOAT - floating-point number stored in ieee 754 format
R/W
Read/write:
R - read-only data
W - write-only data
R/W - read and write data
Quantity
Number of registers holding the parameter
Settings
Range of parameter settings

LE-03MW –user manual
13
Register
Function
Typ
e
R/W
Qua
ntity
Settings
Dec
Hex
0
0
Serial number
U32
R
2
1
1
Modbus address of the meter
U16
R/W
1
1÷247
2
2
Transmission rate
U16
R/W
1
1200, 2400, 4800, 9600
3
3
Software version
Float
R
2
6
6
Hardware version
Float
R
2
9
9
Configuration of the pulse output
Float
R/W
2
1, 10, 100, 1000
11
B
Measuring mode of total energy
consumption
U16
R/W
1
1 - total energy
= consumed energy,
5 - total energy
= consumed energy,
+ energy exported
9 - total energy
= consumed energy
- energy exported
13
D
View display time
U16
R/W
1
1÷30
14
E
L1 - Phase voltage;
Float
R
2
16
10
L2 - Phase voltage;
Float
R
2
18
12
L3 - Phase voltage;
Float
R
2
20
14
Frequency
Float
R
2
22
16
L1 –Phase current;
Float
R
2
24
18
L2 –Phase current
Float
R
2
26
1A
L3 –Phase current
Float
R
2
28
1C
Total active power
Float
R
2
30
1E
L1 phase - active power
Float
R
2
32
20
L2 phase - active power
Float
R
2
34
22
L3 phase - active power
Float
R
2
36
24
Total reactive power
Float
R
2
38
26
L1 phase - reactive power
Float
R
2
40
28
L2 phase - reactive power
Float
R
2
42
2A
L3 phase - reactive power
Float
R
2
44
2C
Total apparent power
Float
R
2

LE-03MW –user manual
14
Register
Function
Type
R/W
Qua
ntity
Settings
Dec
Hex
46
2E
L1 phase - apparent power
Float
R
2
48
30
L2 phase - apparent power
Float
R
2
50
32
L3 phase - apparent power
Float
R
2
52
34
Total power factor
Float
R
2
54
36
L1 phase - power factor
Float
R
2
56
38
L2 phase - power factor
Float
R
2
58
3A
L3 phase - power factor
Float
R
2
60
3C
Time
Float
R/W
2
256
100
Total active energy
Float
R
2
258
102
L1 phase - total active energy
Float
R
2
260
104
L2 phase - total active power
Float
R
2
262
106
L3 phase - total active power
Float
R
2
264
108
Consumed active energy
Float
R
2
266
10A
L1 phase - consumed active energy
Float
R
2
268
10C
L2 phase - consumed active energy
Float
R
2
270
10E
L3 phase - consumed active energy
Float
R
2
272
110
Exported active energy
Float
R
2
274
112
L1 phase - exported active energy
Float
R
2
276
114
L2 phase - exported active energy
Float
R
2
278
116
L3 phase - exported active energy
Float
R
2
280
118
Total reactive energy
Float
R
2
282
11A
L1 phase - reactive energy
Float
R
2
284
11C
L2 phase - reactive energy
Float
R
2
286
11E
L3 phase - reactive energy
Float
R
2
288
120
Consumed reactive energy
Float
R
2
290
122
L1 phase - consumed reactive energy
Float
R
2
292
124
L2 phase - consumed reactive energy
Float
R
2
294
126
L3 phase - consumed reactive energy
Float
R
2
296
128
Exported reactive energy
Float
R
2

LE-03MW –user manual
15
Register
Function
Typ
e
R/W
Qua
ntity
Settings
Dec
Hex
298
12A
L1 phase - exported reactive energy
Float
R
2
300
12C
L2 phase - exported reactive energy
Float
R
2
302
12E
L3 phase - exported reactive energy
Float
R
2
304
130
T1 tariff - total active energy
Float
R
2
305
132
T1 tariff - consumed active energy
Float
R
2
308
134
T1 tariff - exported active energy
Float
R
2
310
136
T1 tariff - total reactive energy
Float
R
2
312
138
T1 tariff - consumed reactive energy
Float
R
2
314
13A
T1 tariff - exported reactive energy
Float
R
2
316
13C
T2 tariff - total active energy
Float
R
2
318
13E
T2 tariff - consumed active energy
Float
R
2
320
140
T2 tariff - exported active energy
Float
R
2
322
142
T2 tariff - total reactive energy
Float
R
2
324
144
T2 tariff - consumed reactive energy
Float
R
2
326
146
T2 tariff - exported reactive energy
Float
R
2
328
148
T3 tariff - total active energy
Float
R
2
330
14A
T3 tariff - consumed active energy
Float
R
2
332
14C
T3 tariff - exported active energy
Float
R
2
334
14E
T3 tariff - total reactive energy
Float
R
2
336
150
T3 tariff - consumed reactive energy
Float
R
2
338
152
T3 tariff - exported reactive energy
Float
R
2
340
154
T4 tariff - total active energy
Float
R
2
342
156
T4 tariff - consumed active energy
Float
R
2
344
158
T4 tariff - exported active energy
Float
R
2
346
15A
T4 tariff - total reactive energy
Float
R
2
348
15C
T4 tariff - consumed reactive energy
Float
R
2
350
15E
T4 tariff - exported reactive energy
Float
R
2

LE-03MW –user manual
16
Warning!
For advanced configuration of the LE-03MW meter (tariff zones, holidays, etc.) we
recommend the free configuration software LE Config Program available for download
from the www.fif.com.pl website.
10. MANUFACTURER'S WARRANTY
Warning!
Do not make any changes to the unit yourself. Doing so can result in damage to or improper
operation of the device, which in turn can lead to damage to the controlled device and pose a threat
to people operating it. In such cases, the manufacturer is not responsible for the resulting events and
may refuse the provided warranty in the event of a complaint.