Faradite FAR-M360-*-VOLF Series User manual

2.5M 3M
6.6M
5.6M
8M
OBSERVATION AREA
2.5M Height - Beam Pattern
3M Height - Beam Pattern
OVERVIEW
MOTION SENSOR 360 - VOLT FREE
The Faradite Motion Sensor 360
- Volt Free is a low prole passive
infrared ceiling mounted motion
sensor. It’s designed for use with
home/building/lighting control
systems that have volt free / dry
contact inputs.
At 2.5M it gives a 5.6M * 6.6M
detection area.
At 3M it gives a ~8M diameter, as
shown below.
The following conditions have to
be met to detect motion:
1.Movement speed: 1.0m/s
2.Target concept is a human body
(Min object size: ~700×250mm)
3. The temperature dierence
between the target and the
surroundings must be greater
than 4
°
C when mounted at 5M
TECHNICAL DATA
Power supply
(consumption)
5V-24V DC @ 24V
(3mA)
Solid state relay -
max load current 80ma
Solid state relay -
on resistance 16 OHMS
Solid state relay -
o-state leakage
current
1uA
Default state Normally open
Ambient
temperature
0-50
°
C
(indoor only)
IP rating IP20
Range (Note 1) 5M
Max mounting
height
3m (for optimal
performance)
Motion output
timeout (see motion
output diagram)
1 second
Mounting hole 35mm (40mm Fire
rated)
Push-t
connector
AWG 20- 24 CAT5 /
CAT6 / CAT7
Standards EN 61000-6-1
EN 61000-6-3
ELECTRICAL CONNECTIONS
It is recommended to use CAT cable
to connect the motion sensor to the
control system. Stranded cable can
be used (20-24 AWG) but please
insert the supplied tool to open the
spring before inserting the wire.
1: Strip the cable back 6mm
2: Push into circular hole
3: To remove the wire insert the
supplied tool or a small screwdriver
in the slot behind the wire
EQUIVALENT CIRCUIT
MOTION OUTPUT
TIMEOUT
1 SECOND
OPEN
CLOSED
- 0V/GND
VOLT FREE RELAY
+ 5V-24V DC
VOLT FREE RELAY
CLOSED DURING
MOTION
(NORMALY OPEN)
Note 1: Please note that the specied range is 5m but under optimal conditions the sensor
might detect movement at a much longer range
Strip back Push in Remove
Pull to remove connector from motion sensor
X
Y
X
Y
FIRE RATING
The stand-alone Motion Sensor 360
- Volt Free is not re rated.
To achieve a 60 minute re rating to
BS 476: Part 21 1987, the optional
Fire IDR must be tted to the
Motion Sensor 360 - Volt Free.
The Fire IDR is an optional extra.
RELAY
NOTE: After applying power, the sensor will calibrate for roughly
8 seconds; during this period no motion will be reported.
FAR-M360-W-VOLF (WHITE) ----- FAR-M360-B-VOLF (BLACK)
X
Y

Directive 2014/30/EU (Electromagnetic Compatibility (EMC))
Directive 2012/19/EU (WEEE)
Directive 2011/65/EU (RoHS)
Harmonised standards: EN 61000-6-1 Immunity for residential, commercial and light-industrial environments
& EN 61000-6-3 Emission standard for residential, commercial and light-industrial environments
INSTALLATION
To install the Faradite Motion
Sensor 360 - Volt Free, cut a 35mm
hole using a suitable hole saw. Fold
the spring clips upwards and push
through the hole. If you are using
the optional Fire IDR to achieve a
60 minute re rating to BS 476: Part
21 1987, then a 40mm hole will be
required.
USE A 35mm
HOLE SAW FOR
INSTALLATION
For further support & datasheets in other languages
please visit: faradite.com
CONNECTION TO LOXONE
Connection to Loxone is simple: connect
one side of the relay to a digital input on the
MiniServer / Extension / Nano DI Tree / Nano
IO Air and the other side to 24V. Simply provide
the 24V supply from the power supply in the
cabinet or the 24V output of a Nano IO Air if
retrotting.
MOUNTING & SAFETY
PRECAUTIONS
1) Do not under any circumstance
use these sensors outside the range
of their ratings shown in the technical
data.
2) Faradite is committed to making
products of the highest quality and
reliability. Nevertheless, all electrical
components are subject to natural
deterioration, and the product
durability will depend on the
operating environment and
conditions of use.
3) Please note that the sensor can
detect heat sources other than the
human body, such as:
a) Small animals
b) Direct sun light, incandescent
lamps, car headlights (even if the heat
source is outside the detection area)
c) Sudden temperature change inside
or around the detection area i.e. hot
or cold winds/drafts or vapour from a
humidier can aect the
performance of the sensor
4) Please note that the sensor will
have diculty sensing the heat
source if it is behind glass, acrylic or
similar materials, as these materials
may not allow a correct transmission
of infrared rays
CONNECTION TO CONTROL4
Connection to Control4 is simple: connect one
side of the relay to the “SIGNAL” input on a contact
closure and the other side of the relay to the 12V
power supply. Simply provide the sensor power
using the +12V and GND outputs of the contact
closure or any other 5V-24V supply. When using a
contact closure the generic motion sensor driver can be used. You might
need to tick the invert tickbox depending on what contact closure you have
connected the sensor to as the sensor is “normally open”.
Janus Technology have written a driver that integrates the Faradite Motion
Sensor 360 - Volt Free with Control4, via a Brainboxes’ I/O device as an
alternative to a contact input. Search for “Faradite Janus Technology driver”
for more info.
CONNECTION TO CRESTRON
Connection to Crestron is simple: connect one
side of the relay to a digital input and the other
side to GND (G) and congure the input as a
dry contact. The sensor can be powered using
any available 5-24V supply.
INSTALLATION GUIDE FOR VARIOUS CONTROLLERS
THE SENSOR CAN ALSO BE USED WITH MANY OTHER SYSTEMS THAT HAVE A VOLT FREE / DRY CONTACT INTERFACE
-GND
VF RELAY
+ 12V DC
VF RELAY
-GND
VF RELAY
+ 5V-24V DC
VF RELAY
5V-24V POWER SUPPLY
-GND
VF RELAY
+ 24V DC
VF RELAY
CONNECTION TO LUTRON
Connection to Lutron is simple: One side
of the relay should be connected to the
“INPUT” of a contact closure input (CCI) and
the other side should be connected to the
“COMMON” of the CCI. Any 5-24V power
supply can be used to power the sensor.
-GND
VF RELAY
+ 5V-24V DC
VF RELAY
5V-24V POWER SUPPLY
SENSITIVITY ADJUSTMENT
The sensor has been designed for optimal sensitivity.
It is not recommended to change the sensitivity
setting unless it is found to be necessary. To adjust
the sensitivity, remove the two screws and turn over
the circuit board. The small potentiometer can be
used to adjust the sensitivity.
This manual suits for next models
3
Other Faradite Accessories manuals
Popular Accessories manuals by other brands

Aventics
Aventics ST4-2P operating instructions

Elenco Electronics
Elenco Electronics LP-700 Specifications

Balluff
Balluff BTL6-Ax1 Series user guide

A&D
A&D AD4329A-DLC instruction manual

Action Sports
Action Sports S001264DC-2 Assembly, Installation, Care, Maintenance, and Use Instructions

Daga
Daga Flexyheat NC Directions for use