
Author – D. Rehe Feb 2020
1.B Minimum Control Input
Connect a 4-20mA signal to terminals 0V (0 volt reference) and I (4-20mA signal input).
Input the minimum Control Signal. I.e 0V, 4mA, or 10K POT to 0 position. depending on
the input required. Default is 4mA, for 4-20mA input control.
Clamp the active output wire using the current clamp. Adjust the BIAS POT on the
PCB control card give the minimum output current to the load. You will know when the
controller is at a minimum when the output current will not go down any further.
If you do not have a current clamp available, measure the output voltage to the load and
adjust until you have the minimum voltage across the load.
2.A Gain Adjustment
Connect a 4-20mA signal to terminals 0V (0 volt reference) and I (4-20mA signal input).
Apply the maximum control signal 10V, 5V, 20mA, or 10K POT position.
2.B Maximum Control Input
1. Adjust the GAIN Potentiometer(POT) on the PCB until the maximum current is
output to the load. you will know when you are at maximum when the current will
not increase further. You should now see the expected load current based on the
number of heating/welding elements. If you do not have access to a current
clamp you can monitor the load voltage instead and it will also stop increasing
like the current. In both cases you should wind the GAIN POT back and forth a
little unit you are confident you are right on the maximum output, no more, no
less.
2. Verify the Bias (Zero) again by changing the input signal back to the minimum
value. You will likely find the Bias has moved slightly, re-adjust as necessary as
in step 1.B.
3. Verify the GAIN adjustment by inputting the maximum control input and following
step 2.B again.
Repeat these two steps for a third time to ensure adequate calibration/tuning.
3. Ramp/Soft Start Adjustment
The RAMP potentiometer(POT) sets the step response of the controller for any change
in the control input signal. Setting Range in the standard controller is between 1 and 20
seconds. Special versions are available which allow faster turn on for special
applications such as spot welding. Check here for list of recorded SP versions made
over the last 30+ years. See here for a list of available SP versions.
To check the response time, input a step change to the control input and measure the
time taken to reach the desired output.
4.A Current Limit
Note: The Output of the controller will not be sinusoidal when the output is limited. We
recommend to only use a True RMS Current Clamp for this procedure