Federal ITD48 Installation instructions

- 1 -
E3788
6/15/2016
INSTALLATION & OPERATIONS INSTRUCTIONS
ITR: Self-Contained & Remote Refrigerated Models
& ITD: Non-Refrigerated Displays
KEEP THIS MANUAL FOR FUTURE REFERENCE
Engineering and technical data are subject to change without notice.
FEDERAL INDUSTRIES 215 FEDERAL AVE Belleville, WI 53508
Toll Free 1(800) 356-4206 WI Phone (608) 424-3331 Fax: (608) 424-3234

- 2 -
CONTENTS
INTRODUCTION.......................................................................................................................................3
WARNING LABELS & SAFETY INSTRUCTIONS..............................................................................4
GENERAL ELECTRICAL & GROUNDING.........................................................................................5
Permanent Connected ......................................................................................................................5
Cord Connected (Option).................................................................................................................5
REFRIGERATION................................................................................................................................. 7-8
Self Contained Models.....................................................................................................................7
Self Contained Refrigeration Operation......................................................................................7
Remote Models ................................................................................................................................8
Remote Refrigeration Operation .................................................................................................8
Remote Refrigeration Instruction................................................................................................8
Condensate Evaporator pan and Pump.............................................................................................8
BASE COMPONENT LAYOUT...............................................................................................................6
Non-Refrigerated Models.................................................................................................................6
Refrigerated Self Contained Models................................................................................................6
Refrigerated Remote Models............................................................................................................6
INSTALLATION INSTRUCTIONS, FLOOR MODELS.......................................................................6
Inspection For Shipping Damage.....................................................................................................5
Locating The Display Case ..............................................................................................................6
Removing Case From Shipping Skid...............................................................................................6
Additional Parts................................................................................................................................6
Cleaning ...........................................................................................................................................6
INSTALLATION INSTRUCTIONS, COUNTER MODELS.................................................................6
Inspection For Shipping Damage.....................................................................................................5
Locating The Display Case ..............................................................................................................6
Removing Case From Shipping Skid...............................................................................................6
Additional Parts................................................................................................................................6
Cleaning ...........................................................................................................................................6
CABINET MOUNTING, COUNTER MODELS.....................................................................................6
ITD Non Refrigerated Models .........................................................................................................6
ITR Refrigerated Self Contained Models.........................................................................................6
ITR Refrigerated Remote Models....................................................................................................6
Additional Parts................................................................................................................................6
Cleaning ...........................................................................................................................................6
COMPARTMENT PANEL REMOVAL............................................................................................ 9-11
Floor Models.............................................................................................................................. 9-10
Counter Models..............................................................................................................................10
END PANEL INSTALLATION & REMOVAL................................................................................ 9-11
SHELVING INSTALLATION & REMOVAL.................................................................................. 9-11
Shelf Brackets & Supports......................................................................................................... 9-10
Glass Shelves .................................................................................................................................11
REAR DOORS REMOVAL............................................................................................................... 12-13
OPERATING INSTRUCTIONS ....................................................................................................... 16-17
Control Description........................................................................................................................16
Using Electronic Control................................................................................................................16
Initial Startup..................................................................................................................................16
Placing Product In Case .................................................................................................................20
MAINTENANCE ......................................................................................................................................21
Cleaning Condenser Coil................................................................................................................22
Top LED Strip Replacement..........................................................................................................21
Shelf LED Replacement.................................................................................................................21

- 3 -
CLEANING INSTRUCTIONS................................................................................................................23
Daily Cleaning................................................................................................................................23
Weekly Cleaning............................................................................................................................24
Weekly Exterior Cleaning..............................................................................................................26
SERVICE...................................................................................................................................................27
Service Information........................................................................................................................28
Pre-Service Checklist.....................................................................................................................28
Electronic Control Operation .........................................................................................................16
SALE & DISPOSAL.................................................................................................................................32
Owner Responsibility.....................................................................................................................32
WIRING DIAGRAMS..............................................................................................................................33
REPLACEMENT PARTS........................................................................................................................35

- 4 -
INTRODUCTION
Thank you for purchasing a Federal Industries display case. This manual contains important instructions for
installing and servicing the Refrigerated Self-Service Merchandisers. A repair parts list and wiring diagram
are also included in the manual. Read all of these documents carefully before installing or servicing your
case.
NOTICE
Read this manual before installing your case. Keep this manual and refer to it before doing any
service on the equipment. Failure to do so could result in personal injury or damage to the case.
NOTICE
Installation and service of the electrical components in the case must be performed by a licensed
electrician.
The portions of this manual covering components contain technical instructions intended only for persons
qualified to perform electrical work.
DANGER
Improper or faulty hookup of electrical components in the case can result in severe injury or death.
All electrical wiring hookups must be done in accordance with all applicable local, regional, or
national standards.
SERIAL NUMBER
Record the model and serial numbers of the case for easy reference. Always refer to both model and serial
numbers in your correspondence regarding the case.
Case Model__________________________ Serial Number______________________
Condensing Unit Model________________ Serial Number______________________
This manual cannot cover every installation, use, or service situation. If you need additional information,
call or write us: WARRANTY/TECHNICAL SERVICE DEPARTMENT
Federal Industries
P.O. Box 290
Belleville, WI 53508
Toll Free (800) 356-4206 / WI Phone (608) 424-3331

- 5 -
WARNING LABELS & SAFETY INSTRUCTIONS
This is the safety-alert symbol. When you see this symbol on your case or in the
manual, be alert to the potential for personal injury or damage to your equipment.
Be sure you understand all safety messages and always follow recommended precautions and safe
operating procedures.
NOTICE TO EMPLOYERS
You must make sure that everyone who installs, uses, or services your case is thoroughly
familiar with all safety information and procedures.
Important safety information is presented in this section and throughout the manual. The
Following signal words are used in the warning and safety messages:
DANGER: Severe injury or death will occur if you ignore the message.
WARNING: Severe injury or death can occur if you ignore the message.
CAUTION: Minor injury or damage to your case can occur if you ignore the message.
NOTICE: This is important installation, operation, or service information. If you ignore the
message, you may damage your case.
The warning and safety labels shown throughout this manual are placed on your Federal
Industries case at the factory. Follow all warning label instructions. If any warning or safety labels
become lost or damaged, call our customer service department at 1(800) 356-4206 for replacements.
This label is located on the back of the display case. This label is located below the display pan.
CAUTION
POWER BEFORE
RISK OF ELECTRIC
SHOCK DISCONNECT
91-12340
SERVICING UNIT.
CAUTION
HAZARDOUS MOVING PARTS
DO NOT OPERATE UNIT WITH
DISPLAY PANS REMOVED.

- 6 -
GENERAL ELECTRICAL & GROUNDING
DANGER:
Improper or faulty hookup of electrical components in the
display case can result in severe injury or death.
SELF CONTAINED
MODEL VOLTAGE PERMANENT CONNECTED AMPS CORD CONNECT AMPS/CORD PLUG
ITR3626 & ITR3634 120V/60H/1PH MIN CIRCUIT AMPACITY 13.9/ MAX FUSE SI E 20 TOTAL AMPS 8.7 / 5-15
ITR4826 & ITR4834 120V/60H/1PH MIN CIRCUIT AMPACITY 16.9/ MAX FUSE SI E 20 TOTAL AMPS 10.7 / 5-15
ITR6026 & ITR6034 120V/60H/1PH MIN CIRCUIT AMPACITY 17.3/ MAX FUSE SI E 20 TOTAL AMPS 11.0 / 5-15
REMOTE
MODEL VOLTAGE PERMANENT CONNECTED AMPS
ITR3626 & ITR3634 120V/60H/1PH
MIN CIRCUIT AMPACITY 15/ MAX FUSE SI E 15
ITR4826 & ITR4834 120V/60H/1PH
MIN CIRCUIT AMPACITY 15/ MAX FUSE SI E 15
ITR6026 & ITR6034 120V/60H/1PH
MIN CIRCUIT AMPACITY 15/ MAX FUSE SI E 15
Permanent Connected
-Only a licensed electrician must perform all case electrical connections.
-All electrical wiring hookups must be done in accordance with all applicable local, regional, or national
electrical standards.
-A separate circuit for each display case is required to prevent other appliances on the same circuit from
overloading the circuit and causing malfunction.
-The electrical service must be grounded upon installation.
-See the electrical data plate located at the rear of the case for proper circuit size and wire ampacity.
-The electrical connection box is accessible from the rear of the case with rear grill removed. See grill
removal section of this manual for grill removal procedure.
Floor Models:
FIELD CONNECTION BOX
FLOOR CONDUIT
CONNECTION .875
O
FLOOR CONDUIT
CONNECTION .875
O
CONDUIT OR
POWER CORD
CONNECTION .875
O
MISC ACCESS HOLE
MISC ACCESS HOLE
REAR BASE PANEL

- 7 -
Counter Models:
FIELD CONNECTION BOX
CONDUIT OR
POWER CORD
CONNECTION .875
O
MISC ACCESS HOLE
MISC ACCESS HOLE
REAR COMPARTMENT PANELS
CONDUIT OR
POWER CORD
CONNECTION .875
O
Cord Connected (OPTION)
-A factory installed optional power cord is properly sized to the amperage requirements of the case. See the
electrical data plate located on the rear exterior of the case for the proper circuit size for each case.
- The cord is factory installed protruding from the rear corner of the case.
-A separate circuit for each display case is required to prevent other appliances on the same circuit from
overloading the circuit and causing malfunction.
CAUTION Risk of Electric Shock. If the cord or plug becomes damaged,
replace only with a cord and plug of the same type".

- 8 -
REFRIGERATION
Self Contained Models Use pressure gauges to set pressure control.
MODEL CHARGE REFRIGERATION
ITR3626 & ITR3634 18 O 1/2HP 3021 BTUH@90F/20F
ITR4826 & ITR4834 20 O 1/2HP 3750 BTUH@90F/20F
ITR6026 & ITR6034 24 O 1/2HP 3750 BTUH@90F/20F
The self-contained models are shipped from the factory with a completely operational 134A refrigeration
system and require no modifications or adjustments upon installation. Case must be installed as per the
installation section of this manual to provide proper condensing air cooling.
Self Contained Refrigeration Operation
The unit temperature is controlled by an electronic control that senses air temperature and turns
refrigeration on off as required to maintain proper temperature.
The electronic control will also sense a frosted coil that requires a shutdown defrost cycle and shuts down
refrigeration until defrost is complete. There are may also a defined number of daily defrosts that will also
shut the refrigeration solenoid to insure a full defrost occurs. The solenoid will remain off until the either
the off time is reached or until the electronic control senses low temperature set point
Remote Models
MODEL REFRIGERANT
REFRIGERATION
PRESSURE CUT
IN PRESSURE CUT 0UT
ITR3626R & ITR3634R
R134A 1/2HP 3021 BTUH@90F/20F 32# 0 #
ITR4826R & ITR4834R
R134A 1/2HP 3750 BTUH@90F/20F 32# 0 #
ITR6026R & ITR6034R
R134A 1/2HP 3750 BTUH@90F/20F 32# 0 #
Use pressure gauges to set pressure control
Remote Refrigeration Operation
The remote models are designed to use134A refrigerant and shipped from the factory with the evaporator
coil, expansion valve, drier filter, sight glass and refrigerant solenoid valve. The required high-low-pressure
control and remote condenser can be provided as a factory option and will be required to be charged with
134a refrigerant after installation.
The unit temperature is controlled by an electronic control that senses air temperature and opens and closes
the refrigerant solenoid valve as required to maintain proper temperature.
Once proper temperature is reached the solenoid valve closes and shuts off the refrigeration flow to the unit
and initiates a pump down cycle. This will allow the remote low pressure switch to open and shut off
remote compressor. The solenoid will remain off until the either the off time is reached or until the
electronic control senses that low temperature set point has been reached.
The electronic control will also sense a frosted coil that requires a shutdown defrost cycle and closes
solenoid until defrost is complete. There are may also a defined number of daily defrosts that will also shut
the refrigeration solenoid to insure a full defrost occurs. The solenoid will remain off until the either the off
time is reached or until the electronic control senses low temperature set point.

- 9 -
Remote Refrigeration Instruction
The condensing unit and pressure control are optionally supplied from the factory for remote location
installation. A remote high low pressure switch must be mounted and wired by the installer. The high low
pressure switch must be wired in series with the compressor power supply as shown in diagram below.
1. Mount condensing unit indoors as close to the remote display case as practical. The refrigeration line
should be as short as possible and must not exceed 30 feet.
2. All refrigeration and/or electrical materials between the condensing unit and display case are to be
supplied by installing contractor.
3. Route properly sized and designed refrigeration lines from the condensing unit to the cabinet.
Horizontal suction lines should be pitched downward towards the condensing unit at least ½” per 10’
run to aid the oil drainage. A “P” trap must be installed in the suction line at the foot of every riser to
insure oil return. Dry nitrogen must be used to flow through tubing while brazing refrigeration lines.
4. Suction line must be insulated the entire length with Armaflex (or equivalent). Do not run liquid line
inside insulation with suction line.
5. The remote high/low-pressure control must be mounted, wired and set pressures by the installer.
6. Leak check condensing unit, cabinet, and all connecting tubing. Cabinet and condensing unit tubing
should be checked to insure no leaks occurred during shipping or from rough handling.
Make certain all refrigeration valves are opened and evacuate system to 500 microns. Charge the
system with refrigerant type specified on the data plates.
REMOTE
HIGH LOW
PRESSURE
CONTROL
LIQUID LINE
SUCTION LINE (INSULATED)
REMOTE
CONDENSING
UNIT
EVAPORATOR
COILS
DISPLAY CASE
EXPANSION
VALVE
HIGH
LOW
LIQUID LINE
SOLENOID VALVE
SIGHT GLASS
DRIER/FILTER
FIELD CONNECTION
HOT
FUSED
POWER
SUPPLY
DEFROST
TERMINATE
PROBE
ELECTRONIC
CONTROL
AIR TEMP. CONTROL PROBE
FUSED
CASE
POWER

- 10
-
Condensate Evaporator Pan and Pump
Condensate Evaporator (Standard Self Contained Models)
NOTICE: During normal defrost cycles, steam from the condensate
evaporator may be visible around the case.
The standard Self Contained case is furnished with an electric condensate evaporator. Plumbing
connections are not required.
The condensate evaporator can be removed from the case and the condensate drain can be plumbed to a
drain to conserve energy if desired. Disconnect the condensate evaporator wires at the condensate
evaporator to remove. This must be done by a qualified electrician.
Make sure that the drain line has not been dislodged during shipment and that the drain trap terminates
properly over the water reservoir.
Condensate Pump (Standard Remote, optional Self Contained)
When unit is shipped with a condensate pump a condensate discharge hose is supplied from factory. This
hose must be run to a nearby drain. When the condensate pan is full the pump will turn on and pump water
out condensate drain hose. Note Drain hose can be run in verticle direction but must not exceed height of
15 feet
Note: There is a piece of cardboard that has to be removed from the side of the pump to free up the
float. If this is not done, the pump will not turn on and the pan will overflow.
NOTICE: This unit could be shipped with an optional condensate pump. The pump has a
float that turns the pump on automatically when needed.
The pump is mounted in the base compartment. The pump should be cleaned and
inspected every 3-4 months.

- 11
-
BASE COMPONENT LAYOUTS
Refrigerated Self Contained Models
Counter ITR36 Self Contained
CONDENSING UNIT
CONDENSATE
EVAPORATOR
OR PUMP
POWER SUPPLY
ELECTRICAL
CONNECTION BOX
ACESS
HOLE 2.75
O
ACESS
HOLE 2.75
O
FILTER DRIER
SIGHT
GLASS
ELECTRICAL
CONNECTION .88
O
17
3
3.7
97
36
30
FRONT TOP VIEW
Counter ITR48 Self Contained
CONDENSING UNIT
CONDENSATE
EVAPORATOR
OR PUMP
POWER SUPPLY
ELECTRICAL
CONNECTION BOX
ACESS
HOLE 2.75
O
ACESS
HOLE 2.75
O
FILTER DRIER
SIGHT
GLASS
ELECTRICAL
CONNECTION .88
O
9
9
17
3.7
3.0
FRONT TOP VIEW
48
30

- 12
-
Counter ITR60 Self Contained
CONDENSING UNIT
CONDENSATE
EVAPORATOR
OR PUMP
POWER SUPPLY
ELECTRICAL
CONNECTION BOX
ACESS
HOLE 2.75
O
ACESS
HOLE 2.75
O
FILTER DRIER
SIGHT
GLASS
ELECTRICAL
CONNECTION .88
O
60
30
3.7
3
11.5
17
9
9
FRONT TOP VIEW
Floor ITR36 Self Contained
CONDENSING UNIT
CONDENSATE
EVAPORATOR
OR PUMP
POWER SUPPLY
ELECTRICAL
CONNECTION BOX
ACESS HOLE
2.75
O
ACESS
HOLE 2.75
O
FILTER DRIER
SIGHT GLASS
ELECTRICAL
CONNECTION .88
O
FRONT TOP VIEW
30.8
36
7
9
17.5
9
3.4
LEG LEVELER PLATES
OR CASTER POCKETS 12

- 13
-
Floor ITR48 Self Contained
CONDENSING UNIT
CONDENSATE
EVAPORATOR
OR PUMP
POWER SUPPLY
ELECTRICAL
CONNECTION BOX
ACESS HOLE
2.75
O
ACESS
HOLE 2.75
O
FILTER DRIER
SIGHT GLASS
ELECTRICAL
CONNECTION .88
O
FRONT TOP VIEW
LEG LEVELER PLATES
OR CASTER POCKETS
48
30.8
17.5
9
9
9.2
3.5
12.0
Floor ITR60 Self Contained
CONDENSING UNIT
CONDENSATE
EVAPORATOR
OR PUMP
POWER SUPPLY
ELECTRICAL
CONNECTION BOX
ACESS HOLE
2.75
O
ACESS
HOLE 2.75
O
FILTER DRIER
SIGHT GLASS
ELECTRICAL
CONNECTION .88
O
FRONT TOP VIEW
LEG LEVELER PLATES
OR CASTER POCKETS
60
30.8
9
17.5
9
12.0

- 14
-
Refrigerated Remote Models
Counter ITR36 Remote
Counter ITR48 Remote

- 15
-
Counter ITR48 Remote
Floor ITR36 Self Remote

- 16
-
Floor ITR48 Remote
Floor ITR60 Remote

- 17
-
INSTALLATION INSTRUCTIONS FLOOR MODELS
Inspection for Shipping Damage
You are responsible for filing all freight claims with the delivering truck line. Inspect all cartons and crates
for damage as soon as they arrive. If damage is noted to shipping crates, cartons, or if a shortage is found,
note this on the bill of lading (all copies) prior to signing.
Locating Display Case
The case must be located where it is not subjected to the direct rays of the sun, heating ducts, grills,
radiator, or ceiling fans, nor should it be located near open doors or main door entrances. Also, avoid
locations where there are excessive air movement or air disturbances.
The case requires a minimum of 36” clearance on side of air intake or air discharge. Do not locate case with
front or back tight against the wall.
No clearance is needed on sides of the unit.
Removing Case From Shipping Skid and General Installation
CAUTION:
Do not push or pull against the top end glass, or
door frames and do not pull on end panels when removing the case
from the skid or moving the case. Case damage or glass breakage will result.
1. Remove crate top and sides and note missing or damaged items as explained in the pre-installation
procedures outlined above.
2. Move the case as near as possible to the final location and before removing it from the shipping skid.
3. Remove the (4) brackets that secure the case to the shipping skid.
4. Prepare cabinet according to instructions in this section that pertain to your model.
5. Lift the case off of skid and into required position. Only lift the case from under the front and rear lips
on base of unit.
6. The case must be level for proper drainage of defrost condensate to the condensate evaporator or pump.
Using the wrench provided level and square the case as needed by adjusting the leg leveler in each
corner of base.
7. The leveled case must be sealed to the floor using a NSF Listed Sealant.
Additional Parts Shipped with Unit.
Remove bubble wrap and packing material for all shelves and panels, brackets, etc. If it is necessary to
remove tape residue from plastic materials, use cleaning compounds recommended in the cleaning section
of this manual. Install panels and shelving as described proper section of this manual.
Cleaning
For initial setup, clean the case as outlined in the “Weekly Cleaning” section of this manual.

- 18
-
INSTALLATION INSTRUCTIONS COUNTER MODELS
Inspection for Shipping Damage
You are responsible for filing all freight claims with the delivering truck line. Inspect all cartons and crates
for damage as soon as they arrive. If damage is noted to shipping crates, cartons, or if a shortage is found,
note this on the bill of lading (all copies) prior to signing.
Locating Display Case
The counter units are designed to be placed on or into the top of a cabinet counter. The cabinet that the case
is to be used with must be located where it is not subjected to the direct rays of the sun, heating ducts,
grills, radiator, or ceiling fans, nor should it be located near open doors or main door entrances. Also,
avoid locations where there are excessive air movement or air disturbances.
The refrigerated cases require special consideration of cabinet design to allow condenser air to enter intake
and discharge from cabinet space. The requirements for specific cases outlined in this section must be
followed. Failure to follow these instructions will void warranty.
Removing Case From Shipping Skid and General Installation
CAUTION:
Do not push or pull against the top end glass, or
door frames and do not pull on end panels when removing the case
from the skid or moving the case. Case damage or glass breakage will result.
2. Remove crate top and sides and note missing or damaged items as explained in the pre-installation
procedures outlined above.
8. Move the case as near as possible to the final location and before removing it from the shipping skid.
9. Remove the (4) brackets that secure the case to the shipping skid.
10. Prepare cabinet according to Cabinet Mounting Counter Models instruction in next section that pertain
to your model.
11. The counter cases are shipped with end glass removed and lifting handles are provided on each side of
case. Using lifting handles lift the case off of skid and into required position. Once case is placed into
position remove lifting handles and install end glass as described in End Glass Installation Section
12. The counter top that the case is being placed on must be level for proper drainage of defrost condensate
to the condensate evaporator or pump.
13. The case must be sealed to the counter using a NSF Listed Sealant.
Additional Parts Shipped with Unit.
Remove bubble wrap and packing material for all shelves and panels, brackets, etc. If it is necessary to
remove tape residue from plastic materials, use cleaning compounds recommended in the cleaning
section of this manual. Install panels and shelving as described proper section of this manual.
Cleaning
For initial setup, clean the case as outlined in the “Weekly Cleaning” section of this manual.

- 19
-
CABINET MOUNTING COUNTER MODELS
ITD Non-Refrigerated Model Mounting
Cabinet Preparation
The ITD models set directly on top of counter. The Case must be attached and sealed to top of counter to
prevent counter from moving. Counter will require (2) 3/8”dia. holes to be drilled through the counter top
surface to attach case to counter. Use the diagram below for hole location.
Place case on to counter and fasten from under cabinet with (2) 10-32 screws and washers provided.
The case must be sealed to the counter using a NSF Listed Sealant.
IMPORTANT: When placing cases in a line up the number of end panels used will be different. The cut
out and hole placement dimension will need to be adjusted for each particular line up circumstance. See
LINE UPS INTALLATION section of this manual.
ITR 36" MOUNTING HOLE CENTERS 33.5"
ITR 48" MOUNTING HOLE CENTERS 45.5"
ITR 60" MOUNTING HOLE CENTERS 57.5"
ITR 36" OUTSIDE OF CASE 36.0"
ITR 48" OUTSIDE OF CASE 48.0"
ITR 60" OUTSIDE OF CASE 60.0"
DRILL 3/8
O
MOUNTING
HOLE THROUGH COUNTER
DRILL 3/8
O
MOUNTING
HOLE THROUGH COUNTER
FRONT
TOP VIEW 30.0
OUTSIDE
OF CASE
15.0
MOUNTING HOLE
CASE CENTER

- 20
-
ITR Refrigerated Self Contained Models
Cabinet Preparation
The ITR Self Contained models have a large condenser compartment hanging from the bottom of case that
contains the condenser and condensate evaporator unit. This compartment hangs inside the cabinet
compartment. The interior of the cabinet must be open to allow space for this compartment.
Cabinet Cutout
The countertop must be cut to allow the case’s base and condenser compartment to drop into the cabinet
interior. Use the diagram below for cutout dimensions.
IMPORTANT: When placing cases in a line up the number of end panels used will be different. The cut
out and hole placement dimension will need to be adjusted for each particular line up circumstance. See
LINE UP INTALLATION section of this manual.
27.37
2.00" TO 3.5" REF FROM TOP
CUT OUT TO BACK OF DOOR
ITR 48" WIDE 45.5"
ITR 60" WIDE 57.5"
TOP CUT OUT
GRILL CUT OUTS
C
L
FRONT
BACK
BACK
3.00 MAX
FROM TOP TO
DOOR CUT OUT
14.0
10.5 10.5
14.0
4.25 FROM TOP OF
COUNTER TO TOP OF
GRILL CUTOUT
6.7 6.7
GRILL CUT OUTS
L
BACK
3.00 MAX
FROM TOP TO
DOOR CUT OUT
9.6
10.5
4.25 FROM TOP OF
COUNTER TO TOP OF
GRILL CUTOUT
9.6
10.5
5.2
5.2
C
ITR 36" WIDE 33.5"
27.37
2.00" TO 3.5" REF FROM TOP
CUT OUT TO BACK OF DOOR
TOP CUT OUT
FRONT
BACK
CENTER TOP CUTOUT
WITH CENTER OF REAR DOORS
CENTER TOP CUTOUT
WITH CENTER OF REAR DOORS
This manual suits for next models
16
Table of contents
Other Federal Display Case manuals

Federal
Federal CRR4828 Installation instructions

Federal
Federal ECGR50 Installation instructions

Federal
Federal FCC-4 Installation instructions

Federal
Federal SNR482C-2 User manual

Federal
Federal SN48 Installation instructions

Federal
Federal RSSM360 Installation instructions

Federal
Federal SNR48 Installation instructions