Fema S40-T User manual

Series S40
Panel meter 72x36mm size
Panel meter for Pt100/RTD (2 and 3 wires), and thermocouples J, K, T, E, S,
R, N, C, L and X with temperature display in degrees celsius (ºC) or fahrenheit
(ºF). Selectable Pt100/RTD resolution at 1º or 0.1º, and manual offset available.
Thermocouple measure with internal CJC selectable (enabled or disabled).
Selectable behavior in case of sensor break (‘to_high’ or ‘to_low’). Reduced
housing 72x36mm DIN standard. Display in 4 digits and negative sign. Maximum
and minimum display memory, steps, alarms with single or double setpoints, 5
levels of brightness, ... Universal AC and DC power modules and up to 2 modules
for signal retransmission and control.
Model S40-T for Pt100 / RTD
for Thermocouples
Panel Meters
FEMA ELECTRÓNICA
USER’S MANUAL
(2264R00)

User’s Manual S40-T
FEMA ELECTRÓNICA - Page 2
Meter S40-T
Panel meter 72x36mm size for Pt100/RTD and Thermocouples
Panel meter for temperature signals, accepts Pt100/RTD with
2 and 3 wires, and thermocouples J, K, T, E, S, R, N, C, L and
X. Temperature display in degrees celsius (ºC) or fahrenheit
(ºF). Thermocouple cold junction compensation selectable.
Manual offset selectable. Selectable behavior for alarms in
case of sensor break (‘to_high’ or ‘to_low’).
Instrument with small 72x36mm standard DIN size. Resolu-
tion 4 digits and negative sign.
Management for up to 4 alarms with 1 or 2 setpoints each
alarm, with hysteresis and delays. Provides memory for maxi-
mum and minimum, display on selectable steps, password
and selectable levels of brightness.
Power options with universal AC and DC ranges, and space
for two additional control and/or signal retransmission mod-
ules.
Standard IP54 front protection, with optional upgrade to IP65
protection.
Connections via plug-in screw terminals and conguration
via three front push-buttons. For application on industrial
environments.
This instrument has been designed and veried according to the 61010-1
CE security regulation, and is designed for applications on industrial environ-
ments. See the “CE Declaration of Conformity” further in this document for
information on the category of measure and the degree of pollution levels
that apply.
Installation of this instrument must be performed by qualied personnel
only. This manual contains the appropriate information for the installation.
Using the instrument in ways not specied by the manufacturer may lead
to a reduction on the specied protection level. Disconnect the instrument
from power before starting any maintenance and / or installation action.
Risk of electrical shock. Instrument terminals can be connected
to dangerous voltage.
Instrument protected with double isolation. No earth connection
required.
The instrument does not have a general switch and will start operation as
soon as power is connected. The instrument does not have protection fuse,
the fuse must be added during installation.
The instrument is designed to be panel mounted. An appropriate ventilation
of the instrument must be assured. Do not expose the instrument to excess
of humidity. Maintain clean by using a humid rag and do NOT use abrasive
products such as alcohols, solvents, etc.
General recommendations for electrical installations apply, and for proper
functionality we recommend : if possible, install the instrument far from
electrical noise or magnetic eld generators such as power relays, electri-
cal motors, speed variators, ... If possible, do not install along the same
conduits power cables (power, motor controllers, electrovalves, ...) together
with signal and/or control cables.
Before proceeding to the power connection, verify that the voltage level
available matches the power levels indicated in the label on the instrument.
In case of re, disconnect the instrument from the power line, re alarm
according to local rules, disconnect the air conditioning, attack re with
carbonic snow, never with water.
Instrument is in conformity with CE rules and regulations. See
“CE Declaration of Conformity” further in this document.
S40 TH
Model Power
-H (85-265 Vac/dc)
-L (11-60 Vdc
and 24/48 Vac)
-- - ---
Option1
-R1 (1 relay)
-AO (Analogue Output)
-(empty)
----
Others
-65 (IP65)
-(empty)
---
Option2
-R1 (1 relay)
-AO (Analogue Output)
-(empty)
-
Order Reference
Precautions on installation

User’s Manual S40-T
User’s Manual S40-T
FEMA ELECTRÓNICA - Page 3
Button
UP
Logo
Alarms
Units
PowerSignal
Option1 Option2
Button
SQ
Button
LE
Front View
Rear View
Earth connection - Although a terminal is offered for earth connection, the
connection is optional. The instrument does not need this connection for
correct functioning nor for compliance with the security regulations.
Fuse - To comply with security regulation 61010-1, add to the power line
a protection fuse acting as disconnection element, easily accessible to the
operator and identied as a protection device.
Power “H” fuse 250mA time-lag
Power “L” fuse 400mA time-lag
67890
~
~
Power Connections
Input signal connections - Pt100/RTD
12345
RTD/Pt100
2 wires
12345
RTD/Pt100
3 wires
Measure can be selected for 2 or 3 wire systems.
Select input Pt100 2Wires in the
menu. Terminal 2 can be left un-
connected.
Select input Pt100 3Wires in the
menu
Input signal connections - Thermocouple
12345
+Thermocouple
-
To congure, select the appropriate thermocouple type in the
conguration menu.
+
-

User’s Manual S40-T
FEMA ELECTRÓNICA - Page 4
Type Range ºC Max. error
at 25ºC* Range ºF Offset drift Span drift*
*includes offset drift
Pt100/RTD 800 /-200 ºC <0.2ºC 1562 /-328 ºF 0.05º/ºC 0.10º/ºC
Thermocouple J 1200 /-200 ºC <2ºC 2192 /-328 ºF 0.05º/ºC 0.20º/ºC
Thermocouple K 1372 /-200 ºC <2ºC 2372 /-328 ºF 0.05º/ºC 0.20º/ºC
Thermocouple T 400 /-200 ºC <2ºC 752 /-328 ºF 0.02º/ºC 0.02º/ºC
Thermocouple E 1000 /-200 ºC <2ºC 1832 /-328 ºF 0.05º/ºC 0.20º/ºC
Thermocouple S 1768 /-50 ºC <4ºC 2282 /-58 ºF 0.20º/ºC 0.20º/ºC
Thermocouple R 1600 /-50 ºC <4ºC 2912 /-58 ºF 0.20º/ºC 0.20º/ºC
Thermocouple N 1300 /-200 ºC <2ºC 2372 /-328 ºF 0.05º/ºC 0.20º/ºC
Thermocouple C 2320 /0ºC <2ºC 4192 /32 ºF 0.02º/ºC 0.02º/ºC
Thermocouple L 900 /-200 ºC <2ºC 1652 /-328 ºF 0.05º/ºC 0.20º/ºC
Thermocouple X 4000 /-200 ºC <2ºC 7232 /-328 ºF 0.02º/ºC 0.02º/ºC
Table 3 - Thermocouple and PT100/RTD specications
Technical Data
Digits 4
Type 7 segments, red
Height 14 mm
Display maximum 9999
Display minimum -1999
Decimal point selectable 8.8.8.8.
Overrange 9999 ashing
Underrange -1999 ashing
Signals accepted Pt100/RTD and Thermocouples
Temperature scale ITS90
Display units ºC or ºF, selectable
Thermocouple data
Thermocouples acceptedJ, K, T, E, S, R, N, C, L, X
(Thermocouple X is a linear 10uV/ºC signal)
Resolution 1º
Ranges see table 3
Max. error at 25ºC see table 3
Offset drift see table 3
Span drift* see table 3
*Note - span drift includes also the offset drift
CJC automatic (“On”/“Off” selectable)
CJC accuracy <1.0ºC
CJC thermal drift <0.04º/ºC
On sensor break “to_high” or “to_low”, selectable
Acquisitions 3 acquisitions / second
Pt100/RTD data
Sensors accepted 2 or 3 wire, selectable
Resolution 1º or 0.1º, selectable
Ranges see table 3
Alpha Alpha385 or Alpha390, selectable
Max. error at 25ºC see table 3
Offset drift see table 3
Span drift * see table 3
*Note - span drift includes also the offset drift
Cable compensation up to 14 Ohm
Compensation accuracy <0.02ºC / Ohm
Acquisitions 4 acquisitions / second
Power
Power “H” 85 to 265 Vac/dc
Power “L” 11 to 60 Vdc and 24/48Vac
Consumption <4W
Isolation 3500Veff for power “H”
2000Veff for power “L”
all levels tested for 60 seconds
Conguration 3 frontal push buttons
Functions available
Steps yes, congurable
Memory of maximum yes
Memory of minimum yes
Password yes, congurable
Double setpoints yes
Brightness control yes, 5 levels
Options maximum 2
Mechanical
Mounting panel
Connections plug-in screw terminals
Weight <150 grams
Housing materials ABS, polycarbonate, vergaex
Front size 72x36mm
Panel cut-out 69x32.5mm
Deep from panel 98mm (including terminal)
Protection IP54 standard
IP65 optional (Front sealed. Open-
ing the front breaks the seal)
Temperature Operation 0 to 50ºC
Temperature Storage –20 to +70ºC
Warm-up 15 minutes
Technical Data (cont.)

User’s Manual S40-T
User’s Manual S40-T
FEMA ELECTRÓNICA - Page 5
Information Menu
To enter the “Information Menu” press the SQ button. The
“Information Menu” allows to visualize information and does
not allow to modify the conguration of the instrument. It is
not affected by the “PASSWord” function. During operation
with the “Information Menu”, alarms remain “frozen” and are
kept on-hold. Leaving the “Information Menu” returns to the
measuring state of the instrument, without restart.
Information Menu Tree - See page 5.
Rollback - After 30 seconds without interaction from the
operator, the instrument leaves the “Information Menu”.
Button SQ - Selects the visible option.
Button UP - Moves vertically along the available menu op-
tions.
Button LE - Leaves selected menu or leaves the “Informa-
tion Menu”.
Operating the Information Menu
36
8
32,5
Mechanical Dimensions (mm)
72 18 80
69
Panel
cut-out
Conguration (Conf) - Information on the congured input
sensor and the degrees selected.
Maximum (MAX) - Value of the maximum display.
Minimum (MIn) - Value of the minimum display.
AlarmX (ALX) - Conguration of alarm X. The sequence of
information shows if the alarm is being managed (“On/Off”),
the alarm type (“Max/Min”), the setpoint, the hysteresis value,
the activation delay and the value of setpoint2 (“Off” or the
setpoint2 value).
OptionX (OptX) - Type of module installed. If there is no
module shows “nonE”.
Information Menu Description
Conguration
See menu for Alarm1
See menu for Alarm1
See menu for Alarm1
Alarm1
Maximum
Minimum
Memory of minimum
Option1
Option installed
Option2
Option installed
ºC or ºF
Memory of maximum
“On / Off”
“Max” / “Min”
Setpoint
Hysteresis
Delay
Setpoint2
Counts
Seconds
Second
setpoint
Sensor type

User’s Manual S40-T
FEMA ELECTRÓNICA - Page 6
Conguration Menu
Operating the Conguration Menu
To enter the “Conguration Menu” press the SQ button. The
“Conguration Menu” allows to change the conguration of
the instrument. Access to the “Conguration Menu” can be
password protected with the function “PASSWord”. During
operation with the “Conguration Menu” the alarms remain
“frozen” and are kept on-hold. When leaving the “Congura-
tion Menu” the instrument performs a restart, and new con-
guration is applied. During the restart of the instrument a
short alarm deactivation is performed.
Conguration Menu Tree - See page 6 and 7.
Description of Conguration Menu functions - See page
8 and 9.
Rollback - After 30 seconds without interaction from the
operator, the instrument leaves the “Conguration Menu”,
discarding all changes.
Button SQ - Moves horizontally on the menu. Allows selec-
tion of the current option displayed. During a value selection
menu (for example a setpoint value) validates the value on
display.
Button UP - Moves vertically on the menu. Displays the
available menu options. During a value selection menu (for
example a setpoint value) increases digit value from 0 to 1,
2, 3, 4, 5, 6, 7, 8, 9.
Button LE - Leaves the current menu. Pressing LE several
times will leave all menus and leave the “Conguration Menu”
tree. During a value selection menu (for example a setpoint
value) allows to select each digit for modication with the
UP button.
Reset - Leaving the “Conguration Menu” forces a restart of
the instrument, even in case of no changes in conguration.
Input
Pt100/RTD 2 wires
Pt100/RTD 3 wires
Thermocouple J
Thermocouple K
Thermocouple E
Thermocouple S
Thermocouple T
Temp. Cong,
Offset
Pt100/RTD res..
Offset counts
to add
Degrees
Thermoc. CJC
On break
Thermocouple R
Thermocouple C
Thermocouple L
Thermocouple N
Celsius
Fahrenheit
1º Resolution
0.1º Resolution
Reading to high
Reading to low
Thermocouple X
Alpha

User’s Manual S40-T
User’s Manual S40-T
FEMA ELECTRÓNICA - Page 7
Conguration Menu
Sensor Pt100 2Wire
Degrees ºC
Resolution 0.1º
Offset 0
On Break To high
Alpha 385
Alarms 1,2,3 and 4
Active Off (not managed)
Type maximum
Setpoint 1000
Hysteresis 0 counts
Delay 0.0 seconds
Setpoint2 Off
Display
Steps Off
Memory of maximum -9999
Memory of minimum 9999
Tools
Password Off
Brightness 3
Default factory conguration
See menu for Alarm1
See menu for Alarm1
See menu for Alarm1
Alarm1
Setpoint
Hysteresis
Delay
Active = On
Inactive = Off
Max=Maximum
Min= Minimum
Alarm
management
Alarm as max.
Alarm as min.
Counts
Seconds
Alarms
Setpoint2 Second setpoint
Display Steps
Counts for step
Tools
Option1
Conguration for Option1
Password
Version
Select password
Firmware version
Factory Default Resets to factory de-
fault values
Minimum brightness
Brightness
Maximum brightness
Default brightness
Option2
Conguration for Option2
Maximum
Minimum
Memory of maxim.
Reset of maxim.
Memory of minim.
Reset of minim.

User’s Manual S40-T
FEMA ELECTRÓNICA - Page 8
Input Menu
The input menu selects the input signal range. Options avail-
able are Pt100/RTD 2 or 3 wires, and thermocouples J, K, T,
E, S, R, N, C, L and X.
Note - Thermocouple X is a linear signal at 10uV/ºC.
The instrument manages up to 4 alarms. Each alarm is
controlled by the condition “display higher (or lower) than
the congured setpoint”. The front leds are controlled by
the activation / deactivation of the related alarm. The relays
installed on Option1 and/or Option2 are controlled by Alarm1
and Alarm2.
Active (Act) - Value “On/Off”. Denes if the instrument has to
manage this alarm or not. Select “Off” for alarm not managed.
Type (tyPE) - Value “Max/Min”. Denes the behavior of the
alarm as maximum or minimum alarm. The alarms cong-
ured as maximum are activated when the display value is
equal or higher than the setpoint. The alarms congured as
maximum are deactivated when the display is lower than
the setpoint. The alarms congured as minimum have the
inverse behavior.
Setpoint (SEt) - Value from “9999” to “-1999”.Alarm set point.
Hysteresis (hySt) - Value from “0” to “9999”. Points of hyster-
esis. The hysteresis applies on the deactivation of the alarm.
Delay (dEL) - Value from “0.0” to “99.9” seconds. Delay to be
applied to the relay activation and deactivation. Relays are
activated and deactivated X seconds after the activation /
deactivation of the alarm. The delay affects only to the relays.
The delay does not affect to the front leds.
Setpoint2 (SEt2) - Value from “-1999” to “9999”. Second
setpoint. The second setpoint allows for the creation of acti-
vation windows. If the alarm is congured as maximum with
setpoint 1000 and setpoint2 is congured at 1500, the alarm
will be activated between 1000 and 1500 and the alarm will
be deactivated when display is <1000 and >1500. Setpoint2
is affected on the same way as the setpoint with hysteresis
and delays.
Display Menu
Functions on this menu allow for conguration of the visu-
alization.
Steps (StEP) - Display changes on predened steps. Values
are 1, 2, 5, 10, 20 and 50. The display is made in steps of X
counts. For example, select a step of 20 will make the display
to change in steps of 20 (1420, 1440, 1460, ...).
Maximum (MAX) - Memory of maximum display. Indicates
the maximum value of display since the last reset of the
memory. Memory is reset on the following cases : manual
reset from the Conguration Menu (Maximum), change on
the input signal (Input), modication on the scaling (Scaling),
change on the decimal point (dP), modication of the linear-
ization segments, or instrument power-down.
Minimum (MIn) - Memory of minimum display. Indicates the
minimum value of display since the last reset of the memory.
Memory is reset on the following cases : manual reset from
the Conguration Menu (minimum), change on the input
signal (Input), modication on the scaling (Scaling), change
on the decimal point (dP), modication of the linearization
segments, or instrument power-down.
AlarmX Menu
Temperature Conguration Menu
The temperature conguration menu sets the function param-
eters for Pt100/RTD and thermocouple sensors.
Degrees (dEG) - Value “ºC/ºF”. Select the temperature to be
displayed in celsius or fahrenheit degrees.
Pt100/RTD resolution (P.rES) - Value “1º/0.1º”. Resolution
for the Pt100/RTD. Select to display with degree or tenth of
degree resolution.
Offset (oFFS) - Value from “-1999” to “9999” counts. Offset
to be added to the reading. Both for Pt100/RTD and ther-
mocouples.
Thermocouple Cold Junction Compensation (t.cJc) - Val-
ue “On/Off”. Select “On” for automatic CJC compensation in
the instrument. Select “Off” to disable the CJC compensation.
On break (on.bk) - Value “to_h/to_l”. Select “To L” to make
the reading go to minimum, in case of probe broken. Select
“To H” to make the reading go to maximum in case of probe
broken.
Alpha (ALPh) - Value “385/390”. Select “385” or “390” ac-
cording to your PT100/RTD sensor.

User’s Manual S40-T
User’s Manual S40-T
FEMA ELECTRÓNICA - Page 9
Password (Pass) - Select a number to act as password. This
password will be requested when entering the Conguration
Menu. To deactivate the password select “Off”.
Factory Settings (Fact) - Factory default conguration. Se-
lect “yES” to activate the factory default conguration.
Version (Ver) - Firmware version installed.
Light (Ligh) - Luminosity. Select between 5 predened levels
of luminosity.
Tools Menu
Menu options OPT1 and OPT2 give access to the congura-
tion menus of the installed options. The menu depends on the
installed option. If there is no option installed the instrument
shows “nonE”.
Options Menu
When the instrument detects that the displayed value does
not correspond to the input value, the display will ash and
alternate with a message.
“h.udr” Hardware underrange. The thermocouple signal is
lower than minimum readable signal (-30mV).
“h.oVr” Hardware overrange. The thermocouple signal is
higher than maximum readable signal (80mV).
“d.udr” Display underrange. The Pt100/RTD is shortcir-
cuited.
“hoLd” The instrument is showing the value present when
the hold function was activated. Hold function is active.
“Min” The instrument displays the minimum displayed
value in memory. The minimum visualization is active.
“MAX” The instrument displays the maximum displayed
value in memory. The maximum visualization is active.
“brk” The instrument displays “brk” with either “9999” or
“-9999” when : 1) resistance measured is higher than 390
Ohms (higher than 850ºC for PT100/RTD measure), or 2) in
case the third wire ohm is higher than 15 Ohm, or 3) thermo-
couple measure is open circuit.
Err.1 Password incorrect.
Err.2 The instrument has detected an installed option but
was unable to communicate.
Messages and errors
THIS SECTION BLANK

User’s Manual S40-T
FEMA ELECTRÓNICA - Page 10
Relay type 3 contacts (Com, NC, NO)
Maximum current 8A (resistive load)
Voltage 250 Vac continuously
Instalable in Option1 and/or Option2
A B C D E
Common
NC
NO
K L M N
F G H I J
Common
NC
NO
O P Q R
Connections for Option1 Connections for Option2
Manufacturer FEMA ELECTRÓNICA, S.A.
Altimira 14 - Pol. Ind. Santiga
E08210 - Barberà del Vallès
BARCELONA - SPAIN
Products - S40-T
The manufacturer declares that the instruments indicated
comply with the directives and rules indicated below.
Directive of electromagnetic compatibility 2004/108/CEE
Directive of low voltage 73/23/CEE
Security rules 61010-1
Equipment “Fixed”
“Permanently connected”
Pollution degree 1 and 2 (without condensation)
Isolation Double
Emission rules
61000-6-4 Generic rule of emission
Immunity rules
61000-6-2 Generic rules of immunity
61000-4-2 By contact ±4KV - Criteria B
On air ±8KV - Criteria B
61000-4-3 Criteria A
61000-4-4 On AC power lines: ±2KV - Criteria B
On DC power lines: ±2KV - Criteria B
On signal lines : ±1KV - Criteria B
61000-4-5 Between AC power lines ±1KV - Criteria B
Between DC power lines ±0.5KV - Criteria B
61000-4-6 Criteria A
61000-4-8 30A/m at 50Hz - Criteria A
61000-4-11 0% 1 cycle Criteria A
40% 10 cycle Criteria B
70% 25 cycle Criteria B
0% 250 cycle Criteria B
Barberà del Vallès November 2011
Daniel Juncà - Quality Manager
All instruments are warranted against all manufacturing
defects for a period of 24 MONTHS from the shipment date.
This warranty does not apply in case of misuse, accident or
manipulation by non-authorized personnel. In case of mal-
function get in contact with your local provider to arrange for
repair. Within the warranty period and after examination by
the manufacturer, the unit will be repaired or substituted when
found to be defective. The scope of this warranty is limited to
the repair cost of the instrument, not being the manufacturer
eligible for responsibility on additional damages or costs. .
You may need to access the inside of the instrument to insert
additional options. Use a at screwdriver to unlock the upper
clips marked with “A”. Then unlock the lower clips marked
with “B” and move out the front lter. Let the inside of the
instrument slide out of the housing.
To reinsert the instrument make sure that all modules are
correctly connected to the pins on the display module. Place
all the set into the housing, assuring that the modules cor-
rectly t into the internal guiding slides of the housing. Once
introduced, place again the front lter by clipping rst the
upper clips “A” and then the lower clips “B”.
Important - If your instrument was delivered with the IP65 front
seal option, accessing the inside of the instrument will perma-
nently break the IP65 seal on the areas of clips “A” and “B”.
A
B
Option R1 - 1 relay
Warranty
CE Declaration of Conformity
Accessing the instrument

User’s Manual S40-T
User’s Manual S40-T
FEMA ELECTRÓNICA - Page 11
THIS PAGE BLANK

Large Displays
60&100mm digit
Signal Converters
& Isolators
Panel Meters
Standard 96x48mm
other products
ELECTRONIC INSTRUMENTATION FOR INDUSTRY
www.fema.es
FEMA ELECTRÓNICA, S.A.
Altimira 14 - Pol. Ind. Santiga
E08210 Barberà del Vallès
BARCELONA - SPAIN
Tel. (+34) 93.729.6004 - www.fema.es
Panel Meters
Standard 96x48mm
Panel Meters
Miniature 48x24mm
Panel Meters
Small 72x36mm
Table of contents
Popular Control Unit manuals by other brands

Wilo
Wilo Wilo-Star-Z 20/1 Installation and maintenance instructions

WellMark
WellMark 2001NB Series Installation, operation & maintenance instructions

PR
PR 9410 manual

TEM
TEM VS 5500 plus operating manual

Yale
Yale Real Living ZigBee Module Installation and programming instructions

Landis+Gyr
Landis+Gyr E65C user manual