Fenwal Controls FC1 Administrator Guide

1
Page
Control Unit
FC1
Operation Instruction Manual
Thank you for purchasing this product.
In this manual, we have shown the important notice in order for you to use the
device just and the method of handling this system.
In addition to you read this manual well before the utilization, understanding
well, and use.
A
fter you read, in the place where it is seen with anytime, please be sure to
keep.
ES0911 K5

730110 K0
2
ES0911
Page
Table of contents
1. Safety instructions.................................................................... 3
2. Installation........................................................................... 5
2.2. Installation of control unit...................................................... 6
2.3. Installation of detector.......................................................... 7
2.4. Wiring............................................................................ 8
3. Starting the system.................................................................... 9
3.2. Control unit..................................................................... 10
3.3. Dimensions....................................................................... 16
3.4. Electric specifications.......................................................... 17
3.5. Environmental specifications..................................................... 19
3.6. Mechanical specifications........................................................ 19
4. Procedures/steps to be taken in the event of alarm occurrence ......................... 20
4.1. Alarm............................................................................ 20
4.2. Zone Alarm...................................................................... 20
5. Indication of the time of trouble..................................................... 21
6. Procedures/steps to be taken in the event of trouble occurrence ....................... 22
7. Detector.............................................................................. 23
7.1. Connectable detector............................................................. 23
8. Serial communication facility......................................................... 24
9. Maintenance and Inspection............................................................ 25
9.1. Daily Inspection................................................................. 25
9.2. Periodically Inspection.......................................................... 26
9.3. Functional Inspection............................................................ 28
10. Disposal............................................................................ 30
11. Support............................................................................. 30

730110 K0
3
ES0911
Page
1
11
1.
Safety instructions
Safety instructionsSafety instructions
Safety instructions
・ Before the using, read this chapter and use correctly.
・ The contents which it occurs when you handle erroneously are divided in two of “warning”
and “caution”. This division states clearly the size and impendence of the harm and the
damage.
・ Please keep below rules for safety.
!
!!
!
Warning
・Do not disassemble a control unit. It causes trouble.
・Do not remove a control unit and detector, Fire can not detect.
・
Do not use a control unit which has impacted. And also do not paint
a control unit.
・
Do not soak a control unit in water, and do not put a control unit
into water. It causes electric shock.
・
Do not use the method that not listed in this manual, It causes
trouble.
Caution
!
!!
!
・
This system only tells the outbreak of a fire. This system is not
Fire prevention systems. And Fire extinguishing system.
・
Do not use at the place where it exceeds environmental
specification. It causes trouble.
The Warning symbol is
used to indicate situations and conditions that
can cause operator serious injury and/or equipment damage.
The Caution symbol is
used to indicate situations and conditions that
can cause operator injury and/or equipment damage.
!
!!
!
Warning
Caution
!
!!
!

730110 K0
4
ES0911
Page
・ A term of a guarantee and a guarantee range
【A term of a guarantee】
In regard to the guarantee of this product, the designated payment of the order main thing
after the paying 1 years you guarantee first only the breakdown which occurs in the normal
busy condition which you follow the instruction manual.
【guarantee range】
In regard to the breakdown which it occurs in this product with the criticism of payment
person side during the above-mentioned guarantee period, it does returns repair in the
responsibility of payment person side. However, when it corresponds next, you exclude from
the object of this guarantee.
① Fire, earthquake and the damage by wind and flood, breakdown and the loss by the
thunderbolt and other natural disasters etc.
② After the shipping, transporting and moving and falling etc at your corporation,
breakdown and the loss with inadequate handling.
③ When cause of breakdown due to the reason other than the payment item.
④ Error in regard to use of the consumer, breakdown and the loss with repairing,
remodeling other than our company and error connecting.
⑤ In case of life of the relay part by wearing and depositing of the relay contact.
Furthermore, the guarantee referred to here being something which means the guarantee of
the payment item single unit, pardons the damage which is induced by the breakdown of the
payment item.

730110 K0
5
ES0911
Page
2
22
2.
I
II
Installation
nstallationnstallation
nstallation
2.1.1. System configuration & Connection
This control unit receives the information of warning or breakdown from the detector which
is connected. In addition, it is the equipment which informs outside with the indication
LED and the warning buzzer and the signal contact.
① Control unit : Control unit communicates with the detector,
Control unit controls the indicating LED and 7seg. LED and
the buzzer and signal contact according to the state of the
detector and itself.
FC1-DY:DIN rail mount type
FC1-HY:Surface mount type
② Communication line : It is the line which shares the power supply and the
communication line of the detector.
③ Detector : The connectable detector is shown with the 7th section.
2.1.2. Power Supply
Power supply of the control unit is DC24V±10%.
・
Please prepare for the control unit exclusive power supply as much
as possible.
・Please reduce the electrical noises on power supply.(Bellow 1Vp-p)
・If necessary, attach a proper noise filter to the power supply line.
Caution
!
!!
!

730110 K0
6
ES0911
Page
2.2. Installation of control unit
2.2.1. FC1-DY
FC1-DY is DIN rail mount type.
Loosen the screw of the metallic parts for the installation of 2 places which are on the
side of control unit itself. And put the control unit to the fixed 35mm width DIN rail.
Tighten the screw in the specified torque range. Please ensure that equipment installed
correctly.
(torque 1.00~1.35N・m: Reference value)
2.2.2. FC1-HY
FC1-HY is surface mount type.
Using the two screw holes of the metallic parts for the installation of 2 places which are
on the both side of control unit itself, please install securely in the equipment.
Tighten the screw in the specified torque range. Please ensure that equipment installed
correctly.
Please you have to match the screw installations environments.
・
Incorrect loading of the equipments can cause a malfunction,
failure or drop.
・Tighten the screw in the specified torque range.
・Under tightening can cause a drop, malfunction.
・
Over tightening can cause a drop, malfunction due to damage to
the screw or he equipments and malfunction.
!
!!
!
Warning

730110 K0
7
ES0911
Page
2.2.3. Installation places
The control unit must be installed on conductive place where is grounded. And must be used,
When it covers around control unit, electronic buzzer sound hears and becomes difficult to
take. In addition, also heat dissipation becomes bad, becomes cause of breakdown.
Because of this, usually at least please guarantee the space of width above 10mm substance
control unit top and around the guaranty of the passage of air current for heat dissipation
as a purpose.
2.3. Installation of detector
Install the mounting base for detector installation with the two screws M3 which is more
than 15mm length.
And install the detector just in the mounting base.
Caution
!
!!
!
Caution
!
!!
!
・
Install and use with environmental temperature and the humidity
which are within specification value.
・If the
control unit is not correctly installed, it causes the
malfunction, the breakdown, and the fall.
Please note it especially when using it with a lot of vibrations.
・
When the installation screw is loose, it causes the fall, the
short-circuit, and the malfunction.
・
When the installation screw is tightened too much, it causes the
fall, the short-
circuits, and malfunctions by the damage of the
screw and the control unit.
Install and use with environmental temperature and the humidity which
are within specification value.

730110 K0
8
ES0911
Page
2.4. Wiring
2.4.1. Power Supply
When turning on power source, rush current is between several mS, but above 10A it flows.
Wiring please tries to withstand this.
Earthing connection of the ground terminal please goes in order to protect the equipment
from electric shock accident prevention and electric noise, securely.
2.4.2. Communication line
The communication line is connected with control unit and detector as the power line and
the signal line. Therefore, use the shield cable of 0.5mm
2
, and connect the shield part in
the shield cable with the terminal FG.
Divergence wiring is possible concerning wiring. In addition also polarity is nonpolar
characteristics.
Do not bundle with line which gives out other electric noise and separate from it.
・Please do the wiring after the external power supply off. It may
get
an electric shock or the control unit may break down.
・Please use the terminal cover for the control unit when the unit
is
energized, after do the wiring.
If the terminal cover is not used, it may get an electric shock.
・When miss-
wiring or connecting to a power supply different from
ratings, it causes a fire and the breakdown.
・Please give the noise of power supply (DC24V±
10%) to the control
unit as 1Vp-p or less.
Please decrease with the power supply filter etc, whe
n the influence
of the noise is strong.
Caution
!
!!
!
!
!!
!
Warning
Caution
!
!!
!
[
Isolation from electric noise source such as power line
]
The signal conductor which is connected to the receiver and the receiver please wires
above 20cm separating from the power line.
Case it is not possible, please pass in the metallic conduit which the power line is
grounded.

730110 K0
9
ES0911
Page
3
33
3.
Starting the system
Starting the systemStarting the system
Starting the system
3.1.1. Setting of control unit
Please verify whether the number of detectors which it is connected with the DET. NUMBERS
switch which is on the panel front is same.
When setting is different, trouble indication is lighting.
3.1.2. Power on
When the supply of power or power switch is pushed, the power light(green LED) lights up,
the system operates starts.
3.1.3. Register at time of power on
ON
Power supply
OFF
Maximum 120 seconds
State of
Control unit
Initialize
※1
,Wait・Registration
※2
Supervision
※1 After power on, the alarm LED and the trouble LED blink sequentially.
※2 Control unit supplying power to the detector which is connected, starts communication.
Control unit inspects the address of all detectors which are connected, registers the detector
automatically.
When detectors of a quantity which is set in 120 seconds are registered, supervision is started.
When a quantity which is set with control unit and the number of detectors which are registered
are different it makes trouble.
Caution
!
!!
!
・
Pay attention to the sharp edge and the like when you handle control
unit. It becomes cause of the wound.
・
Do not operate switch with sharp and hard ones like a ball pen top.
It makes surface sheet make a tears.
・
Do not touch by hand where the oil is attached and the chemicals are
attached. The surface seat deteriorates and softens.

730110 K0
10
ES0911
Page
3.2. Control unit
3.2.1. Name and function of each section
① Operation panel
a. POWER : Power supply switch (White)
Supply of power supply is started, or the each operation of POWER switch turns on/off the
system.
b. RESET : Reset switch(Blue)
Operation of reset switch resets the alarm LED, alarm signal contact output and buzzer rumble
(continual sound).
However, when the detector still has alarm state, control unit for the second time becomes
alarm state.
The alarm LED and the trouble LED blink sequentially while resetting the alarm one by one.
Also, each segment LED of 7seg LED blinks in order one at a time.
c. DET. NUMBERS×10 : Detector numbers switch(X10)
This is the switch whereby to set the connectable detector numbers by ten digits. (X10)
Caution
!
!!
!
Caution
!
!!
!
After turning off the system, until it turns on power supply again,
please provide the interval of a minute o
r more. There are times when
the system does not start normally.
Since the setting of this switch is re
cognized only at the time of
turning the power on, the power is to be off in the event of changing
the setting.

730110 K0
11
ES0911
Page
d. DET. NUMBERS×1 : Detector numbers switch (X1)
This is the switch whereby to set the connectable detector numbers by ten digits. (X1)
e. POWER: Power Supply indication LED (Green)
While power has been turned on, the power light has lit up.
When control unit CPU error occurs, the power light it goes out and `E' or `E. 'is indicated
in 7Seg LED.
f. ALARM: Alarm indication LED (Red)
When the detectors are in alarm state, it lights up.
Control unit keeps alarm state. Control unit until reset switch is pushed even with when
the smoke of the smoke detector is gone, continues to indicate alarm state.
However, at the time of zone alarm occurrence, as for the alarm LED blinks. Concerning
“4.2.Zone alarm “. The zone alarm does not keep with control unit.
When the alarm occurs, alarm LED is indicated in preferentially from indication of other
things.
g. TROUBLE: Trouble indication LED (Yellow)
While trouble occurs in the system, the trouble LED which corresponds to the contents of
trouble lights up or blinks.
Details of trouble contents please refer to “6. Procedures/steps to be taken in the event
of trouble mode”.
h. Buzzer (Embedded)
In case of alarm state it rumbles with continual sound. In case of trouble state it rumbles
with intermittent sound.
However, at the time of control unit CPU error to continue rumble, the contents are indicated
in 7Seg LED.
Caution
!
!!
!
Caution
!
!!
!
Since the setting of this switch is recogni
zed only at the time of
turning the power on, the power is to be off in the event of changing
the setting.
When the alarm occurs in a trouble state where control unit CPU error
is excluded, rumble of the buzzer changes to continual sound from
intermittent sound because of alarm priority indication.

730110 K0
12
ES0911
Page
i. 7 Segment LED (Red)
Address of the detector where the alarm occurs is indicated.
When the alarm occurs with the plural detectors, the scroll it indicates in the order where
the alarm generates the address which is in the midst of alarm occurring 2 seconds.
First address indicates the decimal point in simultaneously
Address of the detector where trouble occurs is indicated.
When the trouble occurs with the plural detectors, the scroll it indicates in the order where
the trouble generates the address which is in the midst of alarm occurring 2 seconds.
First address indicates the decimal point in simultaneously
At the time of zone alarm occurrence “00” is indicated.
In addition, As for 7seg. LED indication “00” the scroll it indicates in the order where
the alarm generates indication and the address indication to which the alarm occurs.
When control unit CPU error occurs, “E” or “E.” indicates.
Because this indication is breakdown of control unit, please exchange.
Caution
!
!!
!
Caution
!
!!
!
Caution
!
!!
!
When trouble occurs in alarm state, for alarm priority indication,
the address where trouble occurs is not indicated.
When trouble occurs in alarm state, for alarm priority indication,
the address where trouble occurs is not indicated.
When the alarm occurs in zone alarm state, the alarm LED from blinking
becomes lighting because of alarm priority indication.
In addition, As for 7seg. LED indication “00”
the scroll it indicates
in the order where the alarm generates indication and the address
indication to which the alarm occurs.

730110 K0
13
ES0911
Page
② Terminal section
a. DC24V(+,-),
It is the terminal which connects the DC 24V power line.
b. FG
It is the terminal which connects the ground line.
c. Power Communication Line (L, C)
It is the terminal which connects the communication line.
Conformity wire
18-26AWG
Screw
M3×6L
Tightening torque
0.5 N・m
Caution
!
!!
!
!
!!
!
Warning
!
!!
!
Warning
!
!!
!
Warning
Please install the bundled terminal cover in order to prevent accident
such as electric shock.
Use the proper screw driver bit for screw size. Tig
hten inside of
torque.
Do not input the power source other than DC 24V to the terminal.
Do not exceed the service voltage range. It becomes cause of accident
such as fire.
Making a mistake in polarity and connect, the equipment breaks down.
Do not conn
ect wiring other than the communication line to this
terminal absolutely.
It becomes cause of breakdown such that it stops starting normally.

730110 K0
14
ES0911
Page
d. ALARM(COM,NO,NC)
At the time of alarm state and power supply stopping/deciding, the alarm contact signal
operates.
However, at the time of zone alarm occurrence, as for the alarm contact signal it does not
operate.
Alarm contact
State of control unit
Between
COM and NO
Between
COM and NC
Normal supervise Close Open
Alarm or Power supply stop
Open Close
Zone alarm Close Open
e. TROUBLE(COM,NO,NC)
At the time of trouble state and power source stopping/deciding, trouble contact signal
operates.
Trouble contact
State of control unit
Between
COM and NO
Between
COM and NC
Normal supervise Close Open
Trouble or Power supply stop
Open Close
f. RESET
With external non voltage contact input, control unit resets.
g. P-off
When power source of control unit is off, the non voltage contact point is output.
State of control unit contact
Power on Open
Power off Close
Caution
!
!!
!
Caution
!
!!
!
Caution
!
!!
!
!
!!
!
Warning
Do not exceed the maximum of contact point voltage and the maximum
of contact point electric current in this terminal. It becomes cause
of breakdown such as contact point depositing.
Do not exceed the maximum of contact point voltage and the maximum
of contact point electric current in this terminal. It becomes cause
of breakdown such as contact point depositing.
・
Do not connect other than the non voltage contact point to this
terminal absolutely. It becomes cause of breakdown such that it stops
starting normally.
・During signal inputting, control unit becomes non supervisory state
.
When reset action is verified, please stop the input of the signal.
Do not exceed the maximum of contact point voltage and the maximum
of contact point electric current in this terminal. It becomes cause
of breakdown such as contact point depositing.

730110 K0
15
ES0911
Page
③ About Trouble indication
a. DETECTOR
It lights up when sensitivity revision over or inside the detector, trouble occurs in the
detector. (Refer to “6.
Procedures/steps to be taken in the event of trouble occurrence”)
In addition, address of the detector where trouble occurs is indicated in 7seg LED.
b. DET.O V E R
It lights up when the number of detectors which have been recognized is greater than
specification at the detector number switch of control unit
c. DET.UNDER
It lights up when the number of detectors which have been recognized is less than specification
at the detector number switch of control unit.
Control unit, the numbers of detectors recognizing few, lights up similarly even when being
disconnected of the communication line and broken wire inside the detector.
d. PCL.SHORT
When the communication line is short, it lights up.
e. RECEIVER
It lights up when specification of detector number switches of control unit 0 or 32 or more.
In this case of control unit trouble, please exchange.

730110 K0
16
ES0911
Page
3.3. Dimensions
3.3.1. FC1-DY
3.3.2. FC1-HY

730110 K0
17
ES0911
Page
3.4. Electric specifications
(1) Name of item :
Control unit
(2) model :
FC1-DY
:
FC1-HY
(3) Rating :
DC24V 0.15A
(4) Range of working
voltage
:
DC24V ±10%
(5) Connectable detector
Numbers
:
Up to 31.
(6) Method of setting up
connectable detector
counts
:
It sets making use of the driver from the operation
panel.
When setting up 0 or 32, the trouble LED is made to light
up as a trouble state.
(7) Set up for receiving
the alarm signals
:
5%/m
(8) External wiring
resistance
:
Less than 10Ω
(9) Start up time :
After the power on and after the maximum of 2 minutes
start of supervision.
(10) Signal contact output
:
Alarm contact output
Contact type
State
Between
COM and NO
Between
COM and NC
Normal supervision Close Open
Alarm or Power off Open Close
Zone alarm Close Open
:
Trouble contact output
Contact type
State
Between
COM and NO
Between
COM and NC
Normal supervision Close Open
Trouble occurs or Power off
Open Close
・
Please install the power supply only for the control unit as
much as possible.
・
Please give the noise in the power supply to the control unit
as 1Vp-p or less.
・Please correspond with the power supply f
ilter etc, when there
is a noise.
!
!!
!
Warning
Caution
!
!!
!
Caution
!
!!
!
Please do not connect the detector of the same address. It becomes
not be able to watch normally.
External wiring value of resistance please do not wire above 10
Ω. Supervision stops impossible normally.

730110 K0
18
ES0911
Page
:
Power off contact output
State Contact
Power on Open
Power off Close
Capacity of contact DC30V 1A AC125V 0.3A Resistance
loading
(11) S o u n d o f a l e r t
:
Electronic buzzer.
Alarm sound : Continual sound
trouble sound : Intermittent sound(continual sound
priority)
(12) On/off of power
switch
:
At the time of power switch operating, when power source
is turned on again, please take the interval of 1 minute
or more.
When while the power switch is on main power source is
stopped directly, when main power source is turned on
again, please take the interval of 1 minute or more.
!
!!
!
Warning
Do not disassemble the equipment.
Electric shock, short circuit, there are times when it become
s cause
of fire and breakdown.

730110 K0
19
ES0911
Page
3.5. Environmental specifications
(1) Working temperature range
: 0℃~60℃
(2) Storage temperature range
: -20℃~70℃
(3) Working humidity range : 30~85%RH
3.6. Mechanical specifications
(1) External form : W125×D104×H40(FC1-DY)
: W121×D104×H40(FC1-HY)
(2) Main material : SPCC t1.0 black paint
(3) Mass : Approximately 420g
!
!!
!
Warning
Do not use at the place where it exceeds environmental specification
and the place where the volatilization gas and the corrosiveness gas
occur.
It becomes cause of breakdown such that it stops operating normally.

730110 K0
20
ES0911
Page
4
44
4.
Procedures/steps to be taken in the event of alarm occurrence
Procedures/steps to be taken in the event of alarm occurrenceProcedures/steps to be taken in the event of alarm occurrence
Procedures/steps to be taken in the event of alarm occurrence
When this system inspects abnormality, the following warning is output from control unit.
When warning is output, verifying circumstance, please do necessary disposal.
4.1. Alarm
The alarm occurs when the alarm signal (AON) from the detector is received by the control
unit.
(1) The alarm LED lights up.
(2) The buzzer (continual sound) rumbles.
(3) The alarm signal contact is output.
(4)The alarm detector address is indicated in 7seg LED indication.
4.2. Zone Alarm
The zone alarm is one of alarm information. That occurs when address recognition becomes
impossible in communication obstacle and control unit or breakdown of the detector,
(1) The alarm LED blinks.
(2) The buzzer (continual sound) rumbles.
(3) “00” is indicated in 7seg LED indication.
The state indicating LED of the detector at the time of alarm state and zone alarm state
blinks 1 times at a time in 2 seconds.
Table of contents
Other Fenwal Controls Control Unit manuals