finder 8A Series User manual

8A
SЕRIES
Programmable
Logic Relays
Control
panels for
pumps
Control and
management
of water
Packaging
machines
Panels for
electrical
distribution
Air
Conditioner
Building
automation
Forced-air
ventilators

FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.

H
Programmable Logic Relays (PLRs) with
8 input and 4 output relays
Type 8A.04-8300
- Lite version with USB (type C port), ETH
Type 8A.04-8310
- Plus version with USB (type C port), ETH and
Modbus RS485
Type 8A.04-8320
- Advanced version with USB (type C port),
ETH, Modbus RS485, Wi-Fi and BLE
• 8 digital or analog (0…10V) input
• 4 relay output 10 A
• USB (type C port) port for programming, data
logging and powering during configuration
• RJ45 port
• Connectivity (*according to type):
- USB
- 1 Gbit Ethernet TCP/IP or Modbus TCP/IP
- Modbus RS485*
- Wi-Fi + BLE*
• LED status indicator for each output
• Programmable USER button
• Programming language via IDE as an option
IEC-61131-3 (LD - SFC - FBD - ST - IL)
• 70 mm wide
• 35 mm rail (EN 60715) mount
8A.04
Screw terminal
8A.04-8300 8A.04-8310 8A.04-8320
• Lite version
• USB Port
• RJ45 Port for ETH and
Modbus TCP/IP
• Plus version
• USB Port
• RJ45 Port for ETH and
Modbus TCP/IP
• Modbus RS485 Port
• Advanced version
• USB Port
• RJ45 Port for ETH and
Modbus TCP/IP
• Modbus RS485 Port
• Wi-Fi/BLE internal module
Partnership with
For outline drawing see page 7
Output specification
Contact configuration 4 NO (SPST)
Rated current/Maximum peak current A 10/15
Rated voltage/
Maximum switching voltage V AC 250/400
Rated load AC1 VA 2500
Rated load AC15 (230 V AC) VA 500
Breaking capacity DC1: 24/110/220 V A 10/0.3/0.12
Minimum switching load mW(V/mA) 300 (5/5)
Output operate/release time ms 6/4
Standard contact material AgNi
Supply specification
Nominal voltage (UN) VDC 12…24
Rated power W 0.6…2.2 (according to type)
Operating range VDC 10.2…27.6
Input circuit
Number of input 8 (configurable)
Type Digital/Analog
Analog input type V 0…10
Analog input resolution 16 to 12 bit user configurable
Input frequency kHz 4.5
Input voltage signal 0/signal 1 <4 VDC / > 5.9 VDC
Input compatibility NPN/Sink
Reverse polarity protection YES
Technical data
Programm language Arduino via IDE , as option IEC-61131-3 (LD - SFC - FBD - ST - IL)
Minimum input signal ms 0.2
Electrical life at rated load in AC1 cycles 100·103
Ambient temperature range °C –20…+55
Protection category IP 20
Approvals (according to type)
3
I-2023, www.findernet.com
8A
SERIES
8A SERIES
Programmable Logic Relays

H
Ordering information
Example: 8A series, Lite PLR version, 4 NO (SPST) - 10A, 8 digital/analog input, 12…24 V DC.
8 A . 0 4 . 9 . 0 2 4 . 8 3 0 0
Series
Type
0 = Control Relay
No. of poles
4 = 4 NO (SPST)
Supply version
9 = DC
Supply voltage
024 = (12…24) V DC
N° of input
8 = 8 digital/
analog input
Options
0 = Standard
Versions
0 = Lite version, RJ45, USB (type C port)
1 = Plus version, RJ45, USB (type C port),
Modbus RS485 port
2 = Advanced version, RJ45, USB (type C
port), Modbus RS485 port, Wi-Fi/BLE
module
Type of output
3 = EMR NO contact (SPST)
4
I-2023, www.findernet.com
8A SERIES
Programmable Logic Relays
8A
SERIES

H
Technical data
Insulation
between input and output circuit VAC 4000
between open contacts VAC 1000
Insulation (1.2/50µs) between input and output kV 6
EMC specifications
Type of test Reference standard
Electrostatic discharge contact discharge EN61000-4-2 4kV
air discharge EN61000-4-2 8kV
Radio-frequency electromagnetic field (80 ÷ 1000MHz) EN61000-4-3 10V/m
Fast transients (burst) (5-50ns, 5kHz) on Supply terminals EN 61000-4-4 4kV
Surges (1.2/50µs) on Supply terminals common mode EN61000-4-5 4kV
differential mode EN61000-4-5 4kV
on input terminals common mode EN61000-4-5 4kV
differential mode EN61000-4-5 4kV
Radio-frequency common mode (0.15 ÷ 80MHz) on Supply terminals EN61000-4-6 10V
Radiated and conducted emission EN55022 class B
Other data
Power lost to the environment without contact current W 1.4
with rated current W 3.2
PLC to PLC communication and
PLC to network communication (Ethernet)
Ethernet:
– For Modbus TCP communication
– As standard TCP/IP
– RJ45 connector CAT5 cable, 2X LAN status led indicators
RS485:
– For Modbus RTU communication
– For custom serial communication
Wireless connectivity Wi-Fi and Bluetooth® Low Energy
Maximum program memory 1 MB internal
External memory module USB-C pendrive
Data Logging USB-C Stick + internal flash memory
Flash memory 2MB int + 16MB Flash QSPI
RESET button YES
USER button Push button configurable for user purposes
MCU STMicroelectronics STM32H747XI Dual ARM® Cortex® M7/M4 IC:
1x ARM® Cortex® -M7 core up to 480 MHz
1x ARM® Cortex® -M4 core up to 240 MHz
Secure element ATECC608B
Programming interface USB-C + OTA via Web Editor (Cloud) + Ethernet
RTC power reserve 10 days at 25 °C
RTC accuracy 10 min/year @25 °C 37.5 min/year @ –10…+70 °C
Cloud support Arduino Cloud via Wi-Fi and Ethernet or the Cloud services
Response time ON/OFF ms 6/4
Bounce time NO/NC ms 3/6
Terminals Screw terminals
Wire strip length mm 10
Screw torque Nm 0.8
Min. wire size solid cable stranded cable
mm20.5 0.5
AWG 20 20
Max. wire size solid cable stranded cable
mm21x6 / 2x4 1x4 / 2x2.5
AWG 1x10 / 2x12 1x12 / 2x14
5
I-2023, www.findernet.com
8A
SERIES
8A SERIES
Programmable Logic Relays

H
Front view
12
3
45
6
7
8
1
Supply terminals
12…24 V DC, Split terminals to facilitate wiring.
2
Input terminals
I1…I8 digital/analog (0…10 V) input configurable via IDE.
3
Output terminals
1…4 Output relay, 10 A 250 V AC, NO contact.
4
LED Status
1…4 LED Status configurable via IDE.
For exemple for 1…4 output relay LED ON = Contact CLOSE.
5
LED Ethernet port status
Status of ETH connection.
6
Modbus RS485 Port
Terminals for Modbus over RS485 protocol.
7
HARDWARE RESET
Button for hardware reset. BE CAREFUL. Press the 'RESET'
button with the tip of a small non-metallic insulated tool.
8
Programmable USER button
Button configurable via IDE by user, according to application
(ex. RUN/STOP, ON/OFF, BLE pair).
Contact specification
F 8A - Electrical life (AC) v contact current H 8A - Maximum DC1 breaking capacity
Cycles
DC breaking current (A)
DC voltage (V)
• When switching a resistive load (DC1) having voltage and current
values under the curve, an electrical life of ≥100·103can be
expected.
• In the case of DC13 loads, the connection of a diode in parallel with
the load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
6
I-2023, www.findernet.com
8A SERIES
Programmable Logic Relays
8A
SERIES

H
Wiring diagrams
Type 8A.04-8300 Type 8A.04-8310/8320
GND
A(-) B(+) B(+) A(-) GND
GND B(+) A(-) GND
A(-) B(+)
Getting "Started Guide"
Getting started - IDE
If you want to program your 8A.04 while offline you need to install the Arduino Desktop IDE.
To connect the 8A.04 to your computer, you’ll need a USB-C cable. This also provides power to the board, as indicated by the LED.
https://www.arduino.cc/en/Main/Software
Getting started - Arduino Web Editor
All Arduino boards, including this one, work out-of-the-box on the Arduino Web Editor, by just installing a simple plugin.
The Arduino Web Editor is hosted online, therefore it will always be up-to-date with the latest features and support for all boards. Follow to start coding
on the browser and upload your sketches onto your board.
https://create.arduino.cc/editor
https://create.arduino.cc/projecthub/Arduino_Genuino/getting-started-with-arduino-web-editor-4b3e4a
Getting started - Arduino IoT Cloud
All Arduino IoT enabled products are supported on Arduino IoT Cloud which allows you to Log, graph and analyze sensor data, trigger events, and
automate your home or business.
Online resources
Now that you have gone through the basics of what you can do with the board you can explore the endless possibilities it provides by checking exciting
projects on ProjectHub and the Arduino Library Reference
https://www.arduino.cc/reference/en/
Board Recovery
All Arduino boards have a built-in bootloader which allows flashing the board via USB. In case a sketch locks up the processor and the board is not
reachable anymore via USB it is possible to enter bootloader mode by double-tapping the reset button right after power up.
Outline drawings
Type 8A.04-8300
Screw terminal
Type 8A.04-8310
Screw terminal
Please see general technical information 7
I-2023, www.findernet.com
8A
SERIES
8A SERIES
Programmable Logic Relays

FCC and RED Cautions (Model 8A.04.9.024.8320)
FCC
Any Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority
to operate the equipment.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may
not cause harmful interference, and (2) this device must accept any interference received, including interference that may
cause undesired operation.
FCC RF Radiation Exposure Statement:
1. This Transmitter must not be co-located or operating in conjunction with any other antenna or transmitter.
2. This equipment complies with RF radiation exposure limits set forth for an uncontrolled environment.
3. This equipment should be installed and operated with minimum distance 20cm between the radiator& your body.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of
the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required
to correct the interference at his own expense.
RED
The product is in compliance with essential requirements and other relevant provisions of Directive 2014/53/EU. This product
is allowed to be used in all EU member states.
Frequency bands
2412 - 2472 MHz (2.4G WiFi)
Maximum output power (EIRP)
5,42 dBm
2,41 dBm
-6,27 dBm
2402 - 2480 MHz (BLE)
2402 - 2480 MHz (EDR)
This manual suits for next models