manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ABB
  6. •
  7. Relay
  8. •
  9. ABB KS Manual

ABB KS Manual

ABB Automation Inc.
Substation Automation and Protection Division
Coral Springs, FL 33065
Instruction Leaflet
All possible contingencies which may arise during installation, operation or maintenance, and all
details and variations of this equipment do not purport to be covered by these instructions. If further
information is desired by purchaser regarding this particular installation, operation or maintenance
of this equipment, the local ABB Power T&D Company Inc. representative should be contacted.
Printed in U.S.A.
 41-498B
Effective: August 1970
Supersedes I.L. 41-498A
Denotes Change Since Previous Issue
*
Type KS
Out-of-step Blocking Relay
0.51–30 Ohms
CAUTION
Before
putting
protective
relays
into
service
make
sure
that
all
moving
parts
operate
freely
,
inspect
the
contacts
to
see
that
they
are
clean
and
close
properly
,
and
operate
the
relay
to
check
the
settings
and
electrical
connections
.
APPLICATION
The
KD
-
3
relay
(
Figure
l
)
is
a
single
phase
impedance
type
relay
connected
to
receive
phase
-
to
-
neutral
voltage
and
phase
current
and
may
be
applied
as
a
supplement
to
conventional
two
-
zone
or
three
-
zone
distance
relaying
.
It
has
provisions
for
a
completely
offset
circle
characteristic
with
both
the
long
reach
and
the
short
reach
adjustable
.
In
KD
relay
applications
where
a
normal
second
zone
or
third
zone
setting
of
the
three
-
phase
unit
might
cause
tripping
because
of
possible
load
conditions
,
the
conventional
relay
settings
must
be
shortened
to
exclude
load
.
The
KD
-
3
displaced
circle
characteris
-
tic
may
be
added
to
the
KD
relay
three
-
phase
unit
shortened
circle
characteristic
to
provide
the
desired
total
reach
at
the
line
angle
without
danger
of
tripping
on
load
.
The
KD
phase
-
to
-
phase
unit
does
not
respond
to
balanced
three
phase
conditions
and
therefore
can
be
set
for
any
distance
without
fear
of
tripping
on
load
or
swing
conditions
.
The
KD
-
3
relay
is
available
with
either
a
1
ampere
or
a
0.2
/
2.0
ampere
indicating
contactor
switch
rating
.
The
1
ampere
rating
is
recommended
for
all
directional
comparison
applications
and
for
most
distance
relaying
applications
.
The
0.2
/
2.0
ampere
rating
is
recommended
for
distance
relaying
where
a
lockout
relay
is
ener
-
gized
or
where
a
high
impedance
auxiliary
tripping
relay
is
utilized
.
CONSTRUCTION
The
type
KD
-
3
relay
consists
of
two
single
air
gap
transformers
(
compensators
)
,
two
tapped
auto
-
transformers
,
a
cylinder
type
operating
unit
,
an
adjustable
reactor
and
an
ICS
indicating
contactor
switch
.
Courtesy of NationalSwitchgear.com
41-498B Type KD-3 Relay
2
Compensator
Compensators
,
which
are
designated
as
TA
and
TQ
,
are
two
-
winding
air
-
gap
transformers
(
Figure
2
)
.
The
primary
,
or
current
winding
,
has
seven
taps
which
terminate
at
the
tap
block
(
Figure
3
)
.
TA
is
the
''
long
reach
"
compensator
,
T
-
R
is
the
"
short
reach
"
compensator
and
tap
markings
for
the
respective
units
are
as
follows
:
TA
=
1.3
,
1.7
^
,
2.4
,
3.3
,
4.5
,
6.3
,
and
8.7
.
TB
=
.
87
,
1.16
,
1.6
,
2.2
,
3.0
,
4.2
,
and
5.8
.
Current
flowing
through
the
primary
coil
provides
an
f
>
lMF
which
produces
magnetic
lines
of
flux
in
the
core
.
A
voltage
is
induced
in
the
secondary
which
is
proportional
to
the
primary
tap
and
current
magnitude
.
This
proportionality
is
established
by
the
cross
sectional
area
of
the
laminated
steel
core
,
the
length
of
an
air
gap
which
is
located
in
the
center
of
the
coil
,
and
the
tightness
of
the
laminations
.
All
of
these
factors
which
influence
the
secondary
voltage
proportionality
have
been
precisely
set
at
the
factory
.
The
clamps
which
hold
the
laminations
should
not
be
disturbed
by
either
tightening
or
loosening
the
clamp
screws
.
The
secondary
winding
has
a
single
tap
which
divides
the
winding
into
two
sections
.
One
section
is
connected
subtractively
in
series
with
the
relay
terminal
voltage
.
Thus
a
voltage
which
is
proportional
to
the
line
current
is
subtracted
vectorially
from
the
relay
terminal
voltage
.
The
second
section
is
connected
to
an
adjustable
loading
resistor
and
provides
a
means
of
adjusting
the
phase
angle
relation
between
primary
current
and
the
induced
secondary
voltage
.
The
phase
angle
may
be
set
for
any
value
between
60
°
and
80
°
by
adjusting
the
resistor
between
its
minimum
and
maximum
values
respectively
or
for
89
°
torque
angle
of
75
°
current
lagging
voltage
.
Auto
-
Transformer
The
auto
-
transformer
has
three
taps
on
its
main
winding
,
S
,
which
are
numbered
1
,
2
,
and
3
on
the
tap
block
.
A
tertiary
winding
M
has
four
taps
which
may
be
connected
additively
,
or
subtractively
to
inversely
modify
the
S
setting
by
any
value
from
-
15
to
+
15
per
cent
in
steps
of
3
per
cent
.
The
sign
of
M
is
negative
when
the
R
lead
is
above
the
L
lead
.
M
is
positive
when
L
is
in
a
tap
location
which
is
above
the
tap
location
of
the
R
lead
.
The
M
settings
is
determined
by
the
sum
of
per
unit
values
between
the
R
and
L
lead
.
The
actual
per
unit
values
which
appear
on
the
tap
plate
between
taps
are
0
,
.
03
,
.
06
,
and
.
06
.
The
auto
-
transformer
makes
it
possible
to
expand
the
basic
range
of
the
compensators
by
a
multiplier
of
S
Therefore
,
any
relay
1
±
M
ohm
setting
can
be
made
within
dr
1.5
per
cent
from
1.13
ohms
to
30
ohms
,
for
a
long
reach
setting
,
and
from
0.75
ohms
to
20
ohms
,
for
a
short
reach
setting
,
by
combining
the
compensator
taps
T
^
Courtesy of NationalSwitchgear.com
Type KD-3 Relay 41-498B
3
and
Tc
with
the
auto
-
transformer
taps
and
M
^
,
and
SQ
and
MQ
.
Tripping
Unit
The
device
which
acts
to
initiate
tripping
is
a
four
-
pole
cylinder
unit
which
is
connected
so
that
one
pole
-
pair
voltage
leads
the
other
by
90
°
and
operates
as
a
two
-
phase
induction
motor
.
Contact
-
closing
torque
is
produced
by
the
unit
when
the
voltage
applied
to
its
terminals
has
a
negative
-
phase
sequence
.
Closing
torque
for
the
relay
forces
the
moving
contact
to
the
left
hand
side
as
viewed
from
the
front
of
the
relay
.
Contact
-
opening
torque
is
produced
when
positive
-
phase
sequence
voltages
are
applied
.
Hence
,
the
cylinder
unit
has
restraint
or
operating
torque
as
determined
by
the
phase
sequence
of
the
voltages
applied
to
its
terminals
.
Mechanically
,
the
cylinder
unit
is
composed
of
four
basic
components
;
a
die
-
cast
aluminum
frame
,
an
electromagnet
,
a
moving
element
assembly
,
and
a
molded
bridge
.
The
frame
serves
as
the
mounting
structure
for
the
magnetic
core
.
The
magnetic
core
which
houses
the
lower
pin
bearing
is
secured
to
the
frame
by
a
spring
and
snap
ring
.
This
is
an
adjustable
core
which
has
a
.
025
inch
flat
on
one
side
and
is
held
in
its
adjusted
position
by
the
clamping
action
of
two
compressed
springs
.
The
bearing
can
be
replaced
,
if
necessary
without
having
to
remove
the
magnetic
core
from
the
frame
.
The
electromagnet
has
two
series
-
connected
coils
mounted
diametri
-
cally
opposite
one
another
,
to
excite
each
set
of
poles
,
and
two
locating
pins
.
The
locating
pins
are
used
to
accurately
position
the
lower
pin
bearing
,
which
is
mounted
on
the
frame
,
with
respect
to
the
upper
pin
bearing
,
which
is
threaded
into
the
bridge
.
The
electromagnet
is
secured
to
the
frame
by
four
mounting
screws
.
The
moving
element
assembly
consists
of
a
spiral
spring
,
contact
carrying
member
,
and
an
aluminum
cylinder
assembled
to
a
molded
hub
which
holds
the
shaft
.
The
hub
to
which
the
moving
contact
arm
is
clamped
has
a
wedge
-
and
-
cam
construction
,
to
provide
low
-
bounce
contact
action
.
A
casual
inspection
of
the
assembly
might
lead
one
to
think
that
the
contact
arm
bracket
does
not
clamp
on
the
hub
as
tightly
as
it
should
.
However
,
this
adjustment
is
accurately
made
at
the
factory
and
is
locked
in
place
with
a
lock
nut
and
should
not
be
changed
.
Optimum
contact
action
is
obtained
when
a
force
of
4
to
10
grams
pressure
applied
to
the
face
of
the
moving
contact
will
make
the
arm
slip
one
-
fourth
of
its
total
free
travel
.
Free
travel
is
the
angle
through
which
the
hub
will
slip
from
the
condition
of
reset
to
the
point
where
the
clamp
projection
begins
to
ride
up
on
the
wedge
.
The
free
travel
can
vary
between
15
°
to
20
°
.
The
shaft
has
removable
top
and
bottom
jewel
bearing
,
rides
between
the
bottom
pin
bearing
and
the
upper
pin
bearing
which
is
adjusted
to
.
025
inch
from
the
top
of
the
shaft
bearing
.
The
shaft
Courtesy of NationalSwitchgear.com
41-498B Type KD-3 Relay
4
The
cylinder
rotates
in
an
air
gap
formed
by
the
electromagnet
and
the
magnetic
core
.
The
bridge
is
secured
to
the
electromagnet
and
frame
by
two
mounting
screws
.
In
addition
to
holding
the
upper
pin
bearing
,
the
bridge
is
used
for
mounting
the
adjustable
stationary
contact
housing
.
This
stationary
contact
has
.
002
to
.
006
inch
follow
which
is
set
at
the
factory
by
means
of
the
adjusting
screw
.
After
the
adjustment
is
made
the
screw
is
sealed
in
position
with
a
material
which
flows
around
the
threads
and
then
solidifies
.
The
stationary
contact
housing
is
held
in
position
by
a
spring
type
clamp
.
The
spring
adjuster
is
located
on
the
underside
of
the
bridge
and
is
attached
to
the
moving
contact
arm
by
a
spiral
spring
.
The
spring
adjuster
is
also
held
in
place
by
a
spring
type
clamp
.
When
the
contacts
close
,
the
electrical
connection
is
made
through
the
stationary
contact
housing
clamp
,
to
the
moving
contact
,
through
the
spiral
spring
and
out
to
the
spring
adjuster
clamp
.
Indicating
Contactor
Switch
Unit
(
ICS
)
The
indicating
contactor
switch
is
a
small
d
-
c
operated
clapper
type
device
.
A
magnetic
armature
,
to
which
the
leaf
-
spring
mounted
contacts
are
attached
,
is
attracted
to
the
magnetic
core
upon
energization
of
the
switch
.
When
the
switch
closes
,
the
moving
contacts
bridge
two
stationary
contacts
,
completing
the
trip
circuit
.
Also
during
this
operation
two
fingers
on
the
armature
deflect
a
spring
located
on
the
front
of
the
switch
,
which
allows
the
operation
indicator
target
to
drop
.
The
target
is
reset
from
outside
of
the
case
by
a
push
rod
located
at
the
bottom
of
the
cover
.
The
front
spring
,
in
addition
to
holding
the
target
,
provides
restraint
for
the
armature
and
thus
controls
the
pickup
value
of
the
switch
.
OPERATION
Type
KD
-
3
relays
have
two
major
components
,
the
compensators
and
the
tripping
unit
.
In
the
internal
schematic
of
Fig
.
4
compensators
designated
T
/
\
and
TQ
are
shown
connected
so
as
to
modify
the
voltage
applied
to
the
long
-
reach
coils
(
Zpy
?
)
and
the
short
-
reach
coils
(
£
SR
)
respectively
.
Operation
of
the
KD
-
3
relay
can
be
explained
by
referring
to
Fig
.
5
.
In
this
figure
the
addition
of
voltage
vectors
,
at
various
fault
locations
,
results
in
a
set
of
vectors
indicating
predominantly
positive
sequence
voltages
for
restraining
the
tripping
unit
or
indicating
predorninantely
negative
sequence
voltages
for
closing
the
tripping
unit
.
In
Fig
.
5
the
short
reach
setting
(
Zq
)
is
about
one
third
of
the
long
reach
setting
(
Z
^
)
and
is
in
the
same
direction
.
This
produces
the
solid
line
offset
circle
characteristic
which
excludes
the
Courtesy of NationalSwitchgear.com
Type KD-3 Relay 41-498B
5
origin
when
plotted
on
an
R
-
X
diagram
.
Note
that
if
Zc
had
been
set
with
reverse
polarity
,
by
reversing
the
external
current
connec
-
tions
,
the
broken
line
circle
characteristic
which
includes
the
origin
would
have
resulted
.
Terms
and
symbols
used
in
the
diagrams
are
defined
as
follows
:
Output
voltage
from
the
autotransformers
which
receive
phase
to
neutral
voltage
.
VSM
Mutual
impedance
setting
of
the
long
reach
compensator
.
ZA
Mutual
impedance
setting
of
the
short
reach
compensator
.
ZC
phase
Current
.
I
Z
(
LR
)
tripping
unit
coil
voltage
.
Z
(
SR
)
tripping
unit
coil
voltage
.
Positive
Sequence
(
restraining
)
phase
rotation
.
Negative
Sequence
(
closing
)
phase
rotation
.
Consider
a
fault
at
location
"
A
"
which
is
beyond
the
long
reach
setting
.
For
the
sake
,
of
simplicity
,
assume
both
the
line
angle
and
the
relay
maximum
torque
angle
to
be
90
°•
Compensator
Z
^
modifies
voltage
Vgp
.
]
by
adding
the
mutual
impedance
drop
IZ
^
which
leaves
voltage
XY
across
the
Z
(
LR
)
coils
.
Compensator
ZQ
modifies
its
voltage
Vgj
/
j
by
adding
IZQ
to
produce
Z
’
Y
.
This
voltage
is
then
advanced
90
°
,
by
the
phase
shifting
action
of
capacitor
Ccs
,
to
provide
voltage
ZY
across
the
Z
(
SR
)
coils
.
The
resulting
diagram
has
an
X
-
Y
-
Z
(
positive
sequence
)
pnase
rotation
which
restrains
the
unit
for
this
fault
beyond
the
protected
zone
.
Using
the
same
method
of
analysis
for
a
fault
at
location
"
B
"
,
the
long
reach
setting
Z
^
,
it
is
shown
that
X
,
Y
,
and
Z
lie
in
a
straight
line
indicating
equal
positive
and
negative
sequence
voltages
which
provides
a
balance
point
.
Within
the
protected
zone
,
for
a
fault
a
*
t
location
"
C
"
,
the
XY
voltage
is
reversed
by
compensa
-
tor
action
and
negative
sequence
voltage
X
-
Z
-
Y
produces
closing
torque
in
the
tripping
unit
.
At
location
"
D
"
,
the
short
reach
setting
,
another
balance
point
is
encountered
as
positive
sequence
and
negative
sequence
voltages
become
equal
again
with
X
,
Y
,
and
Z
in
line
.
XY
ZY
X
-
Y
-
Z
X
-
Z
-
Y
A
fault
at
location
"
En
whi
«
h
is
between
the
relay
and
the
protected
zone
causes
both
XY
and
ZY
to
be
reversed
,
restraining
^
X
-
Y
-
Z
phase
rotation
.
the
relay
,
causes
a
current
reversal
in
both
compensators
and
a
modifying
voltage
is
produced
which
increases
the
restraining
voltage
VSM
to
a
large
value
with
X
-
Y
-
Z
phase
rotation
.
This
provides
a
A
fault
at
location
"
F
"
,
behind
Courtesy of NationalSwitchgear.com
41-498B Type KD-3 Relay
6
The
combination
of
series
resistor
RA
and
parallel
capacitor
C
^
p
shown
in
Figure
4
controls
transients
in
the
Z
(
LR
)
circuit
and
also
provides
a
small
amount
of
phase
shift
.
In
the
Z
(
gR
)
circuit
,
capacitor
Cgg
provides
memory
action
to
improve
the
operaring
characteristics
for
faults
near
the
relay
location
.
CQS
also
provides
the
major
phase
shifting
effect
which
makes
the
voltage
across
Z
(
SR
)
lead
the
voltage
across
Zfjj
;
)
by
90
°
when
only
voltage
is
applied
to
the
relay
.
The
most
efficient
phase
relation
between
pole
pairs
for
the
cylinder
type
tripping
unit
is
90
°
which
can
be
accurately
set
using
the
variable
X
adjustment
.
Reactor
X
is
a
small
adjustable
unit
which
is
used
to
compensate
for
variations
in
other
components
.
CHARACTERISTICS
The
KD
-
3
relay
is
designed
to
respond
primarily
to
three
phase
faults
.
Since
it
receives
phase
-
to
-
neutral
voltage
and
phase
current
,
it
responds
accurately
to
any
three
phase
condition
and
to
phase
-
to
-
ground
faults
on
one
particular
phase
.
It
has
a
limited
response
to
phase
-
to
-
phase
and
double
-
phase
-
to
-
ground
faults
.
Distance
Characteristic
A
characteristic
circle
is
established
by
setting
two
points
on
the
circle
,
diametrically
opposite
one
another
,
by
means
of
the
Long
Reach
and
the
Short
Reach
compensators
.
As
shown
in
Figure
6
,
the
Short
Reach
setting
,
ZgR
,
may
be
positive
or
negative
with
respect
to
ZgR
,
or
it
may
be
zero
depending
upon
the
current
circuit
connections
to
the
Short
Reach
compensator
TQ
.
The
external
schematic
Figure
7
shows
positive
polarity
current
connections
to
both
TA
and
TQ
.
Solid
line
characteristics
of
Figure
6
are
typical
for
a
positive
Z
,
SR
.
Memory
action
in
the
tripping
unit
circuitry
provides
the
light
-
line
dynamic
characteristic
when
normal
voltage
exists
at
the
relay
terminals
prior
to
the
fault
.
The
heavy
-
line
static
characteristic
dominates
for
load
and
swing
conditions
or
if
there
is
zero
voltage
at
the
relay
prior
to
the
fault
.
The
broken
-
line
characteristic
passing
through
the
origin
is
obtained
by
by
-
passing
the
current
terminals
of
the
Tc
compensator
to
make
Zg
^
equal
to
zero
.
origin
is
obtained
by
making
reverse
polarity
connections
to
current
terminals
of
the
TQ
compensator
.
The
dashed
-
line
characteristic
which
includes
the
The
relay
is
inherently
directional
when
ZSR
is
either
zero
or
is
of
positive
polarity
.
If
TQ
has
a
negative
polarity
connection
to
the
current
terminals
,
Zgp
is
reversed
with
respect
to
ZLR
and
the
circle
characteristic
then
includes
the
origin
and
loses
its
sense
of
direction
.
Sensitivity
Figure
8
is
an
impedance
curve
which
demonstrates
the
relay
sensitiv
-
ity
to
faults
at
the
balance
point
for
various
values
of
voltage
at
the
relay
terminals
.
Courtesy of NationalSwitchgear.com
Type KD-3 Relay 41-498B
Zero
voltage
sensitivity
for
characteristics
which
include
the
origin
is
graphically
illustrated
in
Figure
9
.
General
Characteristic
Impedance
settings
in
ohms
reach
can
be
made
for
any
value
from
1.13
ohms
to
30
ohms
for
ZLR
and
from
.
75
ohms
to
20
ohms
for
Zgp
in
steps
of
3
per
cent
.
The
maximum
torque
angle
,
which
is
set
for
75
degrees
at
the
factory
,
may
be
set
for
any
value
from
60
degrees
to
80
degrees
.
A
change
in
maximum
torque
angle
will
produce
a
slight
change
in
reach
for
any
given
setting
of
the
relay
.
Referring
to
Figure
2
note
that
the
compensator
secondary
voltage
output
V
,
is
largest
when
V
leads
the
primary
current
,
I
,
by
90
°
.
This
90
°
relationship
is
approached
,
if
the
compensator
loading
resistor
(
F
*
2
A
or
°
Pen
-
ci
-
rcuit
ed
.
The
effect
of
the
loading
resistor
,
when
connected
,
is
to
produce
an
internal
drop
in
the
compensator
,
which
is
out
-
of
-
phase
with
the
induced
voltage
,
V
,
is
phase
-
shifted
to
change
the
compensator
maximum
torque
angle
.
As
a
result
of
this
phase
shift
the
magnitude
of
V
is
reduced
,
as
shown
in
Figure
2
.
Tap
markings
in
Figure
3
are
based
upon
a
75
°
compensator
angle
setting
.
If
the
resistors
R
2
A
and
R
2
C
are
adjusted
for
some
other
maximum
torque
angle
the
nominal
reach
is
different
than
indicated
by
the
taps
.
The
reach
,
ZQ
,
varies
with
the
maximum
torque
angle
,
9
,
as
follows
:
TS
sin
9
ZQ
-
(
1
t
M
)
sin
75
°
TAP
PLATE
MARKINGS
TA
1.3
1.7
^
2.4
3.3
4.5
6.3
8.7
TC
.
87
1.16
1.6
2.2
3.0
4.2
5.8
SC
&
Sc
12
3
+
Values
between
taps
MA
&
Mc
.
03
.
06
.
06
TIME
CURVES
AND
BURDEN
DATA
Operating
Time
The
speed
of
operation
for
the
KD
-
3
relay
is
shown
by
the
time
curves
in
Figure
10
.
The
curves
indicate
the
time
in
milliseconds
required
for
the
relay
to
close
its
contacts
for
tripping
after
the
inception
Courtesy of NationalSwitchgear.com
41-498B Type KD-3 Relay
8
of
a
fault
at
any
point
on
a
line
within
the
relay
setting
.
Current
Circuit
Rating
in
Amperes
Tap
Setting
Continuous
1
Second
S
=
1
S
2
S
=
3
5.8
8.5 8.5
240
5.0
4.2
6.0
240
10
.
10
.
8.0
3.0
240
10
.
10
.
2.2
240
10
.
10
.
10
.
1.6
240
10
.
10
.
10
.
1.16
0.87
240
10
.
10
.
10
.
240
10
.
10
.
10
.
Burden
The
burden
which
the
relay
imposes
upon
potential
and
current
transformers
is
shown
by
Figure
11
.
Trip
Circuit
Constants
1
ampere
rating
:
0.2
/
2.0
ampere
rating
:
0.1
ohms
d
.
c
.
resistance
0.2
tap
—
6.5
ohms
2
tap
-
-
0.15
ohms
SETTING
CALCULATIONS
Relay
reach
is
set
on
the
tap
plate
shown
in
Fig
.
3
.
markings
are
:
The
tap
TA
1.3
1.74
2.4
3.3
4.5
6.3
8.7
TC
.
87
l
.
16
1.6
2.2
3.0
4.2
5.8
SA
and
Sc
1
2
3
MA
and
Mc
.
03
.
06
.
06
(
Values
between
taps
)
Maximum
torque
angle
is
set
for
75
°
(
current
lagging
voltage
)
in
the
factory
,
of
65
°
or
higher
.
torque
angle
,
by
adjusting
R
2
A
and
R
2
C
*
This
adjustment
need
not
be
disturbed
for
line
angles
For
line
angles
below
65
°
,
set
for
a
60
°
maximum
Courtesy of NationalSwitchgear.com
Type KD-3 Relay 41-498B
9
The
general
formula
for
setting
the
ohms
reach
of
the
relay
is
:
(
Sin
6
)
Z
—
—
(
Sin
75
°
)
The
terms
used
in
this
formula
are
defined
as
follows
:
RC
-
zpri
Z
©
Rv
ZQ
=
the
desired
ohmic
reach
of
the
relay
and
relates
equally
to
Long
Reach
(
ZQ
^
)
and
Short
Reach
(
Z
0
gR
)
.
=
the
tap
plate
setting
.
TS
Z
1
-
M
T
=
compensator
tap
value
.
S
=
Auto
-
transformer
primary
tap
value
.
©
=
Maximum
torque
angle
setting
of
the
relay
.
Sin
Q
=
1
.
)
(
For
a
factory
setting
of
75
°
then
Sin
75
°
M
=
Auto
-
transformer
secondary
tap
value
.
(
This
is
a
Per
Unit
value
and
is
determined
by
the
sum
of
the
values
between
the
"
L
"
and
the
"
R
"
leads
.
The
sign
is
positive
when
"
L
"
is
above
"
R
"
and
acts
to
Lower
the
Z
setting
.
The
sign
is
negative
when
"
R
"
is
above
"
L
"
and
acts
to
raise
the
Z
setting
)
.
Zpri
-
ohms
per
phase
of
the
line
section
to
be
protected
.
Rc
=
current
transformer
ratio
.
Rv
=
potential
transformer
ratio
.
The
following
procedure
should
be
followed
in
order
to
obtain
an
optimum
setting
of
the
relay
.
Relate
the
general
equation
to
Long
Reach
or
Short
Reach
by
sub
letters
"
A
"
and
"
C
"
respectively
.
Select
the
lowest
tap
S
which
gives
a
product
of
10.3
and
6.9
SQ
greater
than
Z
where
Z
=
ZQ
(
sin
75
°
)
(
sin
0
)
*
1
.
Z
Select
a
value
for
T
that
is
nearest
the
value
2
.
S
Determine
the
value
of
M
that
will
most
nearly
make
3
.
TS
If
the
sign
is
negative
,
then
the
M
taps
-
1
.
M
Z
are
connected
with
the
R
lead
above
the
L
lead
to
Raise
the
setting
.
Courtesy of NationalSwitchgear.com
41-498B Type KD-3 Relay
10
For
example
,
assume
the
desired
reach
,
ZQLR
of
the
relay
is
10.8
ohms
at
60
degrees
.
Then
Zjj
{
=
10.8
x
1.11
=
12
ohms
.
The
lowest
tap
S
for
10.3
SA
greater
than
12
is
S
=
2
.
Set
SA
in
tap
2
.
TA
nearest
to
1
.
—
—
=
6.0
is
6.3
ohms
.
Set
TA
in
tap
6.3
2
.
2
12.6
-
1
)
=
(
1.05
-
1
)
=
0.05
(
Use
M
=
.
06
)
3
.
M
=
(
12
Set
MA
for
+
.
06
6.3
x
2
4
.
=
11.9
Then
=
l
f
.
06
(
Sin
0
)
5
.
=
1.07
relay
ohms
at
a
maximum
torque
This
is
of
the
desired
ZGLR
~
ZLR
angle
setting
of
60
degrees
,
value
.
(
Sin
75
°
)
6
.
for
a
600
maximum
torque
angle
.
Set
Ft
2
A
7
.
Use
the
same
six
steps
described
above
to
calculate
settings
for
TQ
,
SQ
than
zero
.
and
by
-
pass
the
current
terminals
of
TQ
.
SETTING
THE
RELAY
,
and
MQ
when
ZQ
^
R
IF
ZOSRI
5
4
°
ke
zero
,
set
is
any
value
other
SQ
on
1
,
MQ
for
0.0
,
The
KD
-
3
relay
requires
settings
for
each
of
the
two
compensators
(
Ta
and
TQ
)
,
each
of
the
two
auto
-
transformer
primaries
(
SA
and
SQ
)
,
and
for
the
two
auto
-
transformer
secondaries
(
MA
and
Me
)
.
All
of
these
settings
are
made
with
taps
on
the
tap
plate
which
is
located
above
the
operating
unit
.
Figure
3
shows
the
tap
plate
.
Compensator
(
TA
and
TQ
)
Each
set
of
compensator
taps
terminate
in
inserts
which
are
grouped
on
a
socket
and
form
approximately
three
quarters
of
a
circle
around
a
center
insert
which
is
the
common
connection
for
all
of
the
taps
.
Electrical
connections
between
common
insert
and
tap
inserts
are
made
with
a
link
that
is
held
in
place
with
two
connector
screws
,
one
in
the
common
and
one
in
the
tap
A
compensator
tap
setting
is
made
by
loosening
the
connector
screw
in
the
center
.
Remove
the
connector
screw
in
the
tap
end
of
the
link
,
swing
the
link
around
until
it
is
in
position
over
the
insert
for
the
desired
tap
setting
,
replace
the
connector
screw
to
bind
the
link
to
this
insert
,
and
retighten
the
connector
screw
in
the
center
.
Since
the
link
and
connector
screws
carry
operating
current
,
be
sure
that
the
screws
are
turned
to
bind
snugly
.
Courtesy of NationalSwitchgear.com
Type KD-3 Relay 41-498B
11
Auto
-
Transformer
Primary
(
SA
and
Sc
)
Primary
tap
connections
are
made
through
a
single
lead
for
each
transformer
.
The
lead
comes
out
of
the
tap
plate
through
a
small
hole
located
just
below
the
taps
and
is
held
in
place
on
the
proper
tap
by
a
connector
screw
.
(
Figure
3
)
.
An
"
S
"
setting
is
made
by
removing
the
connector
screw
,
placing
the
connector
in
position
over
the
insert
of
the
desired
setting
,
replacing
and
tightening
the
connector
screw
.
The
connector
should
never
make
electrical
contact
with
more
than
one
tap
at
a
time
.
Auto
-
Transformer
Secondary
(
M
^
and
F
7
Q
)
Secondary
tap
connections
are
made
through
two
leads
identified
as
L
and
R
for
each
transformer
.
These
leads
come
out
of
the
tap
plate
each
through
a
small
hole
,
one
on
each
side
of
the
vertical
row
of
"
M
"
tap
inserts
.
The
lead
connectors
are
held
in
place
on
the
proper
tap
by
connector
screws
.
Values
for
which
an
,
rM
"
setting
can
be
made
are
from
-
.
15
to
+
.
15
in
steps
of
.
03
.
The
value
of
a
setting
is
the
sum
of
the
numbers
that
are
crossed
when
going
from
the
R
lead
position
to
the
L
lead
position
.
The
sign
of
the
"
M
"
value
is
determined
by
which
lead
is
in
the
higher
position
on
the
tap
plate
.
The
sign
is
positive
(
+
)
if
the
L
lead
is
higher
and
negative
(
-
)
if
the
R
lead
is
higher
.
An
"
M
"
setting
may
be
made
in
the
following
manner
.
Remove
the
connector
screws
so
that
the
L
and
R
leads
are
free
.
Determine
from
the
following
table
the
desired
"
M
"
value
.
Neither
lead
connector
should
make
electrical
contact
with
more
than
one
tap
at
a
time
.
Tabulated
Settings
L
Lead
R
Lead
z
75
°
M
Upper
.
06
Upper
.
06
Lower
.
06
Upper
.
06
0.87
TS
0.89
TS
0.92
TS
0.94
TS
0.97
TS
0
+
-
.
15
+
.
12
+
.
09
+
.
06
+
.
03
.
03
0
Lower
.
06
0
.
03
0
c
0
TS
*
.
03
0
.
03
1.03
TS
1.06
TS
1.1
TS
1.14
TS
1.18
TS
Line
Angle
Adjustment
Lower
.
06
.
06
Upper
.
06
Lower
.
06
Upper
.
06
Upper
.
06
0
.
09
.
12
.
03
.
15
0
Maximum
torque
angle
is
set
for
75
°
(
current
lagging
voltage
)
in
the
factory
.
This
adjustment
need
not
be
disturbed
for
line
angles
of
Courtesy of NationalSwitchgear.com
41-498B Type KD-3 Relay
12
65
°
or
higher
.
For
line
angles
below
65
°
,
set
for
a
60
°
maximum
torque
angle
by
adjusting
the
compensator
loading
resistors
R
2
A
and
Refer
to
repair
calibration
when
a
change
in
maximum
torque
angle
is
desired
.
Indicating
Contactor
Switch
(
ICS
)
R
2
C
:
No
setting
is
required
for
relays
with
a
1.0
ampere
unit
.
For
relays
with
a
0.2
/
2.0
ampere
unit
,
connect
the
lead
located
in
front
of
the
tap
block
to
the
desired
setting
by
means
of
the
connecting
screw
.
When
the
relay
energizes
a
125
-
or
250
-
volt
d
-
c
type
WL
relay
switch
,
or
equivalent
,
use
the
0.2
ampere
tap
;
for
48
-
volt
d
-
c
applications
set
the
unit
in
a
tap
2
and
use
a
Type
WL
relay
with
a
S
#
304
C
209
G
01
coil
,
or
equivalent
.
INSTALLATION
The
relays
should
be
mounted
on
switchboard
panels
or
their
equivalent
in
a
location
free
from
dirt
,
moisture
excessive
vibration
and
heat
.
Mount
the
relay
vertically
by
means
of
the
mounting
stud
for
the
type
FT
projection
case
or
by
means
of
the
four
mounting
holes
on
the
flange
for
the
semi
-
flush
type
FT
case
.
Either
the
stud
or
the
mounting
screws
may
be
utilized
for
grounding
the
relay
.
The
electrical
connections
may
be
made
directly
to
the
terminals
by
means
of
screws
for
steel
panel
mounting
or
to
the
terminal
stud
furnished
with
the
relay
for
thick
panel
mounting
.
The
terminal
stud
may
be
easily
removed
or
inserted
by
locking
two
nuts
on
the
stud
and
then
turning
the
proper
nut
with
a
wrench
.
For
detailed
information
on
the
FT
Case
refer
to
I
.
L
.
41
-
076
.
ACCEPTANCE
TESTS
KD
-
3
relays
have
a
very
small
number
of
moving
parts
and
mechanical
devices
which
might
become
inoperative
.
Acceptance
tests
in
general
consists
of
:
1
.
A
visual
inspection
to
make
sure
there
are
no
loose
connections
,
broken
resistors
,
or
broken
resistor
wires
.
2
.
An
electrical
test
to
make
certain
that
the
relay
measures
the
balance
point
impedance
accurately
.
Distance
Unit
Check
the
electrical
response
of
the
relay
by
using
the
test
connections
for
Test
No
.
6
shown
in
Figure
12
.
Set
TA
for
8.7
,
Tc
for
3.0
,
SA
and
Sr
for
1
,
and and
MQ
for
+
-
0.15
(
L
in
top
position
and
R
in
bottom
position
)
.
Adjust
the
voltage
Vi
to
30
volts
.
A
.
Courtesy of NationalSwitchgear.com
Type KD-3 Relay 41-498B
13
The
current
required
to
make
the
contacts
close
for
the
long
-
reach
balance
point
should
be
between
3.89
and
4.05
amperes
at
the
maximum
-
torque
angle
of
75
°
current
lag
.
The
current
required
to
make
the
contacts
reset
at
the
short
-
reach
balance
point
should
be
between
11.1
and
11.6
amperes
at
75
°
current
lag
.
If
the
electrical
response
is
outside
the
limits
,
a
more
complete
series
of
test
outlined
in
the
section
titled
,
"
Calibration
"
may
be
performed
to
determine
which
component
is
faulty
or
out
of
calibration
.
Indicating
Contactor
Switch
(
ICS
)
B
.
C
.
Close
the
main
relay
contacts
and
pass
sufficient
d
-
c
current
through
the
trip
circuit
to
close
the
contacts
of
the
ICS
.
This
value
of
current
should
not
be
less
than
1.0
ampere
nor
greater
than
1.2
amperes
for
the
1
ampere
ICS
.
The
current
should
not
be
greater
than
the
particular
ICS
tap
setting
being
used
for
the
0.2
-
2.0
ampere
ICS
.
The
operation
indicator
target
should
drop
freely
.
The
contact
gap
should
be
approximately
0.047
"
for
the
0.2
/
2.0
ampere
unit
and
0.070
"
for
the
1.0
ampere
unit
between
the
bridging
moving
contact
and
the
adjustable
stationary
contacts
.
The
bridging
moving
contact
should
touch
both
stationary
contacts
simultaneously
.
ROUTINE
MAINTENANCE
The
relays
should
be
inspected
periodically
,
at
such
time
intervals
as
may
be
dictated
by
experience
,
to
insure
that
the
relays
have
retained
their
calibration
and
are
in
proper
operating
condition
.
All
contacts
should
be
cleaned
periodically
.
#
l
82
A
836
H
01
is
recommended
for
this
purpose
,
material
for
cleaning
contacts
is
not
recommended
because
of
the
danger
of
embedding
small
particles
in
the
face
of
the
soft
silver
and
thus
impairing
the
contact
.
A
contact
burnisher
The
use
of
abrasive
Before
making
"
hi
-
pot
"
tests
,
jumper
the
contacts
together
CAUTION
:
to
avoid
destroying
arc
-
suppressor
capacitors
.
When
performing
routine
maintenance
,
the
distance
unit
and
the
ICS
can
be
checked
by
using
the
same
procedure
as
outlined
in
Acceptance
Tests
.
The
balance
point
impedance
measured
by
the
relay
v
;
here
V
is
the
phase
-
to
-
neutral
voltage
applied
is
VL
-
N
L
-
N
ZR
-
to
the
relay
terminals
and
II
is
the
phase
•
current
.
IL
REPAIR
CALIBRATION
Use
the
following
procedure
for
calibrating
the
relay
if
the
relay
has
been
taken
apart
for
repairs
or
the
adjustments
disturbed
.
Courtesy of NationalSwitchgear.com
41-498B Type KD-3 Relay
14
Connect
the
relay
for
testing
as
shown
in
Figure
12
.
For
best
results
in
checking
calibration
,
the
relay
should
be
allowed
to
warm
up
for
approximately
one
hour
at
rated
voltage
.
However
,
a
cold
relay
will
probably
check
to
within
two
per
cent
of
the
warm
relay
.
Distance
Unit
Calibration
With
the
stationary
contact
open
so
that
the
moving
contact
cannot
touch
,
set
the
moving
contact
spring
adjuster
so
that
the
contact
floats
freely
in
the
gap
.
Make
sure
that
there
is
no
friction
which
prevents
free
movement
of
the
cylinder
and
contact
arm
.
The
upper
pin
bearing
should
be
screwed
down
until
there
is
approximately
.
025
inch
(
one
complete
turn
of
the
screw
)
between
it
and
the
top
of
the
shaft
bearing
.
The
upper
pin
bearing
should
then
be
securely
locked
in
position
with
the
lock
nut
.
The
lower
bearing
position
is
fixed
and
cannot
be
adjusted
.
Check
to
see
that
the
taps
on
front
of
the
tap
block
are
set
as
follows
:
TA
set
on
8.7
and
TQ
set
on
5
*
8
SA
and
SQ
set
on
1
.
"
R
"
for
MA
and
"
L
"
for
MA
and
Mc
hangs
free
.
Resistors
R
2
A
and
R
2
C
open
circuited
by
adjustable
bands
not
making
contact
.
A
.
Compensator
Angle
Adjustment
:
1
.
Long
Reach
Compensator
TA
.
a
.
Connect
the
relay
as
per
Figure
12
.
Test
No
.
1
.
b
.
Adjust
voltage
Vi
to
90
volts
,
set
the
phase
shifter
so
that
current
lags
voltage
by
90
°
,
and
increase
the
current
to
the
value
which
produces
a
null
(
within
three
volts
)
reading
on
null
detector
NA
(
requires
about
10
amperes
)
.
Note
the
Exact
Value
of
Current
.
c
.
Change
voltage
Vi
to
87
volts
,
swing
phase
shifter
to
75
°
current
lagging
,
and
adjust
R
2
A
to
reach
a
null
on
NA
when
the
current
is
at
the
null
value
of
l
.
b
.
noted
above
.
set
on
0.0
Short
Reach
Compensator
TQ
With
the
relay
connected
as
per
Figure
12
,
test
No
.
2
,
adjust
Vj
to
60
volts
,
set
phase
shifter
for
current
2
.
a
.
Courtesy of NationalSwitchgear.com
Type KD-3 Relay 41-498B
15
lagging
voltage
by
90
°
,
increase
the
current
to
the
value
which
produces
a
null
(
within
3
volts
)
reading
on
null
detector
NQ
(
requires
about
10
amperes
)
,
the
Exact
Value
of
Current
.
Note
Change
Vq
to
58
volts
,
swing
the
phase
shifter
to
75
°
current
lagging
,
and
adjust
ROQ
when
the
current
is
at
the
null
above
.
b
.
to
read
a
null
on
NQ
value
of
2
.
a
.
noted
Auto
-
transformer
Check
:
B
.
Auto
-
transformers
may
be
checked
for
turns
ratio
and
polarity
by
using
the
No
.
3
test
connections
of
Figure
12
,
and
the
procedure
outlined
below
.
Set
SA
and
SQ
on
tap
number
3
.
Apply
90
volts
between
terminals
8
and
9
*
Measure
the
voltage
from
terminal
9
to
tap
No
.
1
of
SA
and
SQ
.
It
should
be
l
/
3
the
applied
voltage
=
30
volts
.
From
terminal
9
to
tap
No
.
2
of
SA
and
Sc
the
voltage
should
be
2
/
3
the
applied
value
=
60
volts
.
1
.
2
.
Set
SA
and
SQ
on
tap
number
1
and
apply
100
volts
between
terminals
8
and
9
.
Measure
the
voltage
drop
from
terminal
9
to
each
of
the
MA
and
MQ
taps
.
This
voltage
should
be
equal
to
100
(
l
+
the
sum
of
values
between
R
and
the
tap
being
measured
)
.
Example
:
100
(
1
-
t
-
.
03
+
-
.
06
)
=
109
volts
.
Transformers
which
have
an
output
different
from
nominal
by
more
than
1.0
volt
probably
have
been
damaged
and
should
be
replaced
.
C
.
Tripping
Unit
Core
Adjustment
:
The
adjustable
core
is
set
at
the
factory
to
bias
the
contacts
open
on
current
-
only
.
This
adjustment
can
be
checked
or
made
according
to
the
following
procedure
.
Use
test
connections
of
Test
No
.
4
and
set
"
L
"
for
MA
and
Me
in
the
top
position
(
.
03
+
-
.
06
+
-
.
06
=
.
15
between
L
and
R
)
.
Supply
5
amperes
to
the
relay
and
set
the
adjustable
core
so
that
the
contacts
just
open
.
Increase
the
current
in
steps
of
about
10
amperes
up
to
65
amperes
.
It
may
be
necessary
to
readjust
the
core
in
order
to
make
sure
that
the
contacts
never
close
on
current
only
.
The
reactor
X
adjustment
should
be
checked
after
any
change
in
the
core
adjustment
.
Reactor
X
Adjustment
:
permit
setting
the
impedance
angle
of
its
own
circuit
to
a
proper
relation
with
the
impedance
angle
of
the
Z
(
JJR
)
circuit
.
Use
connections
of
Test
No
.
5
to
check
or
make
the
reactor
adjustments
.
The
reactor
adjustment
is
provided
to
D
.
Courtesy of NationalSwitchgear.com
41-498B Type KD-3 Relay
16
1
.
Set
the
voltage
,
Vi
,
for
50
volts
and
the
current
,
A
,
for
7.5
amperes
.
Adjust
the
Reactor
X
for
a
maximum
torque
angle
of
75
°
-
2
°
.
Rotate
the
phase
shifter
to
find
the
two
angles
,
0
i
and
©
p
,
at
which
the
contacts
just
close
.
The
maximum
torque
angle
is
:
014
-
02
(
)
degrees
This
angle
should
be
between
73
°
and
77
°
for
a
nominal
75
°
adjustment
.
2
A
smaller
angle
may
be
obtained
by
drawing
the
reactor
core
out
.
The
angle
may
be
increased
by
screwing
the
core
in
.
2
.
Check
to
see
if
the
Tripping
Unit
Core
Adjustment
is
changed
as
a
result
of
a
change
in
the
X
adjustment
.
E
.
Contact
Adjustment
:
With
the
moving
-
contact
arm
against
the
right
-
hand
backstop
,
screw
the
stationary
contact
in
until
it
just
touches
the
moving
Then
back
the
stationary
contact
out
two
-
thirds
(
2
/
3
)
of
one
turn
to
give
0.020
-
inch
gap
between
contacts
.
contact
.
F
.
Spring
Restraint
and
Impedance
Curve
:
Connect
for
Test
No
.
6
of
Figure
12
.
Set
TA
=
8.7
and
TQ
=
3.0
;
SA
and
SQ
=
1
;
"
R
"
for
MA
and
MQ
set
0.0
;
,
,
T
"
for
MA
and
MQ
should
be
in
the
'
top
positions
.
1
.
L
Set
=
5.0
volts
A
-
0.88
amp
.
lagging
voltage
by
75
°
.
Then
adjust
the
restraint
spring
so
that
the
contacts
just
close
.
to
reset
the
contacts
when
the
relay
is
deenergized
.
This
should
provide
the
restraint
torque
necessary
o
Increase
the
voltage
to
30
volts
and
check
that
current
for
the
two
balance
point
settings
fall
within
the
limits
stated
below
;
4
-
«
Amperes
(
9
=
75
°
)
/
Settings
Volts
Imin
Imax
ZLR
=
7.56
=
2.64
3.89
4.05
11.06
30
30
7
11.1
VSR
Courtesy of NationalSwitchgear.com
Type KD-3 Relay 41-498B
17
/
To
determine
the
limits
of
current
when
©
is
not
equal
to
75
°
.
>
multiply
the
nominal
values
tabulated
above
by
the
ratio
sin
75
°
sin
9
Indicating
Contactor
Switch
(
ICS
)
Close
the
main
relay
contacts
and
pass
sufficient
d
-
c
current
through
the
trip
circuit
to
close
the
contacts
of
the
ICS
.
This
value
of
current
should
be
not
less
than
1.0
ampere
nor
greater
than
1.2
amperes
for
the
1
ampere
ICS
.
The
current
should
net
be
greater
than
the
particular
ICS
tap
setting
being
used
for
the
0.2
-
2
.
ampere
ICS
.
The
operation
indicator
target
should
drop
freely
.
The
contact
gap
should
be
approximately
0.047
"
for
the
0.2
/
2.0
ampere
unit
and
0.070
"
for
the
1
ampere
unit
,
between
the
bridging
moving
contact
and
the
adjustable
stationary
contacts
.
The
bridging
moving
contact
should
touch
both
stationary
contacts
simultaneously
.
RENEWAL
FARTS
Repair
work
can
be
done
most
satisfactorily
at
the
factory
.
However
,
interchangeable
parts
can
be
furnished
to
the
customers
who
are
equipped
for
doing
repair
'
work
.
When
ordering
parts
,
always
give
the
complete
nameplate
data
.
Courtesy of NationalSwitchgear.com
41-498B Type KD-3 Relay
18
NOMENCLATURE
FOR
RELAY
TYPE
KD
-
3
ITEM
DESCRIPTION
ZLR
Two
Element
-
Coils
in
Long
Reach
Circuit
;
Total
d
.
c
.
resistance
=
127
ohms
.
Two
Element
-
Coils
in
Short
Reach
Circuit
;
Total
d
.
c
.
resistance
=
219
ohms
.
2
Inch
Resistor
355
Ohms
Fixed
.
2
Inch
Resistor
600
Ohms
Adjustable
.
4
MFD
Capacitor
Parallel
Connected
.
1.8
MFD
Capacitor
Series
Connected
.
Variable
Reactor
.
Compensator
(
primary
Taps
-
1.3
;
1.74
;
2.4
;
3.3
;
4.5
;
6.3
;
3.7
)
.
Compensator
(
Frimary
Taps
-
.
87
;
1.16
;
1.6
;
2.2
;
3.0
;
4.2
;
5.8
)
.
Auto
-
transformer
primary
(
Taps
-
1
;
2
;
3
)
Auto
-
transformer
Secondary
(
Between
Taps
-
0.0
;
.
03
;
.
06
;
.
06
)
.
VSR
*
A
R
2
A
&
R
2
C
CAP
ccs
x
TA
Tc
SA
&
Sc
M
/
\
&
Me
Courtesy of NationalSwitchgear.com
Type KD-3 Relay 41-498B
19
S
*
&
M
*
rA
R
2
A
(
REAR
VIEW
)
(
FRONT
VIEW
)
r
Fig
.
1
Type
KD
-
3
Relay
Without
Case
Courtesy of NationalSwitchgear.com
41-498B Type KD-3 Relay
20
LAMINATED
CORE
PRIMARY
SECONDARY
DISTANCE
UNIT
AIR
GAP
I
HO
I
CAT
INC
CONTACTOR
SWITCH
-
—
.
.
I
mo
A
IS
GAP
TRANSFORMERS
AUTO
-
TRANSFORMER
CHASSIS
OPERATED
SHORTING
SWITCH
REO
HANDLE
CURRENT
TEST
JACK
TEST
SWITCH
TERMINAL
FRONT
VIEW
T
~
\
N
V
/
ADJUSTABLE
ANGLE
/
185
A
348
\
i
)
\
Fig
.
4
Internal
Schematic
of
Type
FT
31
case
.
(
ICS
Coil
Not
Tapped
for
Relays
with
1
Amp
I
.
C
.
S
.
)
/
\
/
\
>
1
849
A
034
Fig
.
2
Compensator
Construction
SHORT
REACH
SETTINGS
LONG
REACH
SETTINGS
Z
ZLR
SR
I
LEAD
“
L
1 1
LEAD
“
R
Fig
.
3
Tap
Plate
Courtesy of NationalSwitchgear.com

Other ABB Relay manuals

ABB CM Series User manual

ABB

ABB CM Series User manual

ABB MMCO-2 Manual

ABB

ABB MMCO-2 Manual

ABB CVQ Manual

ABB

ABB CVQ Manual

ABB RGU-10 User manual

ABB

ABB RGU-10 User manual

ABB KD-10 Manual

ABB

ABB KD-10 Manual

ABB Relion REX610 User manual

ABB

ABB Relion REX610 User manual

ABB Relion 670 series Instructions for use

ABB

ABB Relion 670 series Instructions for use

ABB RELION REF615R User manual

ABB

ABB RELION REF615R User manual

ABB REJ 523 Product manual

ABB

ABB REJ 523 Product manual

ABB SPAJ 111 C User manual

ABB

ABB SPAJ 111 C User manual

ABB AS400 User manual

ABB

ABB AS400 User manual

ABB REU615 User manual

ABB

ABB REU615 User manual

ABB C576 User manual

ABB

ABB C576 User manual

ABB CA-26 Manual

ABB

ABB CA-26 Manual

ABB EF19 User manual

ABB

ABB EF19 User manual

ABB REU 523 Product manual

ABB

ABB REU 523 Product manual

ABB ACS255 User manual

ABB

ABB ACS255 User manual

ABB RELION RET670 User manual

ABB

ABB RELION RET670 User manual

ABB CV-21 Manual

ABB

ABB CV-21 Manual

ABB CT-AHS Firmware update

ABB

ABB CT-AHS Firmware update

ABB Relion 615 series User manual

ABB

ABB Relion 615 series User manual

ABB TA200DU User manual

ABB

ABB TA200DU User manual

ABB MG-6 Manual

ABB

ABB MG-6 Manual

ABB ITH-T Series Guide

ABB

ABB ITH-T Series Guide

Popular Relay manuals by other brands

American Time H004896R quick start guide

American Time

American Time H004896R quick start guide

Bticino 3584C manual

Bticino

Bticino 3584C manual

C&S Electronics CSMPA22-2S manual

C&S Electronics

C&S Electronics CSMPA22-2S manual

Omron Sti SR120MP operating instructions

Omron

Omron Sti SR120MP operating instructions

Measurement Computing USB-ERB08 user guide

Measurement Computing

Measurement Computing USB-ERB08 user guide

Crouzet EMWS 84 903 020 Installation sheet

Crouzet

Crouzet EMWS 84 903 020 Installation sheet

M-system R7C-DC8E instruction manual

M-system

M-system R7C-DC8E instruction manual

BECKWITH ELECTRIC M-3520 Instruction book

BECKWITH ELECTRIC

BECKWITH ELECTRIC M-3520 Instruction book

Ampcontrol ELM V2 user manual

Ampcontrol

Ampcontrol ELM V2 user manual

KRIWAN INT69 F Diagnose installation instructions

KRIWAN

KRIWAN INT69 F Diagnose installation instructions

I-Gard SIGMA 3 manual

I-Gard

I-Gard SIGMA 3 manual

Pilz PSEN ma1.3p-20 operating manual

Pilz

Pilz PSEN ma1.3p-20 operating manual

Schweitzer Engineering Laboratories SEL-300G instruction manual

Schweitzer Engineering Laboratories

Schweitzer Engineering Laboratories SEL-300G instruction manual

ERL F-PRO 5100 user manual

ERL

ERL F-PRO 5100 user manual

ASO Safety Solutions ELMON inductive 74-302 operating manual

ASO Safety Solutions

ASO Safety Solutions ELMON inductive 74-302 operating manual

Nexa MSOR-3500 user manual

Nexa

Nexa MSOR-3500 user manual

COQON UPS2MB01 manual

COQON

COQON UPS2MB01 manual

Hella 3099 Operation and installation instructions

Hella

Hella 3099 Operation and installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.