Fire Pro FPX103C User manual

FPX103C
Dual Loop Auto/Manual
Fire Control Panel
Technical Manual

FPX103C Auto DUAL LOOP AUTO/MANUAL FIRE CONTROL PANEL Iss 1.0
SUMMARY:
Dual detection loops with full fault monitoring.
Automatic extinguisher operation after shutdown.
“Double knock” automatic activation logic.
Automatic Engine/fuel/fan shutoff capability.
“Spindown” delay ensures extinguishant is not vented.
Extinguisher activation button with anti-tamper tag.
Universal 12 or 24Vdc electrical power.
Low power consumption in “PARKED” mode.
Full fault monitoring on all detector and firex circuits.
Supports up to 6 aerosol fire extinguisher/generators.
Very low false activation potential, tamper seal on ManOp
The unit is reverse polarity, transient and EMC protected.
Custom behavior logic available on request.
Shutdown and delayed firex activation improves effectiveness and saves cost of extra extinguishant.
Most existing extinguishing systems release the agent into a high airflow environment which makes it
almost completely ineffective. Given that a 7 Liter 4 stroke engine at 3000RPM (that’s 50revs/sec)
aspirates 175 Liters or 0.175m3of air per second, add to this ventilation fan flow and the necessity for
a shutdown with engine/fan spindown delay before activation is obvious.
The FPX103C has effectively eliminated spurious activation warranty costs which are regularly caused
by the inherent characteristics of microprocessors, semiconductor power switches and inquisitive
fingers. Our tamper evident tag technology and our strict electronic design rules has proven highly
effective. To eliminate the inherent hazards of microprocessor control the FPX103C uses a fully
parallel path programmable logic device, which is coded using a language called VHDL, commissioned
by US DOD and used for high reliability and safety critical applications.
FEATURES:
2-wire Smoke, thermal or Linear Heat Sensors up to 50M are continuously monitored for alarms, open
circuit and chassis faults. LED flash codes indicate the location of an alarm or fault condition.
An internal alarm sounder and relay to drive a loud external audible alarm unit up to 2Amps.
Uncommitted relay change-over contacts are available for fuel shutoff, engine/fan shutdown.
The delay option provides a selectable spin-down time so that the extinguishant is not wasted.
“PARKED MODE” is entered when unit senses that ignition is turned off and provides automatic
extinguisher operation should both loops alarm - switching off engine during a double alarm will also
enter timed auto activation mode (aka driver “legging it” protection).
There is an electrical input for an override keyswitch to circumvent shutdown circuits for restarting.
FUNCTIONAL NOTES:
Any loop alarm condition will operate audible and visual alarm indications as follows:
Single loop alarm condition produces internal pulsed alarm (1 per sec) and fan shutdown.
Dual loop alarm condition produces internal pulsed alarm (2 per sec) and automatic
extinguisher and fuel solenoid operation after spindown delay (user set on dip switches),
audible alarm goes continuous.
Alarm LED flash code indicates which loop is in alarm (1=1blink, 2=2blinks, 1&2=3blinks).
The spindown delay allows time for fan and engine to stop before extinguisher is activated. This is to
save extinguishing agent that would otherwise be wasted through venting. The timer tracks the

spindown of engine/fan(s) as a result of ignition switch-off or shutdown by FPX103C as a result of an
alarm (from either detectors or manual operate switch). With the ignition off the unit enters low power
mode and the ON LED will flash to conserve power. Single flash shows the spindown timer is still
counting (fans still turning), then adopts a double flash “heartbeat” indicating that “parked mode” is
active and extinguisher operation will be immediate on double alarm or manual operate.In “parked
mode” (ignition off for longer than spindown delay) then the fuel solenoid will operate on first alarm and
extinguisher immediately on second alarm.
Switching on the ignition even for a short time will restart the spindown timer and it is also active on
initial power-on.
Spindown timer is selectable: NoAUTO, IMMEDIATE, 5 to 30 seconds, 5 sec granularity.
A fault in one detector loop will cause the auto mode to fail (because of the double knock logic)
however a manufacturing option can allow PARKED mode to auto operate the extinguisher after single
loop alarm if the other loop is faulty.
Manual operate command must also wait for the engine/fan spindown before extinguisher activation.
After 125ms filter time the unit will confirm activation request by flashing 2ALARM=AUTO LED and
internal beeper, fan and fuel solenoid shutdown relays are activated immediately. After spindown
timeout the extinguisher will operate and beeper will go continuous.
PANEL LED INDICATIONS:
The panel layout has two distinct areas for extinguisher and detector status with separate LED flash
pattern indications for each detection loop (1 and 2).
Power On (Green LED)
Detector Alarm (Red LED) - inverse flash pattern indicating affected loop
Detector Loop Fault (Red AMBER) - inverse flash pattern indicating affected loop
2 Alarms=Auto Active (Red LED)
Extinguisher Fault (Red AMBER)
Internal sounder will operate on anything that requires user attention (alarm or fault).
CONTROLS:
Extinguisher manual operate button (behind tamper evidence tag)
Auto mode time delay selector DIP switch on panel rear (delay = binary_value * 5 seconds).
SW1-3 off-off-off = immediate, on-on-on = AutoDisabled, on-off-off=5sec, off-on-off=10sec, etc.
SW4 on = vfc operates on single alarm, off = vfc operates on double alarm
CONNECTIONS:
BLOCK 1 (6 way)
GND
External Alarm Output (Power via 2A N.O. relay contact)
GND
Ignition input (sets auto PARKED mode when off)
Power (11-32vdc via 4A fuse)
GND
BLOCK 2 (6 way) BLOCK 3 (6 way)
Detector Loop1A FirexA
Detector Loop1B FirexB
Detector Loop2A GND
Detector Loop2B VFC (2Amps Max)
GND NO VFC (2Amps Max) COM
Aux input VFC (2Amps Max) NC

ELECTRICAL SPECIFICATION (at 24VDC supply unless otherwise stated):
Power Supply
Operating Voltage
11 to 32V DC
Quescent Current Ign Off
8.5mA Typ (excluding external load currents)
Ign On
16mA Typ (excluding external load currents)
Maximum Alarm Current
Draw
100mA (excluding external load currents)
Max current draw
3A (including extinguisher operate current)
Parked current draw
8.5mA Typ
Suppressor Activation
Discharge Current
1A to 4A depending on voltage and number of
suppressors (StatX = 1.8 Ohms nominal each unit)
Up to 2 units on 12V, 4 units max on 24V
Connect in series with bi-directional catch diodes
across each element (see manual).
Current/Time Limit
Output is Vin via switch with 6 Ohms in series.
Constant I2T limit = 9 Amp2*Seconds
Monitoring current
<4mA, Fault if loop R>300, 12Vmax o/c voltage
AuxIn (Override key)
Monitoring current
1.2mA Nominal
Sense Logic
Norm S/C, >1K active typ.
Sensor Loop Inputs 1+2
Max Output voltage
12VDC regulated, filtered and transient protected
Output current limit
25mA per loop
Alarm condition threshold
<700 Ohms Nominal
Fault condition threshold
Approximately 20K Ohms
End Of Line Resistor
10K Ohms
Fault monitoring
Open circuit or ground fault = fault indication
Alarm Output
Relay Contacts
2A @ VinDC (Vin thru NO relay circuit)
VFC Output
Relay Contacts (volt free)
2A @ 24VDC (relay changeover circuit)
Mechanical
Dimensions
H=82mm * W=83mm * D=25mm
Mounting
75mm diameter round hole, retained by four #6*25
self tapping screws
Connections
Via 3 * 6 way terminal block accepting <1mm2
wires with ferrules
DIP SWITCH SETTINGS (Black = switch tab)
DIP switches 1.2.3 set a delay time between shutdown (VFC) and subsequent
extinguisher automatic activation. Delay can be set 0 to 30 seconds in 5 second steps.
Manual only mode can be set with ON.ON.ON.OPT
DIP switch 4 defines critical alarm OPTion.
The default setting is OFF which requires 2 loops to be in alarm (OPT=“double knock”)
before shutdown and time delayed extinguisher activation.
Moving to ON position requires only one loop to be in alarm (OPT=“single knock”)
before shutdown and time delayed extinguisher activation.
Note that the unit dispenses activation delay following depowering of ignition input.
The instant mode is indicated by flashing green PWR LED which gives double flash
whilst moving through the delay and single flash on reaching zero delay instant mode.

Fan/Engine “Spindown” delay time before automatic release.
Note: Spindown delay only when ignition is ON
OFF.OFF.OFF.OPT 0 Sec = Immediate
ON.OFF.OFF.OPT 5 Sec
OFF.ON.OFF.OPT 10 Sec
ON.ON.OFF.OPT 15 Sec
OFF.OFF.ON.OPT 20 Sec
ON.OFF.ON.OPT 25 Sec
OFF.ON.ON.OPT 30 Sec
ON.ON.ON.OPT No Automatic Operation
Installation Notes:
Ensure that Linear Heat Detectors are suitably mounted for the vehicle vibration levels.
Front of panel is splash proof but it must be located to prevent excessive moisture or water getting to
the unit, especially the rear connections.
Locate to avoid excessive direct solar exposure.
WARNING! (And some common sense…..) Refer to the installation manual.
System installation must be verified by a competent technician familiar with regulations governing such
installations.
Do not install in Engine, bilge, fuel or gas storage compartments (see RCD and ISO9094).
In the event of an alarm shutdown the engines and ventilation immediately.
The cause of the activation must be found and corrected before restarting.
DO NOT PROCEED TO OVERRIDE UNLESS IT HAS BEEN DETERMINED SAFE TO DO SO.

Outline & Mounting drawing:


Typical Application wiring (Linear Heat Detector sensors)

Manufacturer: Logician Ltd
25 The Paddock
Maidenhead Berks, SL6 6SD
United Kingdom
Tel: +44 (0) 162 8630891
PRODUCT DISCLAIMERS
FirePro Systems makes no representations or warranties of any kind, either express
or implied, statutory or otherwise, including but not limited to warranties of
merchantability, fitness for a particular purpose, of title, or of non-infringement of third
party rights, including the intellectual property rights of others.
For Materials or Equipment manufactured by Third Parties and not by FirePro Systems,
the Buyer shall only be entitled to the benefit of any such warranty or guarantee as is
given by the Third Party manufacturer to FirePro Systems.
LIMITATION OF LIABILITY
In no event, regardless of cause, shall FirePro Systems be liable for any indirect,
special, incidental, punitive or consequential damages of any kind, whether arising
under breach of contract, tort (including negligence), strict liability or otherwise, even if
advised of the possibility of such damages.

FirePro Systems
6 Koumandarias Street, PO Box 54080, CY-3720 Limassol, Cyprus - EU
Tel.: +357 25 379999 | Fax: +357 25 354432 | Email: mail@firepro.com
www.firepro.com
Table of contents
Other Fire Pro Control Panel manuals

Fire Pro
Fire Pro FP-22408 User manual

Fire Pro
Fire Pro 08451 User manual

Fire Pro
Fire Pro FP-08450 User manual

Fire Pro
Fire Pro 08451 User manual

Fire Pro
Fire Pro 08100 User manual

Fire Pro
Fire Pro FPC-2 User manual

Fire Pro
Fire Pro FPC-2 User manual

Fire Pro
Fire Pro Sigma XT Reference guide

Fire Pro
Fire Pro FPC-2 User manual
Popular Control Panel manuals by other brands

MZ electronic
MZ electronic NAUTI220 Technical manual

Balboa Water Group
Balboa Water Group Clearwater Spas spaTouch BP Series User Interface and Programming Reference Manual

SIMARINE
SIMARINE PICO user manual

CAME
CAME Z Series manual

DMP Electronics
DMP Electronics XR6 COMMAND PROCESSOR installation guide

PEAKnx
PEAKnx Controlmini user manual