Page | 15
•Electrical System Inspection:
-Check Manual Actuators are secure, clean, undamaged.
-Check that anti-tamper seals/pull pins are in place and secure.
-Check all wiring, connection and supports are in intact, undamaged and in correct
position.
•Labels:
-Check manual release, system warning and instruction labels are in place and legible.
•Test the fault monitoring system by disconnecting and reconnecting all connected
detection devices and the siren strobe circuit one at a time. Ensure the “Fault” LED indicator
illuminates and the internal sounder is heard each time a circuit is disconnected.
•Discharge Testing from Control Panel:
-Perform a manual discharge test by pressing and holding both mode switches on the
panel continuously for 5 seconds.
-Following activation, ensure the Test Module Red LED has operated.
-Isolate the panel to silence alarm. Panel should now display a fault.
-Reset Test Module. Panel should no longer be in fault condition.
-Turn off the Isolate function.
•Discharge Testing from External Devices: Each detection and manual actuator device
connected to must be tested individually.
-Perform an automatic discharge test by activating the detectors or manual actuators.
-Following the activation sequence ensure the Test Module Red LED has operated.
-Isolate the panel to silence the alarm. The control panel should now display a fault.
-Reset the Test Module.
-Reset the control panel by pressing and holding a single mode switch until 2 beeps are
heard. The control panel should no longer be in alarm/fault condition.
•System control and indicating equipment.
-During discharge test, ensure operation of all installed siren/strobe(s).
-During discharge test, ensure operation of all installed shutdown relays. This must
shutdown any equipment specified in the risk assessment.
-Test backup battery capacity. Replace every backup battery every 2 years.
•Disconnect the FP-08800 Test Module and reconnect all FirePro aerosol generators.
•Turn off the Isolation function. System is now operational.
Additional requirements for Commissioning of a System after Install or Discharge
•Design Survey - check against the baseline data, for alterations, changes in use or
operating environment, or other factors that could affect the performance of the fire
protection system. (Annual)
•Risk Assessment –required to be prepared and reviewed every 5 years or after any
incident. Review document to ensure system compliance. Check if document is current.