manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. First Alert
  6. •
  7. Security System
  8. •
  9. First Alert FA148CP Series User manual

First Alert FA148CP Series User manual

ÊK5305-5QGV2]Š
K5305-5QGV2 2/11 Rev. A
Copyright © 2009 Honeywell International Inc.
www.firstalertprofessional.com
2 Corporate Center Drive, Melville, NY 11747
FA168CPS Series / FA148CP Series Security Systems
Quick Installation Guide
(A copy of the Installation and Setup Guide is available upon request)
FOR DOCUMENTATION AND ONLINE SUPPORT: http://www.firstalertprofessional.com/drz (see instructions K5305-5V6 or higher)
These instructions apply to the following Honeywell security systems:
FA168CPS, FA168CPSSIA, FA168CPS-CN, FA148CP, FA148CPSIA, FA148CP-CN
Features and procedures apply to all, except where differences are noted.
FA168CPSSIA and FA148CPSIA are certified SIA-compliant controls that meet SIA specifications for
False Alarm Reduction.
Connect Devices, Zones, Sounder, and Phone Line.
Refer to the Wiring Diagram on the reverse side for connection information. NOTE: This system uses a range of reserved addresses for each type of device.
1. Connect keypads and other addressable devices to the ECP terminals 4-7.
Refer to the wiring chart below for wire sizes and maximum wire run lengths.
Wire Chart For Devices Drawing Aux Power From The Control (12V+ & 12V–)
Wire TOTAL CURRENT OF ALL DEVICES CONNECTED TO A SINGLE WIRE RUN
Size 50 mA or less 100 mA 300 mA 500 mA 600 mA
#22 900ft (274m) 450ft (137m) 150ft (46m) 90ft (27m) 75ft (23m)
#20 1400ft (427m) 700ft (213m) 240ft (73m) 140ft (43m) 120ft (37m)
#18 1500ft (457m) 1100ft (335m) 350ft (107m) 220ft (67m) 170ft (52m)
#16 1500ft (457m) 1500ft (457m) 550ft (168m) 350ft (107m) 270ft (82m)
The length of all wire runs for both partitions combined must not exceed 1500 feet (457m) when unshielded quad
conductor cable is used (750 feet if shielded cable is used).
Standard Keypads (FA215KP / FA260KP / FA560KP)
•Keypad addresses range from address 16-23. Set each keypad’s address accordingly.
NOTE: Address 16 is reserved for the first keypad and is always enabled in the control.
•Use data fields ∗190-∗196 to enable keypads and set their sounding options.
Expander Modules (4219, 4229)
•Connect desired field wiring to the module’s zone terminals.
•Expander module addresses range from 07-11. Set each module’s DIP address accordingly.
•Use ∗56 Menu mode to program zone characteristics.
Touchscreen Keypads (FA700KP / FA800KP; FA168CPS = up to 4; FA148CP = up to 2)
•Use of touchscreen keypads is independent from and in addition to the eight (8) standard keypads.
•Set each touchscreen’s address accordingly (1, 2, 5, 6; see table on back) and enable in field ∗189.
•Make sure the auxiliary current drain is within the control’s limitation. Otherwise use an external
power supply to power the touchscreen keypads.
RF Receiver (5881, 5883, RF Keypad)
•5881L / 5882L = up to 8 RF zones; 5881M / 5882M / = up to 16 RF zones
5881H / 5882H / 5883 / FA260RF = up to system maximum RF zones
•Set the receiver’s address to 00 using the module’s DIP switches.
•If using wireless keypads, set field ∗24 RF House ID Code appropriately.
If receiver is mounted remotely, note the following:
•Do not locate the receiver or transmitters on or near metal objects. This will decrease range and/or
block transmissions.
•Do not locate the RF receiver in an area of high RF interference (indicated by frequent or
prolonged lighting of the receiver’s LED; random flicker is OK).
•Do not locate RF receiver closer than 10 feet from any keypads.
Relay Modules (4204)
•Connect desired field wiring to the module’s relay contact terminals.
•Relay module addresses range from address 12-15.Set each module’s DIP address accordingly.
•Use ∗79 / ∗80 Menu modes to map each device address and define output functions.
Communication Device (7847i, 7845GSM, 7845i-GSM, GSMV)
•Set the communication device to address 03.
•Use ∗29 Menu mode to enable and program the device.
AVS System
•If used, follow the installation instructions provided with the module.
•Connect the AVS module to the control’s ECP terminals and connect all other ECP devices to the
AVS module’s ECP terminals.
•Set the AVS address using its DIP switches: FA148CP = 08; FA168CPS = 11
•Use the desired AVS Quick Program Command to set pre-defined options:
installer code + [#] + 0 + 3: enable AVS operation
installer code + [#] + 0 + 4: enable AVS and enable panel sounds on AVST speaker
•Use field ∗55 Dynamic Signaling Priority to select the desired reporting paths.
2. Connect hardwire zones to the appropriate zone terminals 8-20.
3. On-Board Trigger Connections
•Connect field wiring to the appropriate trigger pin using the SA4120XM-1 cable (if using 1361X10
transformer) or the 4-wire cable (N4632-4 not supplied).
•Trigger outputs are normally high, and go low upon programmed condition (can be set inverted).
•Use ∗79/∗80 Menu modes to program the trigger outputs.
•Output 17 (pin 1) = supports up to 100mA max ; Output 18 (pin 5) = supports up to 20mA max
4. Install Wireless Zone Transmitters.
•Use ∗56 Menu mode to program wireless zones and enroll the transmitters.
•Use the Go/No Go Test mode to verify adequate signal strength from each transmitter location:
Enter Installer code + [#] + 4, then fault each transmitter and listen for 3 beeps at the keypad and
the zone display. Exit mode: user code + 1 (OFF).
5. Connect the external sounder to terminals 3 and 4.
•If supervised output desired, see Sounder Supervision wiring diagram on reverse side, and set field
∗91 Option Selection for Bell Supervision.
6. Connect the phone line using terminals 21-24.
•Use an RJ31X jack as shown in the diagram on reverse side.
Mount the Control.
1. Remove the cabinet door. Remove the cabinet
knockouts needed for wiring entry.
2. Mount the control cabinet to a sturdy wall in a
clean, dry area, which is not readily accessible to
the general public, using fasteners or anchors (not
supplied) with the four cabinet mounting holes.
3. When installation and wiring is completed, install
the cabinet door and secure by using 2 screws
(supplied) through the door's edge.
OPTIONAL KEY LOCK: If desired, a key lock can be
installed (K4445, not supplied). See Installation
Instructions for details.
cab_6a-V0
SECURE
WITH
SCREWS
(2)
Securing the Cabinet Door
4. Mount the PC Board. Refer to the diagram below. If mounting an RF Receiver inside the cabinet,
remove the receiver board from its case, then insert the top of the board into the slots at the top of the
cabinet. Install the control board below the receiver board using the clips and screws provided. Insert
grounding lugs into the left-hand terminals of the antenna blocks and secure them with the screws
provided. Insert the receiver's antennas into the blocks' right-hand terminals, and tighten the screws.
+
+
CIRCUIT
BOARD
INSERT THE TOP OF THE
CIRCUIT BOARD INTO THE
SLOTS AT THE TOP OF THE
CABINET
DETAIL B
SIDE VIEW
OF MOUNTING CLIPS
DETAIL A
SIDE VIEW
OF BOARD SUPPORTING
SLOTS
CIRCUIT
BOARD
cb_mount-001-V1
CABINET
CABINET
HANG TWO SHORT MOUNTING CLIPS
(PROVIDED) ON THE RAISED CABINET TABS.
SECURE THE BOARD TO THE
CABINET WITH THE ACCOMPANYING
SCREWS
Mounting the PC Board
Connect the Transformer & Battery.
1321 Transformer (1321CN in Canada)
•Do not plug the transformer into the AC outlet until all wiring connections to the control are complete. As
a safety precaution, always power down the control when making such connections.
1361X10 Transformer
(required if using Powerline Carrier devices)
1. Splice one end of a 3-conductor cable to the wire ends of the SA4120XM-1 cable.
2. Connect the SA4120XM-1 cable plug to the 8-pin connector on the control.
3. Connect the other end of the 3-conductor cable to the 1361X10 Transformer.
Canadian Installations: For Powerline Carrier Devices, use the PSC04 X-10 Interface and trigger pins.
Battery Connections
•After all connections to the control are completed and after AC power has been applied, connect the
red and black flying leads on the control board to the battery.
•IMPORTANT: This control will not power-
up on battery alone (AC power must be applied). However, once
the system is powered up, it will operate on battery if AC is lost.
UL
For UL installations and Residential fire installations, refer to the chart below for the correct battery
size required to meet the mandatory standby time.
CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE
24-HOUR BATTERY BACKUP REQUIREMENTS
The California State Fire Marshal
and UL have regulations which require that all residential fire alarm control
panels must be provided with a backup battery which has sufficient capacity to operate the panel and its
attached peripheral devices for 24 hours in the intended standby condition, followed by at least 4 minutes in
the intended fire alarm signaling condition. This control panel can meet these requirements without using a
supplementary power supply, provided that the panel’s auxiliary power and bell output currents are limited
as listed below.
OUTPUT LIMITATIONS AND REQUIRED BATTERIES
OUTPUT CURRENT LIMITS BATTERY INFORMATION
Current Total
600mA
maximum total of
auxiliary power
plus bell output
currents
Max. Aux. Current
45mA
160mA
200mA
425mA
500mA
Battery Capacity (Amp/Hrs)
4AH
7AH
8AH
14AH
17.2AH
Recommended Battery (Yuasa No.)
NP4-12 (or ADEMCO 467)
NP7-12
NP4-12 (two) ‡
NP7-12 (two) ‡
NPG18-12
‡
NOTE: Use two batteries, connected in parallel. Obtain an Ademco Battery Harness Kit SA5140-1. (Both batteries will
fit inside the cabinet.)
Program the Control.
Refer to the Programming Guide to program the control.
(
The control can also be programmed via the Compass Downloader.)
1. Enter Programming Mode: installer code + 8-0-0.
2. Change the default Installer Code using field ∗20.
3. Enter the appropriate central station phone numbers and account numbers.
4. Program the system data field options as desired.
4. Use the various menu modes to program zones, relay outputs, descriptors, etc.
5. If AVS system is installed, use the appropriate AVS Quick Program Command.
6. Program Schedules (if used): Master code + [#] + 64
7. Enable RF button keyfobs (if used) and assign to user numbers accordingly.
8. Show the Master user how to change the default Master code:
master code + [8] + 0-2 + new code + new code again
Test the System.
Sniffer Mode Test: To verify that all transmitters have been properly programmed, disarm all partitions.
1. From a keypad in partition 1, enter Installer code + [#] + 3. All programmed transmitters are displayed.
2. Fault all transmitters in turn. The display clears each transmitter as a signal is received.
3.
Exit Sniffer mode: Installer code + 1 (OFF). Mode does not automatically expire; you must exit manually.
System Test
1. Disarm the system and close all protected windows, doors, etc.
2. Enter the Installer code + [5] (TEST), then press 0 = walk. (Option 1 = Dial checks phone line integrity.)
3. Listen. The external sounder should sound for about 1 second then turn off.
4. Fault all zones in turn and listen for three beeps from the keypad. ID of each faulted point should
appear on the keypad display. The display clears when the zone is restored.
5. Test all smoke and CO detectors following the manufacturer's instructions and check the display.
6. When all zones have been checked and are intact (closed), there should be no zone identification
numbers displayed on the keypad.
7. Exit test mode: security code + [1] (OFF).
Major Features and Capacities
Feature FA168CPS FA148CP
Partitions 2 plus common area not partitioned
Zones 48 plus 16 keyfob zones for
total of 64 zones:
•8 hardwired zones (1-8)
•Up to 40 additional wired
zones (9-48) using up to 5
4219/4229 modules
•Up to 40 wireless zones
(5800 series; zones 9-48)
•4 configurable zone types
32 zones plus 8 keyfob zones
for total of 40 zones:
•6 hardwired zones (1-6)
•Up to 16 additional wired
zones (9-24) using up to 2
4219/4229 modules
•Up to 26 wireless zones
(5800 series; zones 9-34)
•2 configurable zone types
Security Codes 48 32
Schedules 32 8
Keypad macros 4 2
Event Logging 100 50
Paging 4 2
Keypads 8 8
Touch Screen Devices 4 2
4219, 4229 5 2
4204 4 2
Output Relays / X-10 devices
16 8
On-Board Triggers 2 2
Output Functions 48 24
WARRANTY INFORMATION
For the latest warranty information, please go to:
www.honeywell.com/security/hsc/resources/wa
HARDWIRE ZONE CONNECTION
AC POWER CONNECTIONAC POWER CONNECTION
GND Z5Z4GNDZ3Z2GNDZ1+OUTINAUXAC
RED
GREEN
GRAY
BROWN
AC BELL GND GNDRINGTIPRING
INCOMING
HANDSET
TIPZ8GND Z6 Z7
1237811 12 17 20 21 22 23
18 19
16
15
14
13
10
9
6
45
Z1

EARTH 
GROUND
AFTER ALL WIRING CONNECTIONS ARE COMPLETE, PLUG
TRANSFORMER INTO A 110VAC UNSWITCHED OUTLET (24HR)
CONNECT ONLY AFTER AC POWER HAS BEEN APPLIED.
USE 1361X10 TRANSFORMER INTERFACE WHEN POWER
LINE CARRIER DEVICES ARE BEING USED.
BLACK
RED
2-WIRE SMOKE
DETECTORS
(16 MAX) OR
STANDARD
2K EOLR
PREMISES
PHONES
INCOMING
TELCO
RING (GRAY)
TIP (BROWN)
RING (RED)
TIP GREEN)
RJ31X
1 2 3
4
5
67
8
ZONE
PAIRS

2 / 10
3 / 11
4 / 12
5 / 13
6 / 14
7 / 15
8 / 16


1312 14
RESISTORS NOT SUPPLIED
6.2k
ZONE 10
3k
ZONE 2
2k
2k
2k
ZONE 3
2k
2k
2k
ZONE 4
TAMPER
CONTACTS
TAMPER
CONTACTS
RECHARGABLE
BATTERY
(12V, 4AH)
SEALED LEAD
ACID TYPE
TRANSFORMER WIRE RUNS
"AC LOSS" DISPLAYED IF VOLTAGE FALLS BELOW 16.5VAC.
CONNECT THE TRANSFORMER TO TERMINALS 1 AND 2.
SEE WIRE RUN CHART.
Distance from control Wire Size
# 18
# 16
# 20
50 - 100 feet
100 - 200 feet
Up to 50 feet
HARDWIRE ZONES
ECP DEVICES
PLACE THE 12-VOLT BACKUP BATTERY IN THE CABINET.

AFTER ALL CONNECTIONS TO THE CONTROL ARE MADE AND
AC POWER HAS BEEN APPLIED, CONNECT THE RED AND
BLACK FLYING LEADS TO THE BATTERY.
ZONE DOUBLING
FA168CPS ONLY
FA168CPS ONLY
DOUBLE-BALANCED ZONE
FA168CPS ONLY
UL NOTE:
SET RECEIVER DEVICE ADDRESS TO "00" (SET SWITCHES TO
THE RIGHT, "OFF" POSITION).

MOUNT THE RECEIVER INSIDE THE CABINET OR REMOTELY
WITHIN A NOMINAL RANGE OF 200 FEET FROM TRANSMITTERS,
IN HIGH, CENTRALLY LOCATED AREA.

CONNECT THE RECEIVER'S WIRE HARNESS TO THE CONTROL'S
ECP TERMINALS. SEE RECEIVER'S INSTRUCTIONS FOR
ANTENNA MOUNTING, ETC.

INSTALL TRANSMITTERS ACCORDING TO THEIR INSTRUCTIONS.
FA148CP
26 TRANSMITTER ZONES: 9-34
8 BUTTON ZONES: 49-56
FA168CPS
40 TRANSMITTER ZONES: 9-48
16 BUTTON ZONES: 49-64
WIRELESS ZONE NUMBERS
DO NOT USE DOUBLE-BALANCED ZONES
OR ZONE DOUBLING FOR FIRE ZONES.
OPEN CIRCUIT DEVICES CONNECT IN PARALLEL ACROSS
THE LOOP; FOR EOLR ZONES, CONNECT THE EOLR
ACROSS THE LOOP WIRES AT THE LAST DEVICE.

CLOSED CIRCUIT DEVICES CONNECT IN SERIES IN THE
HIGH (+) SIDE OF THE LOOP; FOR EOLR ZONES, CONNECT
THE EOLR IN SERIES FOLLOWING THE LAST DEVICE.
1.



2.


PROVIDES TWO HARDWIRED
N.C. ZONES FOR EACH
STANDARD HW ZONE
(BUT DOES NOT INCREASE
TOTAL NUMBER OF ZONES
SUPPORTED. A SHORT ACROSS
THE EOL ON EITHER ZONE
CAUSES A TAMPER CONDITION.
ZONE NUMBERS USED FOR
DOUBLING CANNOT BE USED
FOR ANYTHING ELSE.
PROVIDES ZONE TAMPER
PROTECTION AND SHOULD BE
USED AS BURGLARY ZONES ONLY.
A SHORT ACROSS THE EOL
CAUSES A TAMPER CONDITION.
FOR UL COMMERCIAL BURGLARY ALARM INSTALLATIONS,
USE EOLR ZONES.
EOLR NOTE:
IF THE EOLR IS NOT AT THE END OF THE LOOP, THE
ZONE IS NOT PROPERLY SUPERVISED AND THE SYSTEM
MAY NOT RESPOND TO AN "OPEN" ON THE ZONE.
USE CAUTION WHEN WIRING
THE TRANSFORMER TO THE
CONTROL TO GUARD AGAINST
BLOWING THE TRANSFORMER
FUSE (THE FUSE IS
NON-REPLACEABLE).
SOUNDER CONNECTION
RF RECEIVERS & TRANSMITTERS
AC POWER AND BATTERY CONNECTION
1.

2.
PHONE CONNECTION
CONNECT PHONE LINE DIRECT
CONNECT CABLE WIRES TO
TERMINALS 21-24 AS SHOWN.
WIRE COLORS REPRESENT THE
COLORS OF THE CABLE TO THE
RJ31X JACK.

CONNECT INCOMING PHONE
LINE AND HANDSET WIRING TO
THE MAIN TERMINAL BLOCK
(VIA AN RJ31X JACK; CA38A IN
CANADA) AS SHOWN.
1.






2.
EARTH GROUND CONNECTION
KEYSWITCH WIRING CONNECTIONS
METAL COLD WATER PIPE: USE A NON-CORROSIVE METAL STRAP
(COPPER IS RECOMMENDED) FIRMLY SECURED TO THE PIPE TO WHICH
THE GROUND LEAD IS ELECTRICALLY CONNECTED AND SECURED.
AC POWER OUTLET GROUND: AVAILABLE FROM 3-PRONG, 120VAC
POWER OUTLETS ONLY. TO TEST THE INTEGRITY OF THE GROUND
TERMINAL, USE A 3-WIRE CIRCUIT TESTER WITH NEON LAMP
INDICATORS, SUCH AS THE UL LISTED IDEAL MODEL 61-035, OR
EQUIVALENT, AVAILABLE AT MOST ELECTRICAL SUPPLY STORES.
THIS CONTROL DOES NOT NORMALLY NEED AN EARTH GROUND. IF
DESIRED FOR ADDITIONAL PROTECTION, CONNECT TERMINAL 25 TO A
GOOD EARTH GROUND. EXAMPLES OF GOOD EARTH GROUNDS:
DEVICE ADDRESS DEVICE ADDRESS

KEYPADS 16 - 23 5800TM 28 (PART. 1 ONLY)

4219, 4229 07 - 11 COMM DEVICE 03

4204 12 - 15 4286 04

RF RECEIVER 00 TOUCH SCREENS FA148CP: 1, 2
KEYPADS AND ADDRESSABLE DEVICE CONNECTION
FA148CP_FA168CPS_quick-guide_CL
TRIGGER CONNECTOR
USED FOR 1361X10
TRANSFORMER
CONNECTIONS AND FOR
ON-BOARD TRIGGERS.
OUT 17 = 100mA MAX
OUT 18 = 20mA MAX
7 8
GND
+12 AUX
1 2 3 4 5 6
OUTPUT 18
(TRIG. 2)
OUTPUT 17
(TRIG. 1)
ZONE 1
HI
HI
LO
HI
LO
LO
2000 
OHMS
EOLR
2000 
OHMS
EOLR
ZONE 2
2000 
OHMS
EOLR
ZONE 3
HI
HI
LO
LO
2000 
OHMS
EOLR
ZONE 6 HI
HI
LO
LO
2000 
OHMS
EOLR
2000 
OHMS
EOLR
2000 
OHMS
EOLR
ZONE 4
ZONE 8
2000 
OHMS
EOLR
ZONE 7
ZONE 5
YELLOW
GREEN
RED
BLACK
YELLOW
GREEN
RED
BLACK
1.









2.
FOR SOUNDER SUPERVISION
BATTERY
TRANSFORMER
1.


2.



3.



4.
CONNECT SOUNDER TO BELL TERMINALS 3 (+) AND 4 (-).

SOUNDER ACTIVATES UPON ALARM EVENT.

ALARM OUTPUT: 10.5–13.8VDC, 2A MAX. (600mA MAX. FOR
UL USAGE, INCLUDING AUX POWER) STEADY FOR
BURGLARY/PANIC, TEMPORAL PULSE SOUNDING FOR FIRE.
UL: MUST BE A UL LISTED AUDIBLE SIGNAL APPLIANCE RATED
FOR 10.2-13.8 VDC AND BE MOUNTED INDOORS.

CAN USE ADEMCO No. 702 SIREN, OR 12V BELL.

A BATTERY MUST BE INSTALLED BECAUSE THE BATTERY
SUPPLIES THE CURRENT.
EXTERNAL ALARM SOUNDER
820 OHM
EOL
RESISTOR
OBSERVE
POLARITY
TERM 3
TERM 4
10.5-13.8VDC 600mA MAX.
(500mA MAX. FOR UL INSTALLATIONS)
OPTIONAL
1361X10
TO
TERMINALS
1 & 2 BLACK (SYNC)
BLUE (DATA)
PURPLE (COM)
7 8
1 2 3 4 5 6
ECP AUX POWER OUTPUT
SETTING KEYPAD ADDRESS
POWER UP THE KEYPAD. WITHIN 60
SECONDS OF POWER-UP, PRESS AND
HOLD DOWN THE [1] & [3] KEYS AT THE
SAME TIME FOR 3 SECONDS.
1.




2.






3.
ENTER THE PROPER "TENS" DIGIT OF
THE KEYPAD'S ADDRESS, THEN ENTER
THE PROPER "ONES" DIGIT OF THE
KEYPAD'S ADDRESS.
PRESS [ ] TO SAVE THE DISPLAYED
ADDRESS AND EXIT ADDRESS MODE.
4146 KEYSWITCH
(READY)
GREEN
LOCK
SWITCH (N. O.)
TAMPER
SWITCH (N. C.)
(ARMED)
RED
YELLOW
WHITE
2K OHM EOLR
11
10
TYPICAL ZONE
ON CONTROL
BOARD
BROWN
BLUE
BROWN
BLUE
820
ohms
820
ohms
STANDARD
KEYPAD
CABLE
+12 AUX. (RED)
OUTPUT 17 (YEL)
OUTPUT 18 (GRN)
RED
BLACK
SENSORS
(USE 1K EOLR)
4219/4229
EXPANDER
MODULE
RF
RECEIVER
COMMUNICATION
DEVICE
4204
RELAY
MODULE
KEYPAD
CONTROLLED
DEVICES
ARMED
READY
MESSAGE
TRIGGER CONNECTOR
NOTE: FIRST KEYPAD IS ADDRESS 16
DIRECT CONNECT CORD (620)
4-WIRE SMOKE DETECTOR CONNECTIONS
(+)
+
2000
OHMS
EOLR
HEAT
DETECTOR
RED
EOL
POWER
SUPERVISION
RELAY MODULE
EOLR-1.
USE N.O.
CONTACT,
WHICH CLOSES
WHEN POWER
IS APPLIED.
VIOLET
AUX PWR
OUTPUT
TERMINALS
5
4
_
_
+
BLK
_
( )
TO ZONE 2 8 TERM.
RELAY
CONTACT OPENS MOMENTARILY
UPON FIRE ALARM RESET
PROGRAM RELAY
AS ZONE TYPE 54
(FIRE ZONE RESET)
_
+
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
N.C. N.O.
TO OUTPUT 17
PROGRAM OUTPUT 17 FOR
"OUT NORM LOW" = YES IN
79 MENU MODE AND AS ZONE
TYPE 54 IN 80 MENU MODE
MAX. CURRENT = 100 mA
OR
IMPORTANT: THE PANEL WILL NOT POWER UP INITIALLY ON
BATTERY POWER ONLY. YOU MUST PLUG THE TRANSFORMER
IN FIRST, AND THEN CONNECT THE BATTERY.
UL: BELL SUPERVISION IS REQUIRED
FOR FIRE ALARM INSTALLTIONS.
ULC NOTE: THE RF SUPERVISION PERIOD FOR THE FA168CPS-CN
AND FA148CP-CN IS THREE HOURS FOR FIRE ZONES (ZT 9 AND 16)
AND 12 HOURS FOR ALL OTHER ZONE TYPES. FA168CPS: 1, 2, 5, 6
UL: PLC DEVICES AND 1361X10
ARE NOT UL LISTED FOR FIRE
OR BURGLARY FUNCTIONS
AND ARE INTENDED FOR
HOME AUTOMATION.
CANADA: USE PSC04.
SEE INSTALLATION INSTRUCTIONS.
UL: SEE INSTALLATION INSTRUCTIONS
FOR USAGE AND LIMITATIONS.
24 25
SPACE
SHIFT
N/ Y
BS/ESC
ENTER
STX
DEF
ABC
/
ARMED
READY
3
STAY
6
BYPASS
9
CHIME
#
4
7
5
TEST
8
CODE
0
2
AWAY
1
OFF
MAX
INSTANT
READY
ARMED
READY

R
89
7
0
*#
ABC
456
123
DEF
STX
SPACE ENTER
SHIFT
BS/ESC
/
N/Y
HOLD
DOWN
THREE
SECONDS
1321
(1321CN IN CANADA)
16.5VAC, 25VA, CLASS 2
PLUG-IN TRANSFORMER
BATTERY FUSE (IF INSTALLED)
FOR REPLACEMENT,
USE SAME VALUE
(e.g. ADEMCO No. 90-12)

FUSE NOTE
MAY HAVE PTC IN
PLACE OF FUSE.
3A
1.






2.
CONNECT KEYPADS AND OTHER ADDRESSABLE DEVICES TO ECP TERMINALS 4-7.
(SEE "SETTING KEYPAD ADDRESS BOX TO SET KEYPAD ADDRESSES.)
TOUCHSCREEN KEYPAD
(SEE TOUCHSCREEN
NOTE BELOW)
SET EACH MODULE'S ADDRESS ACCORDINGLY:
TOUCHSCREEN NOTE: TOUCHSCREEN KEYPADS MAY REQUIRE AN EXTERNAL
POWER SUPPLY DUE TO AUX POWER LIMITATIONS.
(USE SA4120XM-1 CABLE)
OPTIONAL
POWER
SUPPLY
10 11
IF BELL SUPERVISION IS
ENABLED ( 91 ENABLED)
CONNECT AN 820 OHM
RESISTOR ACROSS THE
EXTERNAL SOUNDER AS
SHOWN BY THE DOTTED LINE.
DO NOT CONNECT THE RESISTOR DIRECTLY TOTHE ALARM OUTPUT TERMINALS!

Other manuals for FA148CP Series

1

This manual suits for next models

1

Other First Alert Security System manuals

First Alert F250 User manual

First Alert

First Alert F250 User manual

First Alert CO606 User manual

First Alert

First Alert CO606 User manual

First Alert FA142C User manual

First Alert

First Alert FA142C User manual

First Alert FA1220C User manual

First Alert

First Alert FA1220C User manual

First Alert First Alert CO400 User manual

First Alert

First Alert First Alert CO400 User manual

First Alert ReadyGuard-R User manual

First Alert

First Alert ReadyGuard-R User manual

First Alert FA2100C User manual

First Alert

First Alert FA2100C User manual

First Alert CO600 User manual

First Alert

First Alert CO600 User manual

First Alert Hearing Impaired Strobe Lights SL177 User manual

First Alert

First Alert Hearing Impaired Strobe Lights SL177 User manual

First Alert ReadyGuard-RI User manual

First Alert

First Alert ReadyGuard-RI User manual

First Alert FA110C User manual

First Alert

First Alert FA110C User manual

First Alert FA168CPS Series User manual

First Alert

First Alert FA168CPS Series User manual

First Alert FA168CPS Series Operating instructions

First Alert

First Alert FA168CPS Series Operating instructions

First Alert FA1600C User manual

First Alert

First Alert FA1600C User manual

First Alert FA 270 User manual

First Alert

First Alert FA 270 User manual

First Alert ReadyGuard Touch User manual

First Alert

First Alert ReadyGuard Touch User manual

First Alert PC900V User manual

First Alert

First Alert PC900V User manual

First Alert FA140C User manual

First Alert

First Alert FA140C User manual

First Alert FA160C User manual

First Alert

First Alert FA160C User manual

First Alert CO600 User manual

First Alert

First Alert CO600 User manual

First Alert Onelink 1042136 User manual

First Alert

First Alert Onelink 1042136 User manual

First Alert ZCOMBO User manual

First Alert

First Alert ZCOMBO User manual

First Alert FA147C User manual

First Alert

First Alert FA147C User manual

First Alert FA1340C-UL User manual

First Alert

First Alert FA1340C-UL User manual

Popular Security System manuals by other brands

Abus FUSG50000 installation instructions

Abus

Abus FUSG50000 installation instructions

SPY Ball 6507 Fitting instructions

SPY Ball

SPY Ball 6507 Fitting instructions

Abus FUSG30000 quick guide

Abus

Abus FUSG30000 quick guide

AXA Remote 2.0 manual

AXA

AXA Remote 2.0 manual

Abus Security Center Eyseo TV7171 installation guide

Abus

Abus Security Center Eyseo TV7171 installation guide

M-TI CX FLEX 4A product manual

M-TI

M-TI CX FLEX 4A product manual

Abus TVAC15000 user manual

Abus

Abus TVAC15000 user manual

Qlight EMCL70 manual

Qlight

Qlight EMCL70 manual

Security Command XR20 Executive Series user guide

Security Command

Security Command XR20 Executive Series user guide

Co2meter CM-1029 installation manual

Co2meter

Co2meter CM-1029 installation manual

Q-See QH50DVR8C Quick installation guide

Q-See

Q-See QH50DVR8C Quick installation guide

Auto Page Professional Vehicle Security System... Operation manual

Auto Page

Auto Page Professional Vehicle Security System... Operation manual

HIK VISION DS-K2M060 user manual

HIK VISION

HIK VISION DS-K2M060 user manual

Co2meter RAD-0100 CALIBRATION PROCEDURE

Co2meter

Co2meter RAD-0100 CALIBRATION PROCEDURE

Abus Bordo 6000 Alarm manual

Abus

Abus Bordo 6000 Alarm manual

i3 International Veo17 user guide

i3 International

i3 International Veo17 user guide

Timeguard TG123SK Installation and operating instructions

Timeguard

Timeguard TG123SK Installation and operating instructions

C & K Systems 236i/L installation manual

C & K Systems

C & K Systems 236i/L installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.