Section 2 – Installing the Control
2-5
Installing External Sounders
The FA2000C provides one notification appliance circuit output rated 12VDC nominal (10-14VDC), 1A maximum, which
may be connected to 12V alarm indicating devices (horns, bells, sirens, etc.). This output may be configured for Style Y
EOLR supervision or no supervision and is intended for use as a supervised fire alarm indicating circuit.
•The bell output must be used for fire alarm annunciation when the FA2000C is used as a stand alone local
control. Unless otherwise specified by the local AHJ, use of the bell output is not required for all other DACT and
stand alone control installations. When used, the bell should be configured for supervision. 24 hour non-fire
alarms (ex. type 07) must be programmed to activate the auxiliary relay output and not the bell output.
•The total alarm current that can be drawn from the bell, auxiliary relay, and auxiliary power outputs combined
must not exceed 1A.
UL
•Commercial fire alarm systems require Notification Appliance Circuit to be supervised.
•This control complies with National Fire Protection Association (NFPA) requirements for temporal pulse
sounding of fire notification appliances.
Notification Appliance Circuit Supervision
When supervision is enabled, the FA2000C monitors the Notification Appliance Circuit wiring for open and short circuit
faults while the output is inactive. The system provides a trouble indication on Zone 6 (Zone 6 must be programmed for
a 24-hour response type) when an open occurs; or when a short occurs between the Bell (+) and Bell (-) terminal wiring,
or between the Bell (+) terminal wiring and earth ground.
Wiring the Alarm Output
The wiring of the Notification Appliance Circuit depends upon whether you are going to supervise the circuit
or not. Use the appropriate procedure below for your application.
ULUse only UL Listed sounding devices for UL installations.
Compatible Alarm Indicating Devices
SOUNDER TYPE MANUFACTURER MODEL # SOUNDER TYPE MANUFACTURER MODEL #
UL listed Grade A Bell in
Housing
Honeywell/ ADEMCO AB12M-ADT 4-Wire Ceiling Mount Horn/Strobe,
12/24V, Standard Candela, Red,
Outdoor
SYSTEM SENSOR PC4RK
RX7 UL Indoor Sounder, 12V ADT 875936B 4-Wire Ceiling Mount Horn/Strobe,
12/24V, High Candela, Red, Outdoor
SYSTEM SENSOR PC4RHK
Chime, 12/24V, Selectable
Tone & Volume, Red
SYSTEM SENSOR CHR 4-Wire Ceiling Mount Horn/Strobe,
12/24V, Standard Candela, White
SYSTEM SENSOR PC4W
Chime, 12/24V, Selectable
Tone & Volume, White
SYSTEM SENSOR CHW 4-Wire Ceiling Mount Horn/Strobe,
12/24V, High Candela, White
SYSTEM SENSOR PC4WH
Chime/Strobe, 12/24V,
Selectable Candela, Tone &
Volume, Red
SYSTEM SENSOR CHSR 2-Wire Wall Mount Strobe, 12/24V,
Standard Candela, Red
SYSTEM SENSOR SR
Chime/Strobe, 12/24V,
Selectable Candela, Tone &
Volume, White
SYSTEM SENSOR CHSW 2-Wire Wall Mount Strobe, 12/24V,
High Candela, Red
SYSTEM SENSOR SRH
Horn, 12/24V, Red SYSTEM SENSOR HR Wall Mount Strobe, 12/24V, Standard
Candela, Red, Outdoor
SYSTEM SENSOR SRK
Horn, 12/24V, White SYSTEM SENSOR HW Wall Mount Strobe, 12/24V, High
Candela, Red, Outdoor
SYSTEM SENSOR SRHK
Horn, 12/24V, Outdoor, Red SYSTEM SENSOR HRK Wall Mount Strobe, 12/24V, Standard
Candela, White
SYSTEM SENSOR SW
2-Wire Wall Mount
Horn/Strobe, 12/24V,
Standard Candela, Red
SYSTEM SENSOR P2R Wall Mount Strobe, 12/24V, High
Candela, White
SYSTEM SENSOR SWH
2-Wire Wall Mount
Horn/Strobe, 12/24V, High
Candela, Red
SYSTEM SENSOR P2RH Ceiling Mount Strobe, 12/24V,
Standard Candela, Red
SYSTEM SENSOR SCR