F-2833 - 9 - Technical Data Subject to alterations
due to heat transmission. To achieve this the duct must 
slope downstream and the wet air outlet must be 
placed as far as possible from the process air intakes, 
to avoid losses of performance.
5.4 Electric mains connections.
Attention: The dehumidifier works with 
medium electrical power and voltage and its 
connection to the mains must be done by 
qualified personnel and according to the 
applicable local electrical regulations.
The unit must be connected to the electrical network of 
the installation through a short circuiting and ground 
leakage protection line, with wires section/sensitivity as 
corresponds to the dehumidifier power.
5.5 Control equipment locations and 
connections.
The location and mounting instruction for the control 
equipment are normally specified by the corresponding 
supplier.
In case of On-Off Control using a Hygrostat you can 
choose between the complete unit switch off or the 
reactivation air heater switch off, as described before.
6. Start up.
6.1 Unit start up.
Once the ductwork has been completed and the 
equipment is connected to the electrical mains, as 
well as to the control equipment, proceed in this way:
Attention: Before using the control panel, 
verify that all mechanical elements can work 
freely and the unit has no installation d e b r i s 
inside.
»Checkthattheairflowregulationdampers,ifexist,are 
opened.
»Checkthathygrostatsetpoint-ifexists-isatleast10-
15% lower than environmental humidity.
»Checkthatelectricmainsisprotectedwithafuse 
adequate to the unit power.
»Switchontheunit.Integralpilotmustlight.Fanstarts 
operation and the ammeter reading reaches the upper 
limit due to the PTC heater consumption. PTC heater, 
like motors, have a consumption peak on starting 2 or 
3 times the normal consumption.
»Waitafewminutesallowingthedesiccantwheelto 
rotate several times until drying and regeneration 
processes are stabilized. Check that dry air 
temperature is lightly higher than the process air 
temperature, and the wet air temperature is higher 
than the dry air temperature. Adjust air flows to 
specific requirements of each application.
»Measureforeseenthermohygrometricparameters. 
To reduce the u nit capacity yo u ha ve to strangl e th e 
wet air stream, this automatically reduces 
consumption indicated by the ammeter.
6.2 Stopping the unit.
The equipment can be stopped manually or 
automatically.
Manual mode:
»Justoperatethecontrolswitchtoits"OFF"position.
Automatic mode:
»Theunitwillbeshut-offwhenjumperH2,showninthe 
wiring diagram, is open (this stops the unit totally). In 
case of opening jumper H1, the reactivation air heater 
is shut-off while the two motors keep on running.
Installation, Operation and Maintenance Manual
Desiccant Rotor Type Air Dehumidifiers DFRB series