flowair T-box User manual

T-box
MANUAL
INSTRUKCJA
РУКОВОДСТВО
ПОЛЬЗОВАТЕЛЯ
instrukcja obsługi / user manual / руководство пользователя / Betriebsanleitung

54 55
www.owair.com
Table of contents
Installation.....................................................................................................54
Navigation.....................................................................................................54
Technical data.............................................................................................55
First run............................................................................................................56
Main screen ..................................................................................................58
Main menu ............................................................................................. 58
Time............................................................................................................59
Date.............................................................................................................59
Calendar...................................................................................................59
Language.................................................................................................63
Integrated units...................................................................................64
Reset...........................................................................................................64
Antifreeze ................................................................................................65
Leading sensor.....................................................................................65
Controller lock......................................................................................66
External gas detector ....................................................................... 66
Information menu..............................................................................67
BMS..............................................................................................................67
LEO fan heaters.......................................................................................... 68
LEO EL fan heaters................................................................................... 72
KM mixing chambers ...........................................................................76
LEO D destraticators...........................................................................82
ROBUR gas heaters ................................................................................. 84
ROBUR mixing chambers ..................................................................86
ELiS air curtains ........................................................................................90
ELiS DUO air curtain-fan heater combo units....................92
OXeN heat recovery units .................................................................96
OXeN EL heat recovery units ....................................................... 100
Alarms............................................................................................................ 103
T-box controller has a built-in sensor for measuring air
temperature in the room. To ensure proper measure-
ments, the controller should be installed at a height of
approx. 1.5 m above the ground in a place with good air
circulation. Do not place it near heat sources, lighting, air
inlets, windows and door openings, etc.
If temperature sensor was chosen in a T-Box menu as
„installed in unit”, T-box controller can be mounted out
of area i.e. technical room.
Installation
12
return to previous screen with
save of changes
change of parameter value
change of unit group
return to previous screen without
save of changes
menu navigation
Navigation

55www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
Technical data
Name Description
Power supply 24 VDC
Way of control touch screen
Temperature adjustment range
+5 ÷ +45°C
Operating temperature range 0 ÷ +60°C
Temperature sensor built-in
Protection degree IP20
Installation on the wall
Casing ABS plastic, RAL 9003
Max. number of connected
units 31
Dimensions (HxWxD) 130 x 115 x 35 mm
Installation DRV - SW1 ADDRESS SETTING
DRV - SW2 ADDRESS SETTING
BMS
GND
B A
SW1
RESET
SW1
T120
T-box
GND
B A VCC
max. 50 m
VCC
GND
A
T- box
B
In the case, when T-box in BMS network is the
last device, SW1 switch should be set in T120
position. Last DRV
in line
Others DRV
in line
SW1
1
0
1 2 4 8 16 Y1
SW
T120
LIYCY-P min. 2x2x0,5 mm2
A and B braided wire pair
screen
1 2 4 8 16 Y1
1
0
Adress:1
1 2 4 8 16 Y1
1
0
Adress: 2
1 2 4 8 16 Y1
1
0
Adress: 3
1 2 4 8 16 Y1
1
0
Adress: 4
1 2 4 8 16 Y1
1
0
Adress: 5
1 2 4 8 16 Y1
1
0
Adress: 6
1 2 4 8 16 Y1
1
0
Adress: 7
1 2 4 8 16 Y1
1
0
Adress: 8
1 2 4 8 16 Y1
1
0
Adress: 9
1 2 4 8 16 Y1
1
0
Adress: 10
1 2 4 8 16 Y1
1
0
Adress: 11
1 2 4 8 16 Y1
1
0
Adress: 12
1 2 4 8 16 Y1
1
0
Adress: 13
1 2 4 8 16 Y1
1
0
Adress: 14
1 2 4 8 16 Y1
1
0
Adress: 15
1 2 4 8 16 Y1
1
0
Adress: 16
1 2 4 8 16 Y1
1
0
Adress: 19
1 2 4 8 16 Y1
1
0
Adress: 20
1 2 4 8 16 Y1
1
0
Adress: 21
1 2 4 8 16 Y1
1
0
Adress: 22
1 2 4 8 16 Y1
1
0
Adress: 23
1 2 4 8 16 Y1
1
0
Adress: 24
1 2 4 8 16 Y1
1
0
Adress: 25
1 2 4 8 16 Y1
1
0
Adress: 26
1 2 4 8 16 Y1
1
0
Adress: 27
1 2 4 8 16 Y1
1
0
Adress: 28
1 2 4 8 16 Y1
1
0
Adress: 29
1 2 4 8 16 Y1
1
0
Adress: 30
1 2 4 8 16 Y1
1
0
Adress: 31
1 2 4 8 16 Y1
1
0
Adress: 17
1 2 4 8 16 Y1
1
0
Adress: 18
SW2
T120
SW2
T120
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1
DRV control module

56 57
www.owair.com
First run
active language
Searching of connected units.
Selection of language Setting of date
Setting of time
DevicesTime
DataLanguage
13PM
August

57www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
12:55PM
Devices
Verify if all units have been
found. If not, check:
• correct connection of communication signal
A-A, B-B,
• power supply of the unit,
• correct setting of addresses, each unit must have
dierent address,
• if in the last unit dip-switch SW2 is set in T120 position.
Setting of desired temperature.group of devices
water heater
gas heater
electric heater
destraticator
ventilation unit
water heater with
mixing chamber
gas heater with
mixing chamber
air curtain-fan heater
combo unit
air curtain
device no 8 in LEO
group
LEO
LEO KM
LEO
EL DUO
LEO
DELiS
OXeN
ROBUR
ROBUR
KM

58 59
www.owair.com
Main screen Main menu
long press turn on/off of the controller
long press main menu
short press units menu
alarms
setting of desired temperature time
setting antifreeze
date
setting
selection of
leading sensor
calendar controller lock
language selection
integrated units hardware
version
restore factory settings BMS settings
set temperature
measured temperature
date, time
settings lock active
BMS mode active
calendar active
calendar active - settings forced
icon informs that the OXeN dampers
position is changing, fan are stopped
Enter to the menu after entering the
password: 2014
long
press
external gas
detector
settings
4:05PM
12:55PM General settings

59www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
Time Calendar
Date
Setting of time
Setting of date
• For each day you can set up to 20 on/o events,
• Start time of new event is also the end time of previous event,
• For each event you can set any temperature for units, in the
range of 5 – 45oC,
• For each event you can set for KM an air ow and dampers
opening degree, for OXeN an air ow,
• Events for each day can be set individually or can be copied
from day, which was already set.
Activation of calendar is signalized on main screen via
following icons:
There were ad hoc set other parameters than
the settings programmed in the calendar:
• desired temperature,
• air ow for OXeN,
• air ow or dampers opening degree for KM,
• system were OFF and was turned on (to turn
on the system press and hold for 2 s the
calendar icon on main screen),
• system were ON and was turned o (to turn
o the system press and hold for 2 s the
calendar icon on main screen).
Ad hoc settings stays as long as time of current
event in calendar. With start of next event,
units will operate according to programmed
settings.
calendar active – SYSTEM ON
calendar active – SYSTEM OFF
calendar active – settings forced.
Date
Time
13PM
August

60 61
www.owair.com
Calendar – Adding the ON event
In given example SYSTEM will be turned on at 6:15 and
the units will maintain temp. 12oC.
SYSTEM WILL OPERATE USING CURRENT SETTINGS UNTIL
NEW EVENT WILL BE SET.
KM – additional settings for KM group
OXeN – additional settings for OXeN group
activation/deactivation of calendar
moving to the next day
adding the event
event – system ON
copying events on the following days
event – system OFF
removing the events
Calendar
Weekly programer
New task
Weekly programer
Monday
4:15AM
7:00AM
11:30PM
4:00PM 6:00PM Tue
7:00AM
9:00AM

61www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
For OXeN it is possible to set an air ow in current event.
For KM it is possible to set an air ow and dampers
opening degree in current event.
When the dampers are closed (no ventilation), it
is possible to select the operating mode of the
fan after reaching desired temperature. Fan can
operate continuously or be turned o.
Weekly programer
OXeN
Weekly programer
KM

62 63
www.owair.com
Calendar – Copying events
day from which events will be copied
day selected for copying events from PN day
day with already programmed operation
schedule – you can also copy here the events
from PN day
day without programmed operation schedule
Calendar – Adding the OFF event
In given example units will be turned o at 16:00.
SYSTEM WILL BE TURNED OFF UNTIL THE NEXT EVENT,
ACCORDING TO CALENDAR SETTINGS.
Weekly programer
Copy
Weekly programer
New task
Mon ThuTue
SatFr
4:00PM Wed
Sun

63www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
Calendar – Removing events Language
events selected
to remove conrmation of
events removal active language
Language
Weekly programer
Delete task
7:00AM
8:15PM
9:15AM9:00AM
10:00PM
4:00PM 4:15PM 7:00PM
Tue

64 65
www.owair.com
Integrated units Reset
searching for units integrated with system
active
unit
deactivated unit
– not operating
Restore default settings.
Reset to default settings?
Yes No
Devices
long press displays the DRV software
System information
LEO M 01
CURTAIN MAIN
DRV-V 2.1
2.0.0-2d-....

65www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
The correction of sensor measurements is also possible.
Antifreeze Leading sensor
Automatic protection against too low temperature in
the room. When temperature in the room drops below
desired temperature, LEO and KM units are turned on:
• valves (if installed) opens,
• fan is turned on at 100% of eciency,
• KM dampers are closed, unit operates using recirculating air.
Units operate until the temperature in the roomis higher
of 1oC than antifreeze temperature, protecting the hall
against too low temperature inside and freeze of heating
medium in the exchanger.
active temperature sensor
leading sensor is the sensor built
in T-box controller
leading sensor is the local sensor. When it is
selected, operation of each unit is regulated
locally
Temperature sensor

66 67
www.owair.com
External gas detector
SYSTEM enables cooperation with external detectors
of CO2sensors, humidity sensors etc. – two-step alarm
signal. Air ow setting of KM and OXeN and dampers
settings of KM will be automatically changed depending
on alarm signal.
Detectors should be connected to one of the DRV KM or
DRV OXeN control module.
It should be noted in the menu to which DRV module
detectors is connected.
In given example detectors is connected to DRV KM
no. 7.
Controller lock
To activate the lock:
1. Set password
2. Conrm OK
Free 4-digit password can be set.
After returning to main screen and 30s of inactivity,
controller will be locked automatically.
Gas detector
Controller lock

67www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
System information BMS – settings
Basic information about software and hardware version.
ID – setting unit adress: from 1 to 247
BAUD – setting data transmission speed: from 9600 to
230400 bit/s
Physical layer: Modbus RTU
Protocol: RS485
System information

68 69
www.owair.com
LEO-type fan heaters
air ow setting – 3-steps
selection of operating mode
readings
destratication
short
press Operating modes
heating – heating medium valve is opened when
measured temperature is lower than desired
temperature
cooling – heating medium valve is opened when
measured temperature is higher than desired
temperature
ventilation – valve is constantly closed, fan
operates continuously at selected speed
Manual – fan operates with constant, selected
speed
Auto – automatic fan regulation depending on
desired and measured temperature
active operating mode
Operating modeSettings

69www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
Operating modes Air ow setting
air ow setting during operation in manual mode Automatic air ow regulation according to desired and
measured temperature, manual air ow regulation is not
possible - inactive menu.
In MANUAL mode after reaching desired
temperature fan can operate continously on
selected step: 1, 2, 3 or be turned o - select OFF.
SettingsSettings
In AUTO mode after reaching desired temperature
fan can operate continously on selected step: 1, 2, 3
or be turned o - select OFF.
Airow AUTO

70 71
www.owair.com
heater activated for operation in
destratication mode
activation of destratication mode
setting of temperature dierence (dierence
between temperature under the ceiling and
temperature in the occupied zone), at which
LEO heaters will be turned on
selection of heaters, which should operate in
destratication mode
LEO heaters can optionally operate in destratication
mode (only heaters installed under the ceiling). When
the measured temperature drops to the set temperature
only fan starts. When the heat under the ceiling is not
enough, and the temperature continues to decline
(-1oC from the setpoint) valve will open.
The heater must be equipped with T3 sensor (optional
equipment).
Destratication
DestraticationDestratication

71www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
Readings
Temperature
under the
ceiling
ON/OFF
valve
Temperature in
the room
To read temperatures near the unit, external tempera-
ture sensors PT-1000 must be connected to DRV control
module.
Readings

72 73
www.owair.com
Electric heaters
LEO EL
short
press Operating mode
LEO EL
Settings
air ow setting – 3-steps
heating power setting
selection of operating mode
heating
ventilation – heaters are OFF, fan operates
at selected speed continuously
automatic fan and heaters power
regulation depending ondesired
and measured temperature
manual regulation of airow
and heaters power
readings
destratication
LEO EL
Operating mode
active operating mode
Other manuals for T-box
3
Table of contents