ELECTRICAL ACTUATORSFlowCon FN.0.3 actuator
FlowCon International assumes no responsibility
for mistakes, if any, in any printed material.
Denmark Dubai USA Singapore www.owcon.com
1B95071 - 04/2016
- 2 -
Figure 9: Dip switch factory settings (ON-OFF).
Black
Power 110/230V AC
Ground/common
White
Red
Open
FN.0.3 Actuator
Close
Figure 5
FlowCon FN.0.3 Actuator
2-Position, Normally Closed
Black
Power 110/230V AC
Ground/common
White
Red
Open
FN.0.3 Actuator
Close
Figure 6
FlowCon FN.0.3 Actuator
2-Position, Normally Open
Black
Power 110/230V AC
Ground/common
White
Red
Open
Stop
FN.0.3 Actuator
Close
Figure 7
FlowCon FN.0.3 Actuator
3-Point-Floating, Normally Closed
Black
Power 110/230V AC
Ground/common
White
Red
Open
Stop
FN.0.3 Actuator
Close
Figure 8
FlowCon FN.0.3 Actuator
3-Point-Floating, Normally Open
Actuator wiring
The wiring diagrams for FlowCon FN.0.3 is
shown in figure 5-8.
Dip switch settings
Lift the silicone cap on the back of the actuator to
get access to the dip switches (figure 9).
Dip switch no. 1- Rotation direction:
OFF - Normally open.
ON - Normally closed.
Dip switch no. 2 - NA:
This dip switch is not in use.
Removing actuator / Manual override
operation
To disengage the actuator or perform manual
override, please turn off the power supply and
press the release button while turning the top
part of the actuator counter clockwise 30° (figure
2, previous page).
The piping network can now be tested if neces-
sary by manually adjusting the valve adaptor
knob.
IMPORTANT: FlowCon FN.0.3 actuator and
FN.0.3 valve adaptor are not custom made
as a pair from the supplier, which means that
a FN.0.3 actuator can be used with any FN
valve adaptor with green indicators. Using
other models of valve adaptors may cause
valve damage.
Warranty obligation
Failure to abide by all recommendations as per
this installation and operation instruction will void
warranty.
For latest updates pls. see www.flowcon.com