CONFIGURING ECHOPOD®
EchoPod® is configured through WebCal®, a PC software program. Configuration of your sensor should be
performed prior to mounting, since it requires connection to your PC.
STEP 1: INSTALL WEBCAL® SOFTWARE
Download WebCal® software from www.flowline.com/webcal-software onto a PC with the following minimum
specifications:
Windows® 2000/XP/Vista/7/8/10, 32 or 64-bit system, 10 MB storage space, 256 MB RAM, 1 USB® 2.0 port
You must have an active Internet connection to download WebCal®. Double-click the WebCal® installer to
install software before proceeding to Step 2. Installer program will automatically install any required drivers.
STEP 2: CONNECT THE USB® FOB
NOTE: Do not connect the Fob to your computer until after you’ve installed WebCal® software.
The sensor communicates to WebCal® through the USB® Fob. Prior to plugging the Fob into your computers
USB® port, ensure that all external power is disconnected from EchoPod®. The maximum distance between
the computer and EchoPod® is 15’.
1. Connect the red, green, white, and black
wires from the EchoPod® to the
corresponding colored terminals on the
Fob.
2. Tighten the terminal screws with a slotted
screwdriver.
3. Plug the Fob into your PC’s USB® port.
Wiring identical for all series – Use only the Red,
Black, Green and White wires.
STEP 3 - MEASURE THE TANK
Measuring the tank is one of the most important aspects
in configuring the sensor. When measuring the tank,
take into account the location of the sensor with respect
to fittings, risers, dome tops and bottoms, and identify
where the measurements are taken from the sensor.
The HEIGHT and FILL-H settings determine the 4-
20mA span and are always measured from the bottom
of the tank up.
Relay set points will always be measured from the
bottom of the tank up, regardless of the function of the
relay (Pump, Valve, Alarm or Independent Relay).