
12 of 13 DeltaSpan (IS) LD31 / LD32 Series 31 MAR 11
MN301031 Rev C
Installation
The LD31 / LD32 series is designed to operate while submerged in the actual application
liquid. Avoid installing the level transmitter along the bottom of the tank is materials
such as sludge will build up and coat/cover the transmitter. This also includes any debris
that will settle along the bottom of the tank. In these applications, it is best to suspend
the transmitter above the highest level of sludge/debris that will occur.
1. Location: Select a location where the temperature of the transmitter will be
between 0 and 176°F (-18 to 80°C). Distance from the receiver is limited only by total loop resistance.
2. Position: The transmitter is not position sensitive. However all standard models are originally calibrated
with the unit in a position with the pressure connection downward. Although they can be used at other
angles, for best accuracy it is recommended that units be installed in the position calibrated at the
factory.
3. Mounting: The transmitter can be mounted via several methods. It can be suspended from the electrical
cable, it can be placed resting on the bottom of the tank in either horizontal or vertical orientation, or it
can be attached to a pipe or hang wire by the 1/2˝ NPT male connection on the top of the housing.
Interference
The DeltaSpan is designed to operate under the surface of the liquid in the tank. Avoid
installations where other tank requirements will cause the transmitter to move or swing.
For example: a mixer blade could cause the level transmitter to whip around within the
tank. An alternative would be to move the transmitter to a more stable section of the tank
or to install the LD31 series inside a still well/drop tube. The still well/drop pipe will
minimize the effects created by the mixer.
Termination
The cable for the DeltaSpan is typically terminated at a junction box located on top of the
tank. Since the vent tube is contained within the cable, the pressure within the junction box
must always be the same as the reference (typically atmospheric) pressure for the liquid.
The inside of the junction box must be clean, dry and free of moisture. Add the optional
pressure fitting (LD90-_001) to complete the package. The LD90-_001 features a 2” NPT
thread for mounting and a liquid tight connector to seal the cable interface.
Note: Use caution when sealing the cable at the top of the tank. The ventilation tube must
be open and free to allow air to flow back to the pressure diaphragm. Avoid blocking the
ventilation tube by compressing the cable. Always keep the cable termination clean, dry
and free of moisture and prevent liquid from entering the vent tube.
Maintenance
After final installation of the pressure transmitter and its companion receiver, no routine maintenance is
required. A periodic check of system calibration is suggested. The pressure transmitters are not field repairable
and should be returned if repair is needed (field repair should not be attempted and may void warranty). Be sure
to include a brief description of the problem plus any relevant application notes. Contact customer service to
receive a return goods authorization number before shipping.
Maintenance should consist of inspection to see that the transmitter is free from debris and not coated with any
substance, which would prevent liquid from freely entering and leaving the transmitter. If this occurs, the
transmitter should be cleaned.