Flowserve PMV PS Ultraswitch User manual

USER INSTRUCTIONS
Installation
Operation
Maintenance
PMV PS/PM Ultraswitch™
Switchbox
FCD PMENIM0008-02 - 08/14

32
1. GENERAL INFORMATION
PSPM Ultraswitch™ enclosures provide local and remote position indication for automated valves. They ge-
nerally feature a visual black/yellow or red/green indicator for intuitive local position determination. The PSPM
Ultraswitch™ is available with a number of limit switch options for remote indication, in a variety of electrical
applications. They may also be used as a junction box for direct installation of solenoid valves.
2. SAFETY INSTRUCTION
Read the safety instructions in this manual carefully before using the product. If any questions arise during
installation, contact supplier/sales office before continue working.
This equipment is suitable for use in class (as applicable), division 2, groups (as applicable) or non-hazardous
locations only.
Report transport damage to the carrier immediately. In case of discrepancies - contact your nearest
FLOWSERVE location.
3. UNPACKING
1. GENERAL INFORMATION .........................................................................................................................3
2. SAFETY INSTRUCTION.............................................................................................................................3
3. UNPACKING..............................................................................................................................................3
4. CERTIFICATES..........................................................................................................................................4
5. SPECIFICATIONS......................................................................................................................................4
5.1 Technical data.........................................................................................................................................4
5.2 Materials of construction ........................................................................................................................4
5.3 Type sign ................................................................................................................................................4
5.4 PS/PM UltraSwitch™ nomenclature.......................................................................................................5
5.5 PS/PM UltraSwitch™ switch options ......................................................................................................6
6. INSTALLATION .........................................................................................................................................8
6.1 Wiring instructions ..................................................................................................................................9
7. SWITCHES (Certified) ............................................................................................................................10
7.1 ATEX EEx e mb certificate info...............................................................................................................10
7.2 Installation in hazardous locations ........................................................................................................10
7.3 Adjusting limit switches ........................................................................................................................10
7.4 Cam fine adjustment ............................................................................................................................11
7.5 Adjusting UltraDome™ position indicator..............................................................................................11
7.6 Calibrating 4-20 mA transmitter............................................................................................................11
7.7 Switch option specifications (all) ...........................................................................................................12
7.8 Analog feedback option specifications...................................................................................................13
8. DIMENSIONS..........................................................................................................................................14
9. SPARE PARTS ........................................................................................................................................15
CONTENTS
• Substitution of components may impair suitability
for Div. 2 locations.
• Inspect periodically for degradation. Replace parts
if degradation is found.
• Cleaning this housing by rubbing should be done in
a non-hazardous area.
• Potential electrostatic charging hazard, clean only
with a damp cloth – danger of propagating discharge.
• All grounding and bonding installation requirements
must be addressed.
• Pay attention to personal protection, (clothing, glas-
ses, gloves) when performing installation or service.
• Use only Flowserve original spare parts not to
invalidate certification.
• All installation, inspection, and maintenance of the
equipment should be performed by suitably trained
personnel. In addition, for ATEX, all installation, in-
spection, maintenance and repair must be done by
suitably trained personnel. For more information refer
to EN 60079-14:1997, EN 60079-17, EN 60079-18,
EN 60079-19.
• For ATEX Ex e mb certied units the unit must also
be placed in an area where it is low risk of mechanical
danger.
• Do not disconnect equipment unless area is known
to be non-hazardous.
• To prevent ignition of ammable or combustible
atmospheres, disconnect power before servicing.
FCD PMENIM0008-02 - 08/14 FCD PMENIM0008-02 - 08/14

54
5.4 PS/PM UltraSwitch™ nomenclature
4. CERTIFICATES
ATEX II 1G Ex ia IIC T4/T5/T6
IEC Ex ia IIC T4/T5/T6
ATEX II 2 G Ex e mb IIC T6
cFMus IS Class I,II,III Division 1 Group A,B,C,D,E,F,G
cFMus NI Class I Division 2 Group A,B,C,D; Class II Division 2 Group E,F,G; Class III Division 1&2
cCSAus Class I, Division 1 Groups A,B,C,D; Class II Division 1 Groups E,F,G; Classs III
cCSAus Class I, Division 2, Groups A,B,C,D; Class II, Division 2, Groups E,F,G; Class III
All certificates available for
download at www.pmv.nu
5. SPECIFICATIONS
5.1 Technical data
Ingress protection IP66 & Type 4x Weight 1 kg / 2.2 lbs
5.2 Materials of construction
Part Material
Housing/Cover PA6/PA66 Nylon 25% - 33% Glass Filled Engineered Resin
Shaft Stainless Steel
Cams/Splines Nylon
Terminal Block Nylon – Buchanan TBS Series
Internal Brackets Stainless Steel or Plated Steel
All Internal Fasteners Stainless Steel or Plated Steel
All External Fasteners Stainless Steel
All Molded in Fasteners Anodized Aluminum
UltraDome™ Polycarbonate
Rotor Polycarbonate
5.3 Type sign
Product name and model code
Warnings
Year of manufacture
S/N: XXXXXX
Manufacturer
Electrical rating
Serial number
Logotype
WARNING
POTENTIAL ELECTROSTATIC CHARGING HAZARD
SEE INSTRUCTIONS
POWER SOURCE MUST BE PROTECTED BY A FUSE
OF 3 A WITH BREAKING CAPACITY ≥ 1500A
Model code
Type sign for
Atex Ex e mb
PALMSTIERNA INTERNATIONAL AB, SOLNA, SWEDEN
S/N:
IP 66/Type 4X
DATE:
0470
Cl. I Div.2 Gr. A-D T6
Cl. I Div.2 Gr.A-D T4-6
Cl. II Div.2 Gr. E-G
Cl. I Div.1 Gr.A-D T5
Cl. II Div.1 Gr. E-G
Cl. III
NON INCENDIVE
Cl. II Div.2 Gr. E-G T6
II 1 G
11ATEX1065X
NEMKO
Ex ia IIC T4-T6 Gb
REFERENCE TO CONTROL DWG NO. RA-2 FOR SAFE USE
SAFTY AND SUITABILITY FOR DIVITION 2.
Div. 1,Gr A-G,T4-T6
CLASS I,II&III
INTRINSIC SAFY
SUBSTITUTION OF COMPONENTS MAY IMPAIR INSTRINS IC
Cl.III Div.1&2
WARNING:
POTENTIONAL ELECTROSTATIC CHARGING HAZARD- SEE
INSTRUCTIONS.
INTRINSIC SAFY
NON INCENDIVE
IECEx
NEM 11.0012X
*If the equipment is likely to come in contact with aggressive substances, it is the
responsibility of the user to take suitable precautions to prevent it from being
adversely affected, thus ensuring that the type of protection provided by the
equipment is not compromised.
A. Brand sticker P PMV
B. Shaft N NAMUR VDI/VDE 3845
D Double D 1/4”
C. Connections (cable entry) PS Engineered Resin Housing 1/2 NPT
PM Engineered Resin Housing M20x1,5
PN Engineered Resin Housing 3/4 NPT
PG Engineered Resin Housing M25x1,5
D. Number of cable entries 1 1 conduit
2 2 conduits
3 3 conduits
E. Indicator option 1 Flat cover without indicator
U Standard UltraDomeTM red/green
C 90 deg 3-way UltraDomeTM
D 180 deg 3-way UltraDomeTM
E 180 deg 3-way Centre-blocked UltraDomeTM
F 120 deg Thru/Divert UltraDomeTM
H Black/Yellow UltraDomeTM
K Ektar UltraDomeTM (red/green)
R Reverse UltraDomeTM (red=open / green=closed)
X 180 deg 3-way UltraDomeTM (white/blue)
F. Switch quantity 0 No Switches
2 2 Switches
4 4 Switches
G. Switch options options See page with switch options
H. Certificate 14 General Purpose
15 ATEX II 1G Ex ia IIC T4/T5/T6
21 IEC Ex ia IIC T4/T5/T6
22 ATEX II 2 G Ex e mb IIC T5/T6
27 FM IS Cl. l Div. 1 Grp. A, B, C, D; T4
28 FM NI, CSA NI Cl. l Div. 2 Grp. A, B, C, D, D
40 ATEX Ex ia, FM IS, CSA IS, IEC Ex ia
60 ATEX Ex ia, FM IS, CSA IS, IEC Ex ia, FM NI, CSA NI
I. Analog output 0 None
T 4-20 mA transmitter
D 180 deg 4-20 mA transmitter
A 0-1K Ohm Potentiometer
J. Wiring options 0 None
3 Brad Harrison Connectors - 7 pins
4 Weidmüller special AKZ 2,5
H Heavy Duty Terminal Block
K. Minimum extra terminals 2 2 Open Terminal Locations (Standard)
4 4 Open Terminal Locations (2 SPST switches)
6 6 Open Terminal Locations (2 SPDT switches)
8 8 Open Terminal Locations (2 or 4 SPST switches)
L. Special options 0 None
V Viton O-rings
FCD PMENIM0008-02 - 08/14 FCD PMENIM0008-02 - 08/14

76
5.5 PS/PM UltraSwitch™ switch options
A = brand, NAMUR shaft, Resin housing, 2 conduits, stadard UltraDome™, 2 proximity switches, ATEX certificate,
2 terminals.
Code Cert. Switch Option Manufacturer Load Capacity
M1 SPDT Mechanical Honeywell
MicroSwitch
15A @ 125/250 VAC; 0,5A @ 125 VDC;
0,25A @ 250VDC; 5A @ 120VAC
MG A, B, D, F SPDT Gold Mechanical Honeywell
MicroSwitch
1A @ 125 VAC; 50 mA @ 24 VDC
MA 3-Position Control Honeywell
MicroSwitch
15A @ 125 VAC; 0,5A @ 125 VDC;
0,25A @ 250VDC; 5A @ 120VAC
M3 DPDT Mechanical Cherry 15A @ 125/250 VAC
MB DPDT Mechanical Licon 10A @ 125 VAC
MD 3-Pos. Control
with Indication (DA)
Licon 10A @ 125 VAC
MS 3-Pos. Control
with Indication (SR)
Licon 10A @ 125 VAC
P4 A, B, D, E, F, G SPST Proximity Aleph 0.35A @ 140 VAC; 0.25A @ 200VDC (50
W Max.)
P5 A, B, D, E, F, G SPDT Proximity Hamlin 0.25A @ 120 VAC; 0.25A @ 28 VDC (3
W Max.)
PE A, B, D, E, F, G SPDT Sabre Proximity Flowserve 1A @ 120 VAC; 1A @ 24 VDC
PP C, E, G SPDT Phazer Proximity Flowserve 3A @ 120 VAC; 2A @ 24 VDC
PT A, B, C, D, E,
F, G
SPST BRS Proximity Flowserve 3A @ 120 VAC; 0.5 @ 24 VDC
N8 A, B, D, E, F Solid State Proximity PF NJ2 V3 N NAMUR NC Sensor; 8 VDC
NP A, B, D, F Solid State Proximity PF SJ3.5-N NAMUR Sensor Output; 5-25 VDC
Supply
NQ A, B, D, F Solid State Proximity PF NJ4-12GK-N NAMUR NC Sensor; 8 VDC
NR D, F Solid State Proximity PF NJ4-12GM40-E1 PNP Sinking; 200 mA max. Current;
10-60 VDC
NS D, G Solid State Proximity PF NJ4-12GM40-E2 NPN Sourcing; 200 mA max. Current;
10-60 VDC
NT D, G Solid State Proximity PF NJ4-12GK40-E2 NPN Sourcing; 200 mA max. Current;
10-60 VDC
N9 Solid State Proximity PF NBB3-V3-Z4 NPN Sourcing; 100 mA max. Current;
5-60 VDC
NW A, B, D Solid State Proximity PF SJ3.5-SN NAMUR NC Sensor; 8 VDC
Notes
1) MA switch element must be ordered with qty. (2) switch elements. MD and MS switch
elements must be ordered with qty. (4) switch elements.
2) Valid certification codes according to table in PS/PM Nomenclature on page 5 and 6.
3) Some models have more than (2) open terminal locations open as standards. Consult
factory for details.
4) Heavy Duty Terminal blocks only available for two (2) SPST or two (2) SPDT type switches
maximum (8 terminal points maximum).
Code Certificate
A ATEX II 1G Ex ia
B IEC Ex ia
C ATEX II 2 G Ex e mb
D cFMus IS
E cFMus NI
F cCSAus IS
G cCSAus NI
FCD PMENIM0008-02 - 08/14 FCD PMENIM0008-02 - 08/14
Ordering code example
A B C C D E F G G H H I J K L
P N P S 2 U 2 N 8 - 1 5 - 0 0 2 0
More switch options available

98
PS/PM switch mounted on rotary actuator
PS/PM switch mounted on linear actuator
Hex. screws
M5 x 8
6. Installation
The PS/PM Ultraswitch™ may be installed to valves or
valve actuators with a variety of mounting hardware.
For best results, specify the NAMUR shaft option
and NAMUR mounting hardware when installing to
NAMUR compliant actuator. These options allow direct
coupling to actuators without couplings, reducing
dead band.
Simply bolt bracket to actuator and PS/PM
Ultraswitch™ to bracket, leaving bolts finger tight.
For NAMUR applications the PS/PM Ultraswitch™
switch shaft features an integral alignment pin. This
pin must engage the tapped hole in the actuator shaft.
For non-NAMUR applications, make sure to properly
install a coupler between the PS/PM Ultraswitch™ and
actuator. Once the PS/PM Ultraswitch™ is installed
with fasteners loosely tightened, stroke the actuator
two or three times to align the bracket. Then tighten
all fasteners.
Ambient temperature working conditions
The PS/PM Ultraswitch™ switch box is tested and
operational in following temperature range:
-40° – 180°F
-40° – 80°C
6.1 Wiring instructions
• Perform all wiring according to the wiring
diagram found on the label in the switch cover
(see picture) and instructions given below.
• Make sure that the ground wire is correctly
connected
• Seal unused entries with proper and suita-
ble conduit plugs.
The PS/PM Ultraswitch™ enclosures feature pre-
wired switches. All user connections are made at a
numbered terminal strip. Both external bonding and
internal grounding locations have been provided for
use in installation. A wiring diagram is located inside
the cover and indicates which terminal numbers
correspond to switch contacts: normally open, nor-
mally closed, common, etc. Simply follow the wiring
diagram, and electric code to connect switches to
your system.
For field wiring: ensure that any excess wire lengths
or loops are routed away from any moving parts
and are short enough, or secured to ensure a 1/4”
clearance between the wire and the inside surface of
the switchbox cover.
Note: for all magnetically tripped proximity switches,
the top switch (top and third switches for 4-switch
versions) should only be used to indicate the clock-
wise position: the bottom switch (second and fourth
switches for 4-switch versions) should only be used to
indicate the counter-clockwise position.Any deviation
from these settings may result in erratic indication.
Solenoids may also be wired through the PS/PM
Ultraswitch™ enclosure. At least two auxiliary
terminals are included as standard.
A ground screw is also included. Simply wire the
solenoid to auxiliary terminals, then connect power
leads to the opposite terminal side. be sure to properly
ground the solenoid at provided ground terminal.
PS/PM UltraSwitch™ Series enclosures include two
3⁄4” NPT conduit entries and the PM Series includes
two M25x1.5 conduit entries.
Special conditions for safe use
• The Rotary Limit Switch Box is marked with the
following warning marking: ”WARNING –
POTENTIAL ELECTROSTATIC CHARGING HAZARD
– SEE INSTRUCTIONS”.
• The total electrical ratings must not exceed the
values indicated in this Schedule.
• For nomenclature breakdown please see the
installation instructions.
Terminal strip
Caution!
• Proper and suitable conduit plugs must be instal-
led in unused conduit entries before taking the unit
into service.
• Installation according to National Electric Code, local
codes, local certificates and manufacture instructions
in all cases. Environmental seals must be used to
protect ingress of water through the conduits.
• Electrostatic build up prevention for safe Use
The enclosure of the PS/PM Ultraswitch™ switch box
is made of PA6/PA66 and any impact or friction caused
by external objects shall be avoided in the application
to prevent electrostatic build up.
Wiring diagram
Wiring diagram
(special configurations)
FCD PMENIM0008-02 - 08/14 FCD PMENIM0008-02 - 08/14

1110
Substitution of components may impair suitability for hazardous (classified) locations. Do not
disconnect equipment unless area is known to be non-hazardous.
To prevent ignition of ammable or combustible atmospheres, disconnect power before servicing,
or; read, understand and adhere to the manufacturer’s live maintenance procedures.
7. Switches (certified)
7.1 ATEX Ex e mb certificate information
Model code:
xxxxxxxPP-22-xxxx or xxxxxxPx2xxxxx: 60VDC 3A 100VA
xxxxxxxPT-22-xxxx or xxxxxxTx2xxxxx: 24VDC 3A 75VA
NEMKO 12ATEX1079X, IP66
Ex II 2G
Ex e mb IIC T5 (T6) Gb
T5 : -40°C ≤ Ta≤ +80°C, T6 : -40°C ≤ Ta≤ +60°C
Power source must be protected by a fuse of 3A with a breaking capacity of ≥ 1500A. For ATEX and IECEx
installations an appropriately rated gland is required. Any unused conduit entry must have a suitable rated
blanking element.
7.3 Adjusting limit switches
UltraSwitch™ enclosures feature Quick-Set™ cams
which are used to trip the limit switches. These cams
are easily adjusted without tools.
Caution: disconnect power before removing cover
when installed in hazardous locations.
Remove cover and set aside. Rotate actuator/valve to
full clockwise (CW) position.Adjust cam(s) associated
with CW as follows:
1. Push or pull cam against spring to disengage it
from splines.
2. Rotate cam CW breaking contact with switch (or
moving magnet away from switch).
3. Continue rotating cam CW just until switch trips.
4. Release cam and reengage it with splines.
Rotate actuator/valve to full counter-clockwise (CCW)
position. Adjust cam(s) associated with CCW as des-
cribed in steps 1 through 4, except rotate cam(s) CCW.
Cam adjustment
7.2 Installation in hazardous locations
Refer to control drawing RA-2.
Note: factory setting is:
Top switch = CW (closed)
Second switch = CCW (open)
Third switch = CW
Fourth switch = CCW
Adjustment screws
Cam fine adjustment
7.4 Cam fine adjustment
Some cams have a fine adjustment available. These
cams will have a small screw embedded into the side
of the cam.
Adjusting this screw clockwise or counter clockwise
will deform the cam, changing the trip point slightly.
7.5 Adjusting UltraDome™ position
indicator
UltraDome™ visual indicators are easily adjusted
to match the dome’s clear windows to the rotor’s
colored sections. The dome is secured to the PS/PM
Ultraswitch™ housing with screws mounted through
slotted holes. The slotted holes allow approximately
20° adjustment of the dome.
In addition, the dome can be completely removed and
reoriented in 45° and 90° increments. The rotor may
be reoriented with respect to the shaft by removing
the shaft coupler and rotating 90° before reinstalling.
This may be necessary to obtain the correct orientation
of windows in a multi-way application.
7.6 Calibrating 4-20 mA transmitter
Setting direct/reverse action: A dip-switch setting
controls the direction of increasing travel. For 4 mA in
the full clockwise position, select ”D”, for 4 mA in the
full counterclockwise position, select ”R”.
Adjusting zero/span:
1. Attach a DC mA meter to +/- terminals.
2. Operate valve/switchbox to position corresponding
to 4 mA.
3. Adjust feedback board zero trim pot to yield 4 mA.
(Turning CW increases value, turning CCW decreases
value).
4. Operate valve/switchbox to position corresponding
to 20 mA feedback.
5. Adjust feedback board span trim pot to yield 20
mA. (Turning CW increases value, turning CCW de-
creases value).
6. The zero and span adjustments are interactive.
Repeat steps 1 through 5 as necessary.
Note: If transmitter adjustment gets difficult (i.e.,
trim pots do not have desired effect) start over by
”centering” the trim pots. This is accomplished by
turning in one direction for 20 turns and reversing
direction for 10 turns.
FCD PMENIM0008-02 - 08/14 FCD PMENIM0008-02 - 08/14

1312
00 No switches
(empty housing)
F1 IFM IN5129 10-36VDC 3-Wire (H=14 only)
F2 2-wire Foundation (Ultra-Low Power Coil Only)
Fieldbus
F3 IFM IF5250 10-36VDC NC PNP, 150mA, 3-wire NC
F4 4-wire Foundation (Select External Solenoid Coil)
Fieldbus
F5 IFM IF6001 18-32VDC,NOPNP,150mA@50°C
F6 IFM IF6034 10-36VDC, NO PNP, 150mA, Stainless steel
F7 IFM IN0074 20-250 AC/DC, NO, 350mA/100mA
F8 IFM IN0081 20-250 AC/DC, NO, 350mA/100mA w/LED
(H=14 only)
FB IFM IF5249 10-36VDC NO PNP, 150mA, 3-wire NO
FC IFM IF5718 10-36VDC NO PNP/NPN, 150mA, plastic
FZ AS-I Bus Card 31VDC 28 mA
M1 SPDT Honeywell V7-1C13D8-201 15.1A (1/2 HP) at 125/250 VAC;
Mechanical MicroSwitch A at 125 VDC; 1/4A at 250VDC; 5A at 120Vac
M3 DPDT Cherry E19-00A 15A, 125/250 VAC 3/5HP
Mechanical
MA 3-Position Honeywell V7-1C13D8-201 15.1A(1/2HP)at125VAC;—ΩA
Control MicroSwitch at 125 VDC; 1/4A at 250VDC; 5A at 120Vac
MB DPDT Licon 22-104 10A (1/2 HP) at 125 VAC
Mechanical
MC SPDT Honeywell V7-1C13D8-201 15.1A(1/2HP)at125VAC;ΩAat
Mechanical 250°F MicroSwitch 125 VDC; 1/4A at 250VDC; 5A at 120Vac
MD 3-Pos. Control
w/Indication (DA) Licon 22-104 10A (1/2 HP) at 125 VAC
MG SPDT Honeywell V7-1D19D8-201 1A at 125 VAC / 50 mA at 24 VDC
Gold Mechanical MicroSwitch
MS 3-Pos. Control
w/Indication (SR) Licon 22-104 10A (1/2 HP) at 125 VAC
N1 Pepperl+Fuchs NJ4-12GM40-E
N2 Pepperl+Fuchs NJ2-12GK-N
N3 Pepperl+Fuchs SJ3,5-S1N
N4 Pepperl+Fuchs NJ2-12GK-SN
N5 Pepperl+Fuchs NJ4-12GK40-E
N6 Pepperl+Fuchs NJ4-12GK40-E1
N7 Pepperl+Fuchs NBB2-V3-E0
N8 Solid State Proximity Pepperl+Fuchs NJ2-V3-N NAMUR Sensor Output / 5-25 VDC Supply
N9 Solid State Proximity Pepperl+Fuchs NBB3-V3-Z4 NPN Sourcing/ 100 mA max. Current / 5-60 VDC
NA Pepperl+Fuchs NBN4-12GM40-E2
NB Pepperl+Fuchs NJ2-12GM-N
NC Pepperl+Fuchs NJ4-12GM-N
ND Pepperl+Fuchs NCB2-12GM40-Z1
NE Pepperl+Fuchs NCB2-12GM35-N0
7.7 Switch option specifications (all) 7.7 Switch option specifications (continued)
Code
Switch Option Manufacturer Part Number Load Capacity
7.8 Analog feedback option specifications
Options T, D, 4-20 mA Transmitter
Voltage Supply: 6 - 30 VAC
Impedance: 300 Ohms at 20 mA
NF NCN4-12GM35-N0
NG NJ5-11-N-G
NH NCB4-12GM40-N0
NJ Efector Type IN-2002-ABOA (Non-certified option)
NK NCN4-12GM40-Z0
NL NCB2-V3-N0
NM NJ2-11-SN-G
NN NBB2-V3-E2
NP Solid State Proximity Pepperl+Fuchs SJ3.5-N
NQ Solid State Proximity Pepperl+Fuchs NJ4-12GK-N
NR Solid State Proximity Pepperl+Fuchs NJ4-12GM40-E1 PNP Sinking / 200 mA max.
Current / 10-60 VDC
NS Solid State Proximity Pepperl+Fuchs NJ4-12GM40-E2 NPN Sourcing / 200 mA max.
Current / 10-60 VDC
NT Solid State Proximity Pepperl+Fuchs NJ4-12GK40-E2 NPN Sourcing / 200 mA max.
Current / 10-60 VDC
NV Solid State Proximity Pepperl+Fuchs NJ2-11-N-G NAMUR Sensor Output / 5-25 VDC Supply
NW Solid State Proximity Pepperl+Fuchs SJ3,5-SN NAMUR Sensor Output / 5-25 VDC Supply
NX NBB2-V3-E3
NY Solid State Proximity Pepperl+Fuchs NJ4-12GK-SN NAMUR Sensor Output / 5-25 VDC Supply
P4 SPST Proximity Aleph PS-6132 0.35A at 140 VAC / .25A at 200VDC
(50 W Max.)
P5 SPDT Proximity Hamlin 59135-030 0.25A at 120 VAC / 0.25A at 28 VDC (3 W Max.)
PE SPDT Sabre Proximity Flowserve XA0199 1A at 120 VAC / 1A at 24 VDC
PP SPDT Phazer Proximity Flowserve XA0155 3A at 120 VAC / 2A at 24 VDC
PT SPST BRS Proximity Flowserve XA0157 3A at 120 VAC / 0.5 at 24 VDC
R1 Pepperl+Fuchs NBB3-V3-Z4-3G-3D
Option A - Potentiometer Output
Maximum Load: 1 Watt
Enclosure Ratings
Type 4x
IP66/67
Code
Switch Option Manufacturer Part Number Load Capacity
FCD PMENIM0008-02 - 08/14 FCD PMENIM0008-02 - 08/14

1514
Notes
8. Dimensions
TM
9. Spare parts
Pos Part No Description
1 31529 Dome spare part set compl.
Red/green
1 34895 Dome spare part set compl.
Black/Yellow
1
FCD PMENIM0008-02 - 08/14 FCD PMENIM0008-02 - 08/14

Country Name
Town Name, City 00000 Country
Telephone: 0 000 000 0000
Country Name
Town Name, City 00000 Country
Telephone: 0 000 000 0000
Country Name
Town Name, City 00000 Country
Telephone: 0 000 000 0000
Country Name
Town Name, City 00000 Country
Telephone: 0 000 000 0000
Country Name
Town Name, City 00000 Country
Telephone: 0 000 000 0000
Country Name
Town Name, City 00000 Country
Telephone: 0 000 000 0000
Country Name
Town Name, City 00000 Country
Telephone: 0 000 000 0000
Country Name
Town Name, City 00000 Country
Telephone: 0 000 000 0000
Country Name
Town Name, City 00000 Country
Telephone: 0 000 000 0000
Country Name
Town Name, City 00000 Country
Telephone: 0 000 000 0000
Country Name
Town Name, City 00000 Country
Telephone: 0 000 000 0000
Country Name
Town Name, City 00000 Country
Telephone: 0 000 000 0000
Country Name
Town Name, City 00000 Country
Telephone: 0 000 000 0000
To find your local Flowserve representative please use
the Sales Support Locator System found at
www.flowserve.com
Or call toll free: 0 000 000
To find your local Flowserve representative:
Bulletin XX-00-00 (X)
This area can be used for divisional information
Flowserve Corporation has established industry leadership in the design and manufacture of its products. When properly selected, this Flowserve
product is designed to perform its intended function safely during its useful life. However, the purchaser or user of Flowserve products should be aware
that Flowserve products might be used in numerous applications under a wide variety of industrial service conditions. Although Flowserve can provide
general guidelines, it cannot provide specific data and warnings for all possible applications. The purchaser/user must therefore assume the ultimate
responsibility for the proper sizing and selection, installation, operation, and maintenance of Flowserve products. The purchaser/user should read and
understand the (INSERT OFFICIAL USER INSTRUCTION TITLE) instructions included with the product, and train its employees and contractors in the
safe use of Flowserve products in connection with the specific application.
While the information and specifications contained in this literature are believed to be accurate, they are supplied for informative purposes only and
should not be considered certified or as a guarantee of satisfactory results by reliance thereon. Nothing contained herein is to be construed as a
warranty or guarantee, express or implied, regarding any matter with respect to this product. Because Flowserve is continually improving and upgrading
its product design, the specifications, dimensions and information contained herein are subject to change without notice. Should any question arise
concerning these provisions, the purchaser/user should contact Flowserve Corporation at any one of its worldwide operations or offices.
For more information about Flowserve Corporation, contact www.flowserve.com or call USA 1-800-225-6989.
To find your local Flowserve representative:
To find your local Flowserve representative please use the Sales Support
Locator System found at www.owserve.com
Flowserve Corporation has established industry leadership in the design and manufacture of its
products.When properly selected, this Flowserve product is designed to perform its intended function
safely during its useful life. However, the purchaser or user of Flowserve products should be aware
that Flowserve products might be used in numerous applications under a wide variety of industrial
service conditions. Although Flowserve can provide general guidelines, it cannot provide specific
data and warnings for all possible applications. The purchaser/user must therefore assume the
ultimate responsibility for the proper sizing and selection, installation, operation, and maintenance
of Flowserve products. The purchaser/user should read and understand the (PS/PM Switchbox User
Instructions) instructions included with the product, and train its employees and contractors in the
safe use of Flowserve products in connection with the specific application.
While the information and specifications contained in this literature are believed to be accurate, they
are supplied for informative purposes only and should not be considered certified or as a guarantee
of satisfactory results by reliance thereon. Nothing contained herein is to be construed as a war-
ranty or guarantee, express or implied, regarding any matter with respect to this product. Because
Flowserve is continually improving and upgrading its product design, the specifications, dimensions
and information contained herein are subject to change without notice. Should any question arise
concerning these provisions, the purchaser/user should contact Flowserve Corporation at any one
of its worldwide operations or offices.
For more information about Flowserve Corporation, contact www.owserve.com or call USA
1-800-225-6989.
© May 2013, Flowserve Corporation, Irving, Texas
Palmstierna International AB
Korta Gatan 9
SE-171 54 Solna
SWEDEN
Tel: +46 (0) 8 555 106 00
Fax: +46 (0) 8 555 106 01
E-mail: infopmv@owserve.com
Germany
Flowserve
Sperberweg 16
D-41468 Neuss
GERMANY
Tel: +49 (0) 2131 795 74 80
Fax: +49 (0) 2131 795 74 99
E-mail: pmvgermany@owserve.com
Flowserve Flow Control GmbH
Rudolf-Plank Strasse 2
D-76275 Ettlingen
GERMANY
Tel: +49 (0) 7243 103 0
Fax: +49 (0) 7243 103 222
E-mail: argus@owserve.com
UK
Flowserve
Abex Road
Newbury, Berkshire, RG14 5EY
UK
Tel: +44 (0) 1635 46 999
Fax: +44 (0) 1635 36 034
E-mail: pmvukinfo@owserve.com
Italy
Flowserve Spa
Via Prealpi, 30
20032 Cormano (Milano)
ITALY
Tel: +39 (0) 2 663 251
Fax: +39 (0) 2 615 18 63
E-mail: infoitaly@owserve.com
USA, Mexico
PMV-USA
14219 Westfair West Drive
Houston, TX 77041, USA
Tel: +1 281 671 9209
Fax: +1 281 671 9268
E-mail: salespmv@owserve.com
Asia Pacific Headquarters
Flowserve Pte Ltd.
No. 12 Tuas Avenue 20
REPUBLIC OF SINGAPORE 638824
Tel: +65 (0) 687 98900
Fax: +65 (0) 686 24940
E-mail: fcdasiaprocess@owserve.com
The Netherlands
Flowserve Flow Control Benelux
Rechtzaad 17
4703 RC Roosendaal
THE NETHERLANDS
Tel: +31 (0) 30 6771946
Fax: +27 (0) 30 6772471
E-mail: fcbinfo@owserve.com
flowserve.com
FCD PMENIM0008-02 - 08/14
This manual suits for next models
1
Table of contents
Other Flowserve Switch manuals

Flowserve
Flowserve Ultraswitch PMV WS Series User manual

Flowserve
Flowserve UltraSwitch PMV DS User manual

Flowserve
Flowserve NRS 1-7 User manual

Flowserve
Flowserve Accord WS/WM Ultraswitch User manual

Flowserve
Flowserve PMV WS Ultraswitch User manual

Flowserve
Flowserve PMV F5 Series User manual

Flowserve
Flowserve F5 User manual