manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Fluke
  6. •
  7. Measuring Instrument
  8. •
  9. Fluke FIBER OneShot User manual

Fluke FIBER OneShot User manual

Other manuals for FIBER OneShot

1

Other Fluke Measuring Instrument manuals

Fluke 374 User manual

Fluke

Fluke 374 User manual

Fluke 360 Use and care manual

Fluke

Fluke 360 Use and care manual

Fluke i2000flex User manual

Fluke

Fluke i2000flex User manual

Fluke 365 User manual

Fluke

Fluke 365 User manual

Fluke 43B User manual

Fluke

Fluke 43B User manual

Fluke 80K-6 User manual

Fluke

Fluke 80K-6 User manual

Fluke OF-500-10 OptiFiber Use and care manual

Fluke

Fluke OF-500-10 OptiFiber Use and care manual

Fluke 805 FC User manual

Fluke

Fluke 805 FC User manual

Fluke SMFT-1000 User manual

Fluke

Fluke SMFT-1000 User manual

Fluke 435-II User manual

Fluke

Fluke 435-II User manual

Fluke 2620A User manual

Fluke

Fluke 2620A User manual

Fluke PM6681 User manual

Fluke

Fluke PM6681 User manual

Fluke 9000A-006 User manual

Fluke

Fluke 9000A-006 User manual

Fluke 302+ User manual

Fluke

Fluke 302+ User manual

Fluke ESA609 User manual

Fluke

Fluke ESA609 User manual

Fluke 5618B User manual

Fluke

Fluke 5618B User manual

Fluke 39 User manual

Fluke

Fluke 39 User manual

Fluke I430FLEX User manual

Fluke

Fluke I430FLEX User manual

Fluke i6000s Flex Series User manual

Fluke

Fluke i6000s Flex Series User manual

Fluke 411D User manual

Fluke

Fluke 411D User manual

Fluke 771 User manual

Fluke

Fluke 771 User manual

Fluke 368 Use and care manual

Fluke

Fluke 368 Use and care manual

Fluke Biomedical IDA-4 Plus Operators User manual

Fluke

Fluke Biomedical IDA-4 Plus Operators User manual

Fluke 789 Use and care manual

Fluke

Fluke 789 Use and care manual

Popular Measuring Instrument manuals by other brands

Suaoki D40 user manual

Suaoki

Suaoki D40 user manual

Elster BK-G1.6 operating instructions

Elster

Elster BK-G1.6 operating instructions

Endress+Hauser Deltabar FMD71 technical information

Endress+Hauser

Endress+Hauser Deltabar FMD71 technical information

Duratool D03128 manual

Duratool

Duratool D03128 manual

Vega VEGAPULS 65 Quick setup guide

Vega

Vega VEGAPULS 65 Quick setup guide

Tonghui TH2618B Operation manual

Tonghui

Tonghui TH2618B Operation manual

Tenmars TM-801 user manual

Tenmars

Tenmars TM-801 user manual

MSR 145 user manual

MSR

MSR 145 user manual

TPS WP-82 manual

TPS

TPS WP-82 manual

PCB Piezotronics 003C30 Installation and operating manual

PCB Piezotronics

PCB Piezotronics 003C30 Installation and operating manual

Tenma 72-10465 manual

Tenma

Tenma 72-10465 manual

Endress+Hauser Proline Promag 50 Brief operating instructions

Endress+Hauser

Endress+Hauser Proline Promag 50 Brief operating instructions

Siemens SITRANS F Coriolis FCT030 Function manual

Siemens

Siemens SITRANS F Coriolis FCT030 Function manual

KLINGER CMF V Series instruction manual

KLINGER

KLINGER CMF V Series instruction manual

Keysight M8290A Getting started guide

Keysight

Keysight M8290A Getting started guide

Acterna MS1400 Operation manual

Acterna

Acterna MS1400 Operation manual

R&S ZPH manual

R&S

R&S ZPH manual

Datacolor ColorReader DC10-2 user guide

Datacolor

Datacolor ColorReader DC10-2 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

October 2009
©2009 Fluke Corporation. All rights reserved.
All product names are trademarks of their respective companies.
FIBER OneShot™
Length Meter
Quick Reference Guide
Safety Information
WWarning: Class 1 Laser*
To prevent possible damage to your eyes caused by
hazardous radiation:
•
Do not look directly into optical connectors. Some optical
equipment emits invisible radiation that can cause
permanent damage to your eyes.
•
Do not turn on the meter unless a fiber is attached to the
port.
•
Do not use a magnifying device to look at the optical
outputs without the correct filter.
•
Use of controls, adjustments, or procedures that are not in
this manual can cause exposure to hazardous radiation.
WCaution
To prevent damage to fiber connectors, to prevent data
loss, and to make sure that your test results are as accurate
as possible:
•
Do not connect APC connectors to the meter. An APC
connector will cause damage to the fiber endface in the
connector on the meter.
•
Use only patch cords that comply with GR-326-CORE
specifications. Other patch cords can cause unreliable
measurements.
•
Use the correct procedures to clean all fiber connectors
before each test. If you do not do this or if you use
incorrect procedures, you can get unreliable test results
and can cause permanent damage to the connectors.
•
Put protective caps on all connectors when you do not use
them.
•
Do not connect the meter to a network that is on. If you
do, the meter can cause problems in the network.
•
If ACTIVE LINE blinks, immediately disconnect the meter
from the fiber. Optical power levels more than +7 dBm can
cause damage to the detector in the meter.
Battery Installation and Life
fjy03.eps
How to Install the Batteries
The meter can do approximately 1500 tests before you must replace
the batteries.
Display Features
fjy01.eps
A
CheckActive™shows when the meter looks for an optical signal
on the fiber. CheckActive™and ACTIVE LINE blink if there is an
optical signal on the fiber. The meter will not do a test if there
is an optical signal on the fiber.
B
When the low battery symbol shows, replace the batteries
soon.
C
The digits show the fiber length in feet or meters.
D
Shows when you look at the setting for the backlight timer.
The setting is in seconds.
E
Shows an error number for error conditions.
F
Shows when the meter completes a length measurement.
G
Shows as the meter measures length.
H
J: Shows when the length is more than the range of the
meter.
I: Can show for short fibers when the meter cannot measure
the length accurately.
I
Settings for the meter.
Settings
To change the settings on the meter:
1
Press M.
2
To select a setting to change, press V, then press M.
3
Use UVto change the setting. See below for information on
the settings.
4
Press Mor Tto save the setting.
•
APC/UPC: Angled Physical Contact/Ultra Physical Contact. If most
cables you will do tests on have UPC connectors, set this to UPC.
•
BACKLIGHT: Timer for the display backlight.
•
I.O.R.: Index of refraction.
•
ft/m: Unit for length measurements.
•
dB LIMIT: Sets the minimum size of a reflection that the meter
shows as a break or the end of the fiber when the reflection is
before the end of the fiber.
How to Clean the Connector on the Meter
1
Turn off the meter.
2
Remove the connector adapter to get access to the ferrule (see
"The Connector Adapter".)
3
Touch the tip of an optical-grade solvent pen or swab soaked in
solvent to a dry, optical-grade wiper.
4
Touch a new, dry swab to the solvent on the wiper.
5
Twist the swab around against the fiber endface 3 to 5 times,
then twist a dry swab around against the fiber endface 3 to 5
times.
AA
IEC LR6
NEDA 15A
Note: Fluke Networks recommends alkaline batteries.
The Connector Adapter
The meter has an SC connector adapter that you can remove to clean
the fiber endface in the port.
fjy02.eps
How to Remove and Install the Connector Adapter
How to Use the Meter
Notes
Always use patch cords that comply with GR-326-CORE
specifications. Other patch cords can cause unreliable
measurements.
Do not use the meter to measure fibers that have PC
connectors. PC connectors cause large reflections that the
meter shows as the end of the fiber.
1
Clean all fiber connectors.
2
Connect the fiber to the meter.
To connect to APC connectors, use a UPC/APC patch cord. To
connect to UPC connectors, use a UPC/UPC patch cord.
3
Turn on the meter, then press T.
fjf05.eps
How to Make Connections
Contacting Fluke Networks
•
Australia: 61 (2) 8850-3333 or 61 (3) 9329 0244
•
Beijing: 86 (10) 6512-3435
•
Brazil: 11 3759 7600
•
Canada: 1-800-363-5853
•
Europe: +44-(0)1923 281 300
•
Hong Kong: 852 2721-3228
•
Japan: 03-3434-0510
•
Korea: 82 2 539-6311
•
Singapore: +65-6799-5566
•
Taiwan: (886) 2-227-83199
•
USA: 1-800-283-5853
For more phone numbers, go to our website.
LIMITED WARRANTY AND LIMITATION OF LIABILITY
Fluke Networks mainframe products will be free from defects in
material and workmanship for one year from the date of
purchase. Parts, accessories, product repairs and services are
warranted for 90 days, unless otherwise stated. Ni-Cad, Ni-MH
and Li-Ion batteries, cables or other peripherals are all
considered parts or accessories.
This warranty does not cover damage from accident, neglect,
misuse, alteration, contamination, or abnormal conditions of
operation or handling. Resellers are not authorized to extend
any other warranty on Fluke Networks’ behalf. To obtain service
during the warranty period, contact your nearest Fluke
Networks authorized service center to obtain return
authorization information, then send your defective product to
that Service Center with a description of the problem.
THIS WARRANTY IS YOUR ONLY REMEDY. NO OTHER
WARRANTIES, SUCH AS FITNESS FOR A PARTICULAR PURPOSE,
ARE EXPRESSED OR IMPLIED. FLUKE NETWORKS IS NOT LIABLE
FOR ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL
DAMAGES OR LOSSES, ARISING FROM ANY CAUSE OR THEORY.
Since some states or countries do not allow the exclusion or
limitation of an implied warranty or of incidental or
consequential damages, this limitation of liability may not apply
to you.
4/04
Unlock
Lock
Ferrule and fiber
endface
Remove
UPC
connector
only
UPC
connector
only
UPC/UPC
or
APC/APC
connectors with
an adapter
UPC to UPC
or
APC to APC
connection
Note: Always use patch
cords that comply with
GR-325-CORE
specifications.