FMC Technologies AccuLoad II Owner's manual

Programming Workbook
Issue/Rev.0.3(8/97) BulletinAB06034
AccuLoad®II - RBU
Electronic Preset Delivery System
This worksheet applies to AccuLoad II operating with
RBU 00 firmware.(Refer to Operator Reference Manual
MN06066L for complete program entry descriptions.)
Security Access Code:
Company Name:
Prepared By:
Date:
Unit/Meter No.:
Location:
The Most Trusted Name In Measurement

Table of Contents
i
System Directories.......................................................................................................................................................1
System General Purpose Directory........................................................................................................................21
System Flow Control Directory...............................................................................................................................26
System Volume Accuracy Directory.......................................................................................................................28
System Temperature & Density Directory..............................................................................................................32
System Pressure Directory....................................................................................................................................33
System Read Only Directory..................................................................................................................................33
System Communication Directory..........................................................................................................................34
System Input/Output Directory...............................................................................................................................43
System Diagnostic Directory..................................................................................................................................50
Product Directories....................................................................................................................................................54
Product General Purpose Directory.......................................................................................................................54
Product Flow Control Directory..............................................................................................................................54
Product Volume Accuracy Directory ......................................................................................................................56
Product Temperature & Density Directory..............................................................................................................59
Product Pressure Directory....................................................................................................................................61
Product Read Only Directory.................................................................................................................................64
Product Communications Directory........................................................................................................................65
Inputs & Outputs Directory.....................................................................................................................................66
Diagnostics Directory.............................................................................................................................................66
Blend Recipe Directories............................................................................................................................................67
Blend Recipe # __ Directory..................................................................................................................................67


Table of Contents
i


Program Program
Code Function Code Description Entry Code
Issue/Rev. 0.3 (8/97) 1
System Directories
000 System Configuration Directory 000
001 Number of Products Enter: "1" One Product 001
"2" Two Products
"3" Three Products
"4" Four Products __
002 Number of Additive Enter: "0" No Additive Injectors 002
Injectors "1" One Additive Injector
"2" Two Additive Injectors
"3" Three Additive Injectors
"4" Four Additive Injectors
"5" Five Additive Injectors
"6" Six Additive Injectors
"7" Seven Additive Injectors
"8" Eight Additive Injectors __
003 A/C Output Relay 1 Enter: "00" No Assignment (N/A) 003
Terminals 89 & 90 "01" Additive Relay 1 (ADD1)
"02" Additive Relay 2 (ADD2)
"03" Additive Relay 3 (ADD3)
"04" Additive Relay 4 (ADD4)
"05" Additive Relay 5 (ADD5)
"06" Additive Relay 6 (ADD6)
"07" Additive Relay 7 (ADD7)
"08" Additive Relay 8 (ADD8)
"09" Additive Pump 1 (ADP1)
"10" Additive Pump 2 (ADP2)
"11" Additive Pump 3 (ADP3)
"12" Additive Pump 4 (ADP4)
"13" Additive Pump 5 (ADP5)
"14" Additive Pump 6 (ADP6)
"15" Additive Pump 7 (ADP7)
"16" Additive Pump 8 (ADP8)
"17" Alarm Relay (ALR) __ __
Note: When using three or four products this relay must be programmed "00" (No Assignment).

Program
Code
Function Code
Description
Entry Program
Code
2 Issue/Rev. 03 (8/97)
004 A/C Output Relay 2 Enter: "00" No Assignment (N/A) 004
Terminals 91 & 92 "01" Additive Relay 1 (ADD1)
"02" Additive Relay 2 (ADD2)
"03" Additive Relay 3 (ADD3)
"04" Additive Relay 4 (ADD4)
"05" Additive Relay 5 (ADD5)
"06" Additive Relay 6 (ADD6)
"07" Additive Relay 7 (ADD7)
"08" Additive Relay 8 (ADD8)
"09" Additive Pump 1 (ADP1)
"10" Additive Pump 2 (ADP2)
"11" Additive Pump 3 (ADP3)
"12" Additive Pump 4 (ADP4)
"13" Additive Pump 5 (ADP5)
"14" Additive Pump 6 (ADP6)
"15" Additive Pump 7 (ADP7)
"16" Additive Pump 8 (ADP8)
"17" Alarm Relay (ALR) __ __
Note: When using three or four products this relay must be programmed "00" (No Assignment).
005 A/C Output Relay 3 Enter: "00" No Assignment (N/A) 005
Terminals 93 & 94 "01" Additive Relay 1 (ADD1)
"02" Additive Relay 2 (ADD2)
"03" Additive Relay 3 (ADD3)
"04" Additive Relay 4 (ADD4)
"05" Additive Relay 5 (ADD5)
"06" Additive Relay 6 (ADD6)
"07" Additive Relay 7 (ADD7)
"08" Additive Relay 8 (ADD8)
"09" Additive Pump 1 (ADP1)
"10" Additive Pump 2 (ADP2)
"11" Additive Pump 3 (ADP3)
"12" Additive Pump 4 (ADP4)
"13" Additive Pump 5 (ADP5)
"14" Additive Pump 6 (ADP6)
"15" Additive Pump 7 (ADP7)
"16" Additive Pump 8 (ADP8)
"17" Alarm Relay (ALR)
"22" General Relay (GEN) __ __

Program Program
Code Function Code Description Entry Code
Issue/Rev. 0.3 (8/97) 3
006 A/C Output Relay 4 Enter: "00" No Assignment (N/A) 006
Terminals 95 & 96 "01" Additive Relay 1 (ADD1)
"02" Additive Relay 2 (ADD2)
"03" Additive Relay 3 (ADD3)
"04" Additive Relay 4 (ADD4)
"05" Additive Relay 5 (ADD5)
"06" Additive Relay 6 (ADD6)
"07" Additive Relay 7 (ADD7)
"08" Additive Relay 8 (ADD8)
"09" Additive Pump 1 (ADP1)
"10" Additive Pump 2 (ADP2)
"11" Additive Pump 3 (ADP3)
"12" Additive Pump 4 (ADP4)
"13" Additive Pump 5 (ADP5)
"14" Additive Pump 6 (ADP6)
"15" Additive Pump 7 (ADP7)
"16" Additive Pump 8 (ADP8)
"17" Alarm Relay (ALR)
“22” General Relay (GEN)
007 A/C Output Relay 5 Enter: "00" No Assignment (N/A) 007
Terminals 87 & 88 "01" Additive Relay 1 (ADD1)
"02" Additive Relay 2 (ADD2)
"03" Additive Relay 3 (ADD3)
"04" Additive Relay 4 (ADD4)
"05" Additive Relay 5 (ADD5)
"06" Additive Relay 6 (ADD6)
"07" Additive Relay 7 (ADD7)
"08" Additive Relay 8 (ADD8)
"09" Additive Pump 1 (ADP1)
"10" Additive Pump 2 (ADP2)
"11" Additive Pump 3 (ADP3)
"12" Additive Pump 4 (ADP4)
"13" Additive Pump 5 (ADP5)
"14" Additive Pump 6 (ADP6)
"15" Additive Pump 7 (ADP7)
"16" Additive Pump 8 (ADP8)
"17" Alarm Relay (ALR)
"18" Pump-Product 1 (PMP1)
"19" Pump-Product 2 (PMP2)
"20" Pump-Product 3 (PMP3)
"21" Pump-Product 4 (PMP4) __ __

Program Program
Code Function Code Description Entry Code
4 Issue/Rev. 03 (8/97)
008 A/C Output Relay 6 Enter: "00" No Assignment (N/A) 008
Terminals 84 & 85 "01" Additive Relay 1 (ADD1)
"02" Additive Relay 2 (ADD2)
"03" Additive Relay 3 (ADD3)
"04" Additive Relay 4 (ADD4)
"05" Additive Relay 5 (ADD5)
"06" Additive Relay 6 (ADD6)
"07" Additive Relay 7 (ADD7)
"08" Additive Relay 8 (ADD8)
"09" Additive Pump 1 (ADP1)
"10" Additive Pump 2 (ADP2)
"11" Additive Pump 3 (ADP3)
"12" Additive Pump 4 (ADP4)
"13" Additive Pump 5 (ADP5)
"14" Additive Pump 6 (ADP6)
"15" Additive Pump 7 (ADP7)
"16" Additive Pump 8 (ADP8)
"17" Alarm Relay (ALR)
"18" Pump-Product 1 (PMP1)
"19" Pump-Product 2 (PMP2)
"20" Pump-Product 3 (PMP3)
"21" Pump-Product 4 (PMP4) __ __
009 A/C Output Relay 7 Enter: "00" No Assignment (N/A) 009
Terminals 124 & 125 "01" Additive Relay 1 (ADD1)
"02" Additive Relay 2 (ADD2)
"03" Additive Relay 3 (ADD3)
"04" Additive Relay 4 (ADD4)
"05" Additive Relay 5 (ADD5)
"06" Additive Relay 6 (ADD6)
"07" Additive Relay 7 (ADD7)
"08" Additive Relay 8 (ADD8)
"09" Additive Pump 1 (ADP1)
"10" Additive Pump 2 (ADP2)
"11" Additive Pump 3 (ADP3)
"12" Additive Pump 4 (ADP4)
"13" Additive Pump 5 (ADP5)
"14" Additive Pump 6 (ADP6)
"15" Additive Pump 7 (ADP7)
"16" Additive Pump 8 (ADP8)
"17" Alarm Relay (ALR) __ __
Note: When using four products this relay must be programmed "00" (No Assignment).

Program Program
Code Function Code Description Entry Code
Issue/Rev. 0.3 (8/97) 5
010 A/C Output Relay 8 Enter: "00" No Assignment (N/A) 010
Terminals 126 & 127 "01" Additive Relay 1 (ADD1)
"02" Additive Relay 2 (ADD2)
"03" Additive Relay 3 (ADD3)
"04" Additive Relay 4 (ADD4)
"05" Additive Relay 5 (ADD5)
"06" Additive Relay 6 (ADD6)
"07" Additive Relay 7 (ADD7)
"08" Additive Relay 8 (ADD8)
"09" Additive Pump 1 (ADP1)
"10" Additive Pump 2 (ADP2)
"11" Additive Pump 3 (ADP3)
"12" Additive Pump 4 (ADP4)
"13" Additive Pump 5 (ADP5)
"14" Additive Pump 6 (ADP6)
"15" Additive Pump 7 (ADP7)
"16" Additive Pump 8 (ADP8)
"17" Alarm Relay (ALR) __ __
Note: When using four products this relay must be programmed "00" (No Assignment).
011 A/C Output Relay 9 Enter: "00" No Assignment (N/A) 011
Terminals 128 & 129 "01" Additive Relay 1 (ADD1)
"02" Additive Relay 2 (ADD2)
"03" Additive Relay 3 (ADD3)
"04" Additive Relay 4 (ADD4)
"05" Additive Relay 5 (ADD5)
"06" Additive Relay 6 (ADD6)
"07" Additive Relay 7 (ADD7)
"08" Additive Relay 8 (ADD8)
"09" Additive Pump 1 (ADP1)
"10" Additive Pump 2 (ADP2)
"11" Additive Pump 3 (ADP3)
"12" Additive Pump 4 (ADP4)
"13" Additive Pump 5 (ADP5)
"14" Additive Pump 6 (ADP6)
"15" Additive Pump 7 (ADP7)
"16" Additive Pump 8 (ADP8)
"17" Alarm Relay (ALR)
"22" General Relay (GEN) __ __

Program Program
Code Function Code Description Entry Code
6 Issue/Rev. 03 (8/97)
012 A/C Output Relay 10 Enter: "00" No Assignment (N/A) 012
Terminals 130 & 131 "01" Additive Relay 1 (ADD1)
"02" Additive Relay 2 (ADD2)
"03" Additive Relay 3 (ADD3)
"04" Additive Relay 4 (ADD4)
"05" Additive Relay 5 (ADD5)
"06" Additive Relay 6 (ADD6)
"07" Additive Relay 7 (ADD7)
"08" Additive Relay 8 (ADD8)
"09" Additive Pump 1 (ADP1)
"10" Additive Pump 2 (ADP2)
"11" Additive Pump 3 (ADP3)
"12" Additive Pump 4 (ADP4)
"13" Additive Pump 5 (ADP5)
"14" Additive Pump 6 (ADP6)
"15" Additive Pump 7 (ADP7)
"16" Additive Pump 8 (ADP8)
"17" Alarm Relay (ALR)
"22" General Relay (GEN) __ __
013 A/C Output Relay 11 Enter: "00" No Assignment (N/A) 013
Terminals 121 & 122 "01" Additive Relay 1 (ADD1)
"02" Additive Relay 2 (ADD2)
"03" Additive Relay 3 (ADD3)
"04" Additive Relay 4 (ADD4)
"05" Additive Relay 5 (ADD5)
"06" Additive Relay 6 (ADD6)
"07" Additive Relay 7 (ADD7)
"08" Additive Relay 8 (ADD8)
"09" Additive Pump 1 (ADP1)
"10" Additive Pump 2 (ADP2)
"11" Additive Pump 3 (ADP3)
"12" Additive Pump 4 (ADP4)
"13" Additive Pump 5 (ADP5)
"14" Additive Pump 6 (ADP6)
"15" Additive Pump 7 (ADP7)
"16" Additive Pump 8 (ADP8)
"17" Alarm Relay (ALR)
"18" Pump-Product 1 (PMP1)
"19" Pump-Product 2 (PMP2)
"20" Pump-Product 3 (PMP3)
"21" Pump-Product 4 (PMP4) __ __

Program Program
Code Function Code Description Entry Code
Issue/Rev. 0.3 (8/97) 7
014 A/C Output Relay 12 Enter: "00" No Assignment (N/A) 014
Terminals 119 & 120 "01" Additive Relay 1 (ADD1)
"02" Additive Relay 2 (ADD2)
"03" Additive Relay 3 (ADD3)
"04" Additive Relay 4 (ADD4)
"05" Additive Relay 5 (ADD5)
"06" Additive Relay 6 (ADD6)
"07" Additive Relay 7 (ADD7)
"08" Additive Relay 8 (ADD8)
"09" Additive Pump 1 (ADP1)
"10" Additive Pump 2 (ADP2)
"11" Additive Pump 3 (ADP3)
"12" Additive Pump 4 (ADP4)
"13" Additive Pump 5 (ADP5)
"14" Additive Pump 6 (ADP6)
"15" Additive Pump 7 (ADP7)
"16" Additive Pump 8 (ADP8)
"17" Alarm Relay (ALR)
"18" Pump-Product 1 (PMP1)
"19" Pump-Product 2 (PMP2)
"20" Pump-Product 3 (PMP3)
"21" Pump-Product 4 (PMP4) __ __
015 D/C Output Relay 1 Enter: "00" No Assignment (N/A) 015
Terminals 9 & 10 "01" Additive Relay 1 (ADD1)
(w/o Quad OPV) "02" Additive Relay 2 (ADD2)
"03" Additive Relay 3 (ADD3)
Terminals 11 & 10 "04" Additive Relay 4 (ADD4)
(on Quad OPV) "05" Additive Relay 5 (ADD5)
"06" Additive Relay 6 (ADD6)
"07" Additive Relay 7 (ADD7)
"08" Additive Relay 8 (ADD8)
"09" Pulse Output (POT1) __ __
016 D/C Output Relay 2 Enter: "00" No Assignment (N/A) 016
Terminals 57 & 58 "01" Additive Relay 1 (ADD1)
(w/o Quad OPV) "02" Additive Relay 2 (ADD2)
"03" Additive Relay 3 (ADD3)
Terminals 15 & 14 "04" Additive Relay 4 (ADD4)
(on Quad OPV) "05" Additive Relay 5 (ADD5)
"06" Additive Relay 6 (ADD6)
"07" Additive Relay 7 (ADD7)
"08" Additive Relay 8 (ADD8)
"09" Pulse Output (POT2) __ __

Program Program
Code Function Code Description Entry Code
8 Issue/Rev. 03 (8/97)
017 D/C Output Relay 3 Enter: "00" No Assignment (N/A) 017
Terminals 13 & 12 "01" Additive Relay 1 (ADD1)
on Quad OPV "02" Additive Relay 2 (ADD2)
"03" Additive Relay 3 (ADD3)
"04" Additive Relay 4 (ADD4)
"05" Additive Relay 5 (ADD5)
"06" Additive Relay 6 (ADD6)
"07" Additive Relay 7 (ADD7)
"08" Additive Relay 8 (ADD8)
"09" Pulse Output (POT3) __ __
Note: This code is only available for use if the Quad OPV option has been purchased with the AccuLoad II.
018 D/C Output Relay 4 Enter: "00" No Assignment (N/A) 018
Terminals 17 & 16 "01" Additive Relay 1 (ADD1)
on Quad OPV "02" Additive Relay 2 (ADD2)
"03" Additive Relay 3 (ADD3)
"04" Additive Relay 4 (ADD4)
"05" Additive Relay 5 (ADD5)
"06" Additive Relay 6 (ADD6)
"07" Additive Relay 7 (ADD7)
"08" Additive Relay 8 (ADD8)
"09" Pulse Output (POT4) __ __
Note: This code is only available for use if the Quad OPV option has been purchased with the AccuLoad II.
019 A/C Input 1 Enter: "00" No Assignment (N/A) 019
Terminals 98 & 101 "01" Additive Feedback 1 (AFB1)
"02" Additive Feedback 2 (AFB2)
"03" Additive Feedback 3 (AFB3)
"04" Additive Feedback 4 (AFB4)
"05" Additive Feedback 5 (AFB5)
"06" Additive Feedback 6 (AFB6)
"07" Additive Feedback 7 (AFB7)
"08" Additive Feedback 8 (AFB8)
"09" First/Second High Flow (FSC)
"10" Printer Tray Switch (PTS)*
"11" Permissive 1 Contact (PRC1)
"12" Permissive 2 Contact (PRC2)
"13" Valve Power (VPW)
"14" Valve Stem-Product 1 (VST1)
"15" Valve Stem-Product 2 (VST2)
"16" Valve Stem-Product 3 (VST3)
"17" Valve Stem-Product 4 (VST4) __ __
*Note: Or can be used for Master Reset.

Program Program
Code Function Code Description Entry Code
Issue/Rev. 0.3 (8/97) 9
020 A/C Input 2 Enter: "00" No Assignment (N/A) 020
Terminals 99 & 101 "01" Additive Feedback 1 (AFB1)
"02" Additive Feedback 2 (AFB2)
"03" Additive Feedback 3 (AFB3)
"04" Additive Feedback 4 (AFB4)
"05" Additive Feedback 5 (AFB5)
"06" Additive Feedback 6 (AFB6)
"07" Additive Feedback 7 (AFB7)
"08" Additive Feedback 8 (AFB8)
"09" First/Second High Flow (FSC)
"10" Printer Tray Switch (PTS)*
"11" Permissive 1 Contact (PRC1)
"12" Permissive 2 Contact (PRC2)
"13" Valve Power (VPW)
"14" Valve Stem-Product 1 (VST1)
"15" Valve Stem-Product 2 (VST2)
"16" Valve Stem-Product 3 (VST3)
"17" Valve Stem-Product 4 (VST4) __ __
*Note: Or can be used for Master Reset.
021 A/C Input 3 Enter: "00" No Assignment (N/A) 021
Terminals 100 & 101 "01" Additive Feedback 1 (AFB1)
"02" Additive Feedback 2 (AFB2)
"03" Additive Feedback 3 (AFB3)
"04" Additive Feedback 4 (AFB4)
"05" Additive Feedback 5 (AFB5)
"06" Additive Feedback 6 (AFB6)
"07" Additive Feedback 7 (AFB7)
"08" Additive Feedback 8 (AFB8)
"09" First/Second High Flow (FSC)
"10" Printer Tray Switch (PTS)*
"11" Permissive 1 Contact (PRC1)
"12" Permissive 2 Contact (PRC2)
"13" Valve Power (VPW)
"14" Valve Stem-Product 1 (VST1)
"15" Valve Stem-Product 2 (VST2)
"16" Valve Stem-Product 3 (VST3)
"17" Valve Stem-Product 4 (VST4) __ __
*Note: Or can be used for Master Reset.

Program Program
Code Function Code Description Entry Code
10 Issue/Rev. 03 (8/97)
022 A/C Input 4 Enter: "00" No Assignment (N/A) 022
Terminals 103 & 105 "01" Additive Feedback 1 (AFB1)
"02" Additive Feedback 2 (AFB2)
"03" Additive Feedback 3 (AFB3)
"04" Additive Feedback 4 (AFB4)
"05" Additive Feedback 5 (AFB5)
"06" Additive Feedback 6 (AFB6)
"07" Additive Feedback 7 (AFB7)
"08" Additive Feedback 8 (AFB8)
"09" First/Second High Flow (FSC)
"10" Printer Tray Switch (PTS)*
"11" Permissive 1 Contact (PRC1)
"12" Permissive 2 Contact (PRC2)
"13" Valve Power (VPW)
"14" Valve Stem-Product 1 (VST1)
"15" Valve Stem-Product 2 (VST2)
"16" Valve Stem-Product 3 (VST3)
"17" Valve Stem-Product 4 (VST4) __ __
*Note: Or can be used for Master Reset.
Note: For "Remote Start" operation either this code or code 028 must be programmed "11" (Permissive 1 Contact), code 807 must be
programmed "5" ("Remote Start") and jumpers must be installed as shown in the Installation Manual (MN06064).
023 A/C Input 5 Enter: "00" No Assignment (N/A) 023
Terminals 104 & 105 "01" Additive Feedback 1 (AFB1)
"02" Additive Feedback 2 (AFB2)
"03" Additive Feedback 3 (AFB3)
"04" Additive Feedback 4 (AFB4)
"05" Additive Feedback 5 (AFB5)
"06" Additive Feedback 6 (AFB6)
"07" Additive Feedback 7 (AFB7)
"08" Additive Feedback 8 (AFB8)
"09" First/Second High Flow (FSC)
"10" Printer Tray Switch (PTS)*
"11" Permissive 1 Contact (PRC1)
"12" Permissive 2 Contact (PRC2)
"13" Valve Power (VPW)
"14" Valve Stem-Product 1 (VST1)
"15" Valve Stem-Product 2 (VST2)
"16" Valve Stem-Product 3 (VST3)
"17" Valve Stem-Product 4 (VST4) __ __
*Note: Or can be used for Master Reset.
Note: For "Remote Stop" operation this code must be programmed "12" (Permissive 2 Contact), code 811 must be programmed "5" ("Remote
Stop" and jumpers must be installed as shown in the Installation Manual (MN06064).

Program Program
Code Function Code Description Entry Code
Issue/Rev. 0.3 (8/97) 11
024 A/C Input 6 Enter: "00" No Assignment (N/A) 024
Terminals 73 & 74 "01" Additive Feedback 1 (AFB1)
"02" Additive Feedback 2 (AFB2)
"03" Additive Feedback 3 (AFB3)
"04" Additive Feedback 4 (AFB4)
"05" Additive Feedback 5 (AFB5)
"06" Additive Feedback 6 (AFB6)
"07" Additive Feedback 7 (AFB7)
"08" Additive Feedback 8 (AFB8)
"09" First/Second High Flow (FSC)
"10" Printer Tray Switch (PTS)*
"11" Permissive 1 Contact (PRC1)
"12" Permissive 2 Contact (PRC2)
"13" Valve Power (VPW)
"14" Valve Stem-Product 1 (VST1)
"15" Valve Stem-Product 2 (VST2)
"16" Valve Stem-Product 3 (VST3)
"17" Valve Stem-Product 4 (VST4) __ __
*Note: Or can be used for Master Reset.
025 A/C Input 7 Enter: "00" No Assignment (N/A) 025
Terminals 106 & 109 "01" Additive Feedback 1 (AFB1)
"02" Additive Feedback 2 (AFB2)
"03" Additive Feedback 3 (AFB3)
"04" Additive Feedback 4 (AFB4)
"05" Additive Feedback 5 (AFB5)
"06" Additive Feedback 6 (AFB6)
"07" Additive Feedback 7 (AFB7)
"08" Additive Feedback 8 (AFB8)
"09" First/Second High Flow (FSC)
"10" Printer Tray Switch (PTS)*
"11" Permissive 1 Contact (PRC1)
"12" Permissive 2 Contact (PRC2)
"13" Valve Power (VPW)
"14" Valve Stem-Product 1 (VST1)
"15" Valve Stem-Product 2 (VST2)
"16" Valve Stem-Product 3 (VST3)
"17" Valve Stem-Product 4 (VST4) __ __
*Note: Or can be used for Master Reset.

Program Program
Code Function Code Description Entry Code
12 Issue/Rev. 03 (8/97)
026 A/C Input 8 Enter: "00" No Assignment (N/A) 026
Terminals 107 & 109 "01" Additive Feedback 1 (AFB1)
"02" Additive Feedback 2 (AFB2)
"03" Additive Feedback 3 (AFB3)
"04" Additive Feedback 4 (AFB4)
"05" Additive Feedback 5 (AFB5)
"06" Additive Feedback 6 (AFB6)
"07" Additive Feedback 7 (AFB7)
"08" Additive Feedback 8 (AFB8)
"09" First/Second High Flow (FSC)
"10" Printer Tray Switch (PTS)*
"11" Permissive 1 Contact (PRC1)
"12" Permissive 2 Contact (PRC2)
"13" Valve Power (VPW)
"14" Valve Stem-Product 1 (VST1)
"15" Valve Stem-Product 2 (VST2)
"16" Valve Stem-Product 3 (VST3)
"17" Valve Stem-Product 4 (VST4) __ __
*Note: Or can be used for Master Reset.
027 A/C Input 9 Enter: "00" No Assignment (N/A) 027
Terminals 108 & 109 "01" Additive Feedback 1 (AFB1)
"02" Additive Feedback 2 (AFB2)
"03" Additive Feedback 3 (AFB3)
"04" Additive Feedback 4 (AFB4)
"05" Additive Feedback 5 (AFB5)
"06" Additive Feedback 6 (AFB6)
"07" Additive Feedback 7 (AFB7)
"08" Additive Feedback 8 (AFB8)
"09" First/Second High Flow (FSC)
"10" Printer Tray Switch (PTS)*
"11" Permissive 1 Contact (PRC1)
"12" Permissive 2 Contact (PRC2)
"13" Valve Power (VPW)
"14" Valve Stem-Product 1 (VST1)
"15" Valve Stem-Product 2 (VST2)
"16" Valve Stem-Product 3 (VST3)
"17" Valve Stem-Product 4 (VST4) __ __
*Note: Or can be used for Master Reset.

Program Program
Code Function Code Description Entry Code
Issue/Rev. 0.3 (8/97) 13
028 A/C Input 10 Enter: "00" No Assignment (N/A) 028
Terminals 110 & 112 "01" Additive Feedback 1 (AFB1)
"02" Additive Feedback 2 (AFB2)
"03" Additive Feedback 3 (AFB3)
"04" Additive Feedback 4 (AFB4)
"05" Additive Feedback 5 (AFB5)
"06" Additive Feedback 6 (AFB6)
"07" Additive Feedback 7 (AFB7)
"08" Additive Feedback 8 (AFB8)
"09" First/Second High Flow (FSC)
"10" Printer Tray Switch (PTS)*
"11" Permissive 1 Contact (PRC1)
"12" Permissive 2 Contact (PRC2)
"13" Valve Power (VPW)
"14" Valve Stem-Product 1 (VST1)
"15" Valve Stem-Product 2 (VST2)
"16" Valve Stem-Product 3 (VST3)
"17" Valve Stem-Product 4 (VST4) __ __
*Note: Or can be used for Master Reset.
Note: For "Remote Start" operation either this code or code 028 must be programmed "11" (Permissive 1 Contact) code 807 must be programmed
"5" (Remote Start) and jumpers must be installed as shown in the Installation Manual (MN06064).
029 A/C Input 11 Enter: "00" No Assignment (N/A) 029
Terminals 111 & 112 "01" Additive Feedback 1 (AFB1)
"02" Additive Feedback 2 (AFB2)
"03" Additive Feedback 3 (AFB3)
"04" Additive Feedback 4 (AFB4)
"05" Additive Feedback 5 (AFB5)
"06" Additive Feedback 6 (AFB6)
"07" Additive Feedback 7 (AFB7)
"08" Additive Feedback 8 (AFB8)
"09" First/Second High Flow (FSC)
"10" Printer Tray Switch (PTS)*
"11" Permissive 1 Contact (PRC1)
"12" Permissive 2 Contact (PRC2)
"13" Valve Power (VPW)
"14" Valve Stem-Product 1 (VST1)
"15" Valve Stem-Product 2 (VST2)
"16" Valve Stem-Product 3 (VST3)
"17" Valve Stem-Product 4 (VST4) __ __
*Note: Or can be used for Master Reset.

Program Program
Code Function Code Description Entry Code
14 Issue/Rev. 03 (8/97)
030 A/C Input 12 Enter: "00" No Assignment (N/A) 030
Terminals 75 & 76 "01" Additive Feedback 1 (AFB1)
"02" Additive Feedback 2 (AFB2)
"03" Additive Feedback 3 (AFB3)
"04" Additive Feedback 4 (AFB4)
"05" Additive Feedback 5 (AFB5)
"06" Additive Feedback 6 (AFB6)
"07" Additive Feedback 7 (AFB7)
"08" Additive Feedback 8 (AFB8)
"09" First/Second High Flow (FSC)
"10" Printer Tray Switch (PTS)*
"11" Permissive 1 Contact (PRC1)
"12" Permissive 2 Contact (PRC2)
"13" Valve Power (VPW)
"14" Valve Stem-Product 1 (VST1)
"15" Valve Stem-Product 2 (VST2)
"16" Valve Stem-Product 3 (VST3)
"17" Valve Stem-Product 4 (VST4) __ __
*Note: Or can be used for Master Reset.
031 RTD #1 Enter: "0" RTD Not Used 031
Terminals 14, 15, "1" Product 1
16, & 17 "2" Product 2
"3" Product 3
"4" Product 4 __
032 RTD #2 Enter: "0" RTD Not Used 032
Terminals 62, 63, "1" Product 1
64, & 65 "2" Product 2
"3" Product 3
"4" Product 4 __

Program Program
Code Function Code Description Entry Code
Issue/Rev. 0.3 (8/97) 15
033 4-20 Channel #1 Enter: Two digit number indicating 033
Terminals 19 & 20 the use of this 4-20 Channel.
First digit:
"0" Channel Not Used
"1" Product 1
"2" Product 2
"3" Product 3
"4" Product 4
Second digit:
"0" Channel Not Used
"1" Temperature
"2" Pressure
"3" Density
(e.g., 11 indicates that this channel
would be used by product 1 for a temperature
input). __ __
34 4-20 Channel #2 Enter: Two digit number indicating 034
Terminals 22 & 23 the use of this 4-20 Channel.
First digit:
"0" Channel Not Used
"1" Product 1
"2" Product 2
"3" Product 3
"4" Product 4
Second digit:
"0" Channel Not Used
"1" Temperature
"2" Pressure
"3" Density
(e.g., 11 indicates that this channel
would be used by product 1 for a temperature
input). __ __
035 4-20 Channel #3 Enter: Two digit number indicating 035
Terminals 68 & 69 the use of this 4-20 Channel.
First digit:
"0" Channel Not Used
"1" Product 1
"2" Product 2
"3" Product 3
"4" Product 4
Second digit:
"0" Channel Not Used
"1" Temperature
"2" Pressure
"3" Density
(e.g., 11 indicates that this channel
would be used by product 1 for a temperature
input). __ __
Other manuals for AccuLoad II
1
Table of contents
Other FMC Technologies Controllers manuals
Popular Controllers manuals by other brands

CD Automation
CD Automation REVEX 1Ph 30A user manual

Trane
Trane Tracer ZN510 Installation, operation, and programming

Smartenit
Smartenit EZIO2X4 5010D quick start guide

SMC Networks
SMC Networks ITV2000-Q Series Installation and maintenance manual

Xylem
Xylem Aquavar IPC quick start guide

Zamel
Zamel exta RTM-20 instruction manual