FRÄNKISCHE profi-air 180 Flat User manual

DRAINAGE SYSTEMS
ELECTRICAL SYSTEMS
BUILDING TECHNOLOGY
INDUSTRIAL PRODUCTS
profi-air®180 flat connection box
Installation and operating instructions

2FRÄNKISCHE
MBA profi-air 180 flat connection box
Table of contents
1 General
2 Intended use 4
3 Structure 4
4 Scope of delivery 4
5.1 Connection options 5
5.2 Dimensional drawing 5
5.3 Schematic wiring diagram 6
5 Technical data
7 Warranty 11
9 Disposal 11
8 Liability 11
1.1 Introduction 3
1.2 Safety 3-4
6 Wiring diagrams 6
6.1 Modbus (connection to the ventilation unit) 7
6.2 Fire/smoke alarm input 7
6.3 Humidistat input 8
6.4 Standby input 9
6.5 External fan activation input 10
6.6 Error message output 10
All information in this publication generally reflects the state of the art at the time of printing. Furthermore, considerable care was taken when preparing this publication. Nevertheless, typesetting
and translation errors cannot be entirely excluded. We also reserve the right to make changes to our products, specifications and other data. Changes may also become necessary as a result of legal,
material-related or other technological requirements, which cannot or can no longer be considered in this publication. For this reason, we cannot assume any liability which is based solely on the data
provided in this publication. The decisive role with regard to the data on products and services is always played by the order placed, the product actually purchased and the documentation in connec-
tion with it, or the information provided by our specialist staff in each specific individual case.

3FRÄNKISCHE
MBA profi-air 180 flat connection box
1 General
These installation and operating instruc-
tions are intended to help you install a
fully functional profi-air 180 flat connec-
tion box and properly operate it. We rec-
ommend that you read these
instructions carefully before you com-
mence installation. These installation
and operating instructions can also
serve as a reference for service and
maintenance work and guarantee
smooth and efficient operation.
If used for its intended purpose, the
device is safe and reliable to operate.
The construction and design are state of
the art and comply with all relevant
DIN / VDE regulations and safety provi-
sions. All safety regulations, warnings
and notices of these installation and
operating instructions have to be com-
plied with; non-compliance may result in
personal injury and/or damage to the
profi-air 180 flat connection box.
nInstallation, connection and taking
into operation of the profi-air 180 flat
connection box must be performed
by authorised and qualified person-
nel only.
nInstallation of the profi-air 180 flat
connection box must be carried out
according to applicable local con-
struction, safety and installation reg-
ulations.
nUnauthorised changes or modifica-
tions of the profi-air 180 flat connec-
tion box are not permitted.
nKeep these installation and operating
instructions near the device during
the entire life of the profi-air 180 flat
connection box.
The profi-air 180 flat connection box
extends the range of electric wiring
options of the profi-air 180 flat ventila-
tion unit.
1.1 Introduction
1.2 Safety
1.2.1 Safety regulations

4FRÄNKISCHE
MBA profi-air 180 flat connection box
1 General
Risk of personal injury
Risk of:
ndamage to equipment
n
errors while operating the device if the instructions are not complied with
correctly
nother material damage
Additional notices
Reference to other sections and/or guidelines of the manufacturer.
Disposal instructions
1.2.3 Symbols used
2 Intended use
3 Structure
The profi-air 180 flat connection box is
an extension of electric connection
options for the profi-air 180 flat ventila-
tion unit. It is connected directly to the
mainboard of the ventilation unit.
The profi-air connection box consists of
a control board with various inputs and
outputs. The control board is incorporat-
ed into a plastic housing which is
installed near the ventilation unit.
4 Scope of delivery
nConnection box incl. 4 PG threaded
connectors
nApprox. 2.5 m of connection cable
wired / with RJ25 connector plug
to connect to the mainboard of the
profi-air 180 flat ventilation unit.
nUSB cable (exclusively for the fac-
tory customer service for firmware
updates)
nInstallation and operating instruc-
tions

5FRÄNKISCHE
MBA profi-air 180 flat connection box
nFire alarm
nStandby switch
nRoom humidistats
nExternal fan activation
nExternal filter alarm
nExternal fault alarm
5 Technical data
5.1 Connection options
5.2 Dimensional drawing
170 mm
140 mm
100 mm

6FRÄNKISCHE
MBA profi-air 180 flat connection box
5 Technical data
5.3 Schematic wiring diagram
6 Wiring diagrams
The profi-air connection box must be wired and put into operation according to the following wiring diagrams.
All connection activities must be performed in the “dead” state only since otherwise
the connection box or the mainboard of the ventilation unit may be damaged.
Pre-heat/cool
Afterheater
AlarmInput
CO₂
Aux
Aftercooler
J6
J11
J7
J8
J9
J10
J12J13
Power In
24VDC
24VDC
24VDC
12V
USB
Fail
OK
Status
Elec. PH
0V
0V
D+
D-
T
Fire
Therm
+-+-
Input Damper 1
Open
Open
Damper 2 ModBus
1
+
2
+
T1GTC
+16V
Standby
Switch
Hygro-
stat
Fail
Alarm
Filter
Alarm
+12V
SDA
SCL
TFAH
T2AH
T2AC
0 - 10V
0 - 10V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 - 10V
0 - 10V
J1 J2 J3 J4 J5
Humidistat input
Filter alarm output
Fault alarm output
Standby input
0 – 10V external fan
activation input
USB connection / rmware Not active
Not active
Not active
Fire/smoke
alarm input
Not active
Not active
Modbus / connection to
pro-air 180 at ventilation
unit and/or connection
to control unit
All connection activities must be carried out by authorised and qualified personnel only.
Additionally, applicable local regulations and safety provisions must be observed.

7FRÄNKISCHE
MBA profi-air 180 flat connection box
6 Wiring diagrams
6.1 Modbus (connection to the ventilation unit)
6.2 Fire/smoke alarm input
The Modbus connection is used to con-
nect the connection box to the main-
board of the profi-air 180 flat ventilation
unit. It is already connected in the deliv-
ery state.
The input can be used to connect the
fire/smoke alarm with a relay output.
When delivered, the contact is furnished
with a bridge. If this contact is interrupt-
ed by, e.g., a triggered fire/smoke alarm,
the control system deactivates the venti-
lation unit. In order to put the ventilation
unit back into operation, it must be com-
pletely disconnected from the power
supply for a short period of time.
Since the external control unit delivered
with the profi-air 180 flat ventilation unit
also uses the Modbus interface on the
mainboard, it must also be connected to
the clamping points of the connection
box on site. Please observe the colour
coding of the wires.
To use the function, the contact must be
connected to the break-contact relay
(see illustration), and the factory-provid-
ed bridge must be removed. If the relay
is in a “live” state, the contact is closed.
If the current at the relay drops, the con-
tact will be broken and the ventilation
unit will be deactivated. The J2 contact
is operated at a maximum of 24 V DC /
300 mA.
For information on the connection to the mainboard of the profi-air 180 flat ventilation unit, see installation
and operating instructions of the ventilation unit.
Pre-heat/cool
Afterheater
AlarmInput
CO₂
Aux
Aftercooler
J6
J11
J7
J8
J9
J10
J12J13
Power In
24VDC
24VDC
24VDC
12V
USB
Fail
OK
Status
Elec. PH
0V
0V
D+
D-
T
Fire
Therm
+-+-
Input Damper 1
Open
Open
Damper 2 ModBus
1
+
2
+
T1GTC
+16V
Standby
Switch
Hygro-
stat
Fail
Alarm
Filter
Alarm
+12V
SDA
SCL
TFAH
T2AH
T2AC
0 - 10V
0 - 10V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 - 10V
0 - 10V
J1 J2 J3 J4
J5
A
1
A
2
1
2
A
1
A
2
1
3
2
Coil driver

8FRÄNKISCHE
MBA profi-air 180 flat connection box
6 Wiring diagrams
6.3 Humidistat input
profi-air room humidistats (Cat. no.
78300841) can be connected to this
input. If the set value at the room humi-
distat is exceeded, the control system
switches the ventilation unit to mode 3.
If the wiring is arranged in parallel, sev-
eral room humidistats can be connected
to the contact.
The digital input on the control board of the ventilation unit can also be used to connect the room humidistats
to the profi-air 180 flat ventilation unit. See profi-air 180 flat operating instructions.
Pre-heat/cool
Afterheater
AlarmInput
CO2
Aux
Aftercooler
J6
J11
J7
J8
J9
J10
J12J13
Power In
24VDC
24VDC
24VDC
12V
USB
Fail
OK
Status
Elec. PH
0V
0V
D+
D-
T
Fire
Therm
+-+-
Input Damper 1
Open
Open
Damper 2 ModBus
1
+
2
+
T1GTC
+16V
Standby
Switch
Hygro-
stat
Fail
Alarm
Filter
Alarm
+12V
SDA
SCL
TFAH
T2AH
T2AC
0 - 10V
0 - 10V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 - 10V
0 - 10V
J1 J2 J3 J4 J5
A
1
A
2
1
2
A
1
A
2
1
3
2
Coil driver

9FRÄNKISCHE
MBA profi-air 180 flat connection box
6 Wiring diagrams
6.4 Standby input
The input can be used to connect the standby switch to the ventilation unit.
If the system has been switched off over a longer period of time, this causes an increased risk of condensation in
the pipes, and/or might lead to moisture damage in the building.
nContact closed – ventilation unit in operation
nContact open – ventilation unit out of operation
Pre-heat/cool
Afterheater
AlarmInput
CO2
Aux
Aftercooler
J6
J11
J7
J8
J9
J10
J12J13
Power In
24VDC
24VDC
24VDC
12V
USB
Fail
OK
Status
Elec. PH
0V
0V
D+
D-
T
Fire
Therm
+-+-
Input Damper 1
Open
Open
Damper 2 ModBus
1
+
2
+
T1GTC
+16V
Standby
Switch
Hygro-
stat
Fail
Alarm
Filter
Alarm
+12V
SDA
SCL
TFAH
T2AH
T2AC
0 - 10V
0 - 10V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 - 10V
0 - 10V
J1 J2 J3 J4 J5
A
1
A
2
1
2
A
1
A
2
1
3
2
Coil driver

10 FRÄNKISCHE
MBA profi-air 180 flat connection box
6 Wiring diagrams
6.5 External fan activation input
6.6 Error message output
The input can be used to control the fan
mode of the ventilation unit using a
0–10 V signal. The activation is carried
out as in the following diagram.
The output can be used to externally
display error messages and filter
alarms. The output signal is 24 VDC.
Pre-heat/cool
Afterheater
Alarm
Input
CO2
Aux
Aftercooler
J6
J11
J7
J8
J9
J10
J12J13
Power In
24VDC
24VDC
24VDC
12V
USB
Fail
OK
Status
Elec. PH
0V
0V
D+
D-
T
Fire
Therm
+-+-
Input Damper 1
Open
Open
Damper 2 ModBus
1
+
2
+
T1GTC
+16V
Standby
Switch
Hygro-
stat
Fail
Alarm
Filter
Alarm
+12V
SDA
SCL
TFAH
T2AH
T2AC
0 - 10V
0 - 10V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 - 10V
0 - 10V
J1 J2 J3 J4 J5
Pre-heat/cool
Afterheater
AlarmInput
CO2
Aux
Aftercooler
J6
J11
J7
J8
J9
J10
J12J13
Power In
24VDC
24VDC
24VDC
12V
USB
Fail
OK
Status
Elec. PH
0V
0V
D+
D-
T
Fire
Therm
+-+-
Input Damper 1
Open
Open
Damper 2 ModBus
1
+
2
+
T1GTC
+16V
Standby
Switch
Hygro-
stat
Fail
Alarm
Filter
Alarm
+12V
SDA
SCL
TFAH
T2AH
T2AC
0 - 10V
0 - 10V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 V
0 - 10V
0 - 10V
J1 J2 J3 J4 J5
Connection of external
0– 10 V control signal

11FRÄNKISCHE
MBA profi-air 180 flat connection box
7 Warranty
8 Liability
Deviating from the applicable GTCs,
the manufacturer grants a warranty of
24 months from the time of comple-
tion of the installation for the profi-air
Warranty expires if
nthe warranty period ends;
nparts not provided by the manufacturer are installed;
nunauthorised changes or modifications to the unit are made.
180 flat connection box. Warranty
claims can only be asserted for
material and/or construction defects
occurring within the warranty peri-
od. In case of a warranty claim, the
profi-air 180 flat connection box may
not be removed without the prior
written consent of the manufacturer.
The profi-air 180 flat connection box
has been developed and produced for
use in so-called comfort ventilation
systems. Any other use is considered
The manufacturer is not liable for damage attributed to the following causes:
nFailure to comply with the safety, operating and maintenance instructions stated herein.
nInstallation of spare parts not provided or stipulated by the manufacturer.
The responsibility for the use of such spare parts rests solely with the installer.
nNormal wear and tear.
“improper” and can lead to damage
to the profi-air flat ventilation unit or
personal injury which the manufac-
turer cannot be held liable for.
In addition, our “General Terms and Conditions” apply as amended, available at www.fraenkische.com.
Please do not dispose of the profi-
air 180 flat connection box with the
normal household waste; please
ask your municipal waste consulting
authority about collection points and
recycling possibilities.
9 Disposal

Rooted in Königsberg –
Our facilities in North America and Mexico:
Anderson, USA
Guanajuato, Mexico
Our facilities in Africa:
Ben Arous, Tunisia
Casablanca, Morocco
FRÄNKISCHE is an innovative, growth-
oriented, medium-sized family-owned
enterprise and industry leader in the
design, manufacturing and marketing
of technically superior corrugated pipe
systems for drainage, electrical, building
technology and industrial applications.
We currently employ about 4,200 people
worldwide. Both our many years of
experience and expertise in plastics pro-
cessing, our consulting services and the
large array of products are highly valued
by our customers.
FRÄNKISCHE is a third generation family
owned business that was established in
1906 and is now run by Otto Kirchner.
Today, we are globally represented with
production facilities and sales offices.
The proximity to our customers enables
us to develop products and solutions
that are perfectly tailored to our cus-
tomers’ needs. Our action and business
philosophy focus on our customers and
their needs and requirements for our
products.
FRÄNKISCHE – Your partner for sophis-
ticated and technologically advanced
solutions.
globally successful!
E.2384/2.01.18 DT | Subject to change without notice | Cat. no. 799.99.582 | 01/2018
FRÄNKISCHE Rohrwerke Gebr. Kirchner GmbH & Co. KG | Hellinger Str. 1 | 97486 Königsberg/Germany
Phone +49 9525 88-2297 | Fax +49 9525 88-2500 | info@fraenkische.de | www.fraenkische.com
Our facilities in Europe:
Königsberg, Germany (headquarters)
Bückeburg, Germany
Schwarzheide, Germany
Okříšky, Czech Republic
St.-Leonards-on-Sea, Great Britain
Moscow, Russia
Yeles/Toledo, Spain
Torcy-le-Grand, France
Ebersbach/Fils, Germany
Hermsdorf, Germany
Mönchaltorf, Switzerland
Milan, Italy
Istanbul, Turkey
Cluj, Romania
Wels, Austria
Our facilities in Asia:
Anting/Shanghai, China
Hangzhou, China
Pune, India
Other manuals for profi-air 180 Flat
3
Table of contents
Other FRÄNKISCHE Accessories manuals
Popular Accessories manuals by other brands

Onvis
Onvis CT3 user manual

CS Instruments
CS Instruments VA 452 Operating instruction

Becker
Becker Centronic VarioControl VC180-II Assembly and operating instructions

Philips
Philips SCF158 Specification sheet

Aveo Engineering
Aveo Engineering VeoLite V2D2 OnePass Compact VC manual

Cornelius
Cornelius Remcor 2849949020 installation instructions