
Power Factor Correction Systems
Commissioning and Maintenance
System location
Standard versions of FRAKO power factor correction systems are
constructed with IP30 ingress protection to EN60529 (in some ca-
ses IP20 and IP54 for small Series LSK systems) and are desig-
ned for operation in dry rooms. The ambient temperature must not
exceed 40°C. Openings are provided in the enclosures for ventila-
tion, and these must not be covered, as this would inhibit the free
circulation of air.
Special versions, such as those constructed for IP54 ingress pro-
tection or for room temperatures over 40°C, or choked systems,
are tted with fan/lter units. If there is any tendency for hot air to
accumulate in the room where the system is installed, it must be
ensured that the room is adequately ventilated.
Fuses and cables
When the installation work is carried out in Germany, the VDE (Ger-
man Association of Electrical Engineers) regulations VDE 0100
and VDE 0105, the general guidelines of the VDEW (German
Electricity Association) and the conditions of supply of the utility
company concerned must be complied with. In other countries the
relevant local regulations must be observed.
VDE 0560 Part 46 states that capacitor units must be suitable for
a continuous r.m.s. current of 1.3 times the current that is drawn
at the sinusoidal nominal voltage and nominal frequency. If the
capacitance tolerance of 1.1×CNis also taken into account, the
maximum allowable current can reach values of up to 1.38×IN.
This overload capability together with the high inrush current to the
capacitors must be taken into account when dimensioning fusess
and cable cross sections.
Note: FRAKO power capacitors offer a current load capacity of 1.5-2.2 × IN
at 400V.
Table 1: Fuses and supply cable cross sections according to VDE 0298
Part 4, installation category C
Cable connections
Each cabinet or wall-mounted enclosure must always be provided
with its own supply cable, with terminals for the L1, L2, L3, N and
PE conductors. If a four-core cable is used, a connection must be
made between the PE and N conductors in order to supply power
to the reactive power control relay and contactor coils.
With wall-mounted systems, either a PG cable gland or a rubber
grommet with a strain relief clip, depending on the power rating
concerned, is provided for cable entry. With freestanding cabinets
the cables enter through the oor of the enclosure.
In the case of systems with a built-in fan / lter unit, care must be
taken that the opening in the oor is closed again after the cables
have been connected, in order to achieve an efcient cooling ef-
fect within the cabinet.
Current transformer
A current transformer is necessary to operate power factor correc-
tion systems. This is not included in FRAKO’s standard scope of
supply, but can be supplied with the system if the requirements in
the customer’s installation have been claried.
The primary current in the current transformer is dictated by the
user’s current consumption, the device being selected on the basis
of the maximum current load or the load connected to the transfor-
mer. The circuit to the reactive power control relay is designed for
a ... / 1 to ... / 5 A current transformer with a rating of 5 VA, Class 3.
If additional instruments are to be operated from the same current
transformer, this must be taken into account when specifying its
rating.
If ammeters are installed in series with the control relay, the rating
of the current transformer must be increased to suit. The internal
power consumption in the control relay circuit amounts to some
1.8VA for a current transformer with 5A nominal current.
Losses also occur in the current transformer wiring, and these
must also be taken into account if there are long lengths of cable
between the current transformer and the reactive power control
relay.
Table 2: Power losses in copper conductors from a current transformer
with a secondary current of 5A.
Note: The current transformer must be installed in any one of the
three phases so that the entire current to the loads requiring po-
wer factor correction and the capacitor current ow through it (as
shown in Figs. 1-3). Terminal P1 (K) is connected to the supply
side, terminal P2 (L) to the load side.
Caution: When the circuit is broken, voltage surges occur which
could destroy the current transformer. The terminals S1 (k) and
S2 (l) must therefore be short-circuited before the current transfor-
mer circuit is broken.
When selecting the current transformer, the step-down ratio must
be considered as well as the installed load, in order to ensure opti-
mum functioning of the reactive power control relay.
Please look up the smallest and largest capacitor stages that can
be switched in as stated in the technical documentation supplied
with the power factor correction system. The minimum and maxi-
mum possible current transformer step-down ratios can then be
obtained from Table 3 below.
230V/50Hz 400V/50Hz 525V/50Hz
Power Current Fuse Cross section Current Fuse Cross section Current Fuse Cross section
in kVAr en A in A en mm2in A in A in mm2in A in A in mm2
2.50 6.3 10 4×1.5 3.6 10 4×1.5 2.7 10 4×1.5
5.00 12.6 20 4×2.5 7.2 10 4×1.5 5.5 10 4×1.5
6.25 15.7 25 4 × 4 9.0 16 4×2.5 6.9 10 4×1.5
7.50 18.8 35 4 × 6 10.8 16 4×2.5 8.2 16 4×2.5
10.00 25.1 35 4 × 6 14.4 20 4×2.5 11.0 16 4 × 2.5
12.50 31.4 50 4×10 18.0 25 4 × 4 13.7 20 4×2.5
15.00 37.7 63 4×16 21.7 35 4 × 6 16.5 25 4 × 4
17.50 43.9 63 4×16 25.3 35 4 × 6 19.2 35 4 × 6
20.00 50.2 80 3 × 25 / 16 28.9 50 4×10 22.0 35 4 × 6
25.00 62.8 100 3 × 35 / 16 36.1 50 4×10 27.5 50 4×10
27.50 69.0 100 3 × 35 / 16 39.7 63 4×16 30.2 50 4×10
30.00 75.3 125 3 × 50 / 25 43.3 63 4×16 33.0 50 4×10
31.25 78.4 125 3 × 50 / 25 45.1 63 4×16 34.4 50 4×10
37.50 94.1 160 3 × 70 / 35 54.1 80 3 × 25 / 16 41.2 63 4×16
40.00 100.4 160 3 × 70 / 35 57.7 80 3 × 25 / 16 44.0 63 4×16
43.75 109.8 160 3 × 70 / 35 63.1 100 3 × 35 / 16 48.1 80 3 × 25 / 16
45.00 113.0 160 3 × 70 / 35 65.0 100 3 × 35 / 16 49.5 80 3 × 25 / 16
50.00 125.5 200 3 × 95 / 50 72.2 100 3 × 35 / 16 55.0 80 3 × 25 / 16
52.50 131.8 200 3 × 95 / 50 75.8 125 3 × 50 / 25 57.7 80 3 × 25 / 16
60.00 150.6 250 3 × 120 / 70 86.6 125 3 × 50 / 25 66.0 100 3 × 35 / 16
62.50 156.9 250 3 × 120 / 70 90.2 125 3 × 50 / 25 68.7 100 3 × 35 / 16
67.50 169.4 250 3 × 120 / 70 97.4 160 3 × 70 / 35 74.2 125 3 × 50 / 25
68.75 172.6 250 3 × 120 / 70 99.2 160 3 × 70 / 35 75.6 125 3 × 50 / 25
75.00 188.3 315 3 × 185 / 95 108.3 160 3 × 70 / 35 82.5 125 3 × 50 / 25
87.50 219.6 315 3 × 185 / 95 126.3 200 3 × 95 / 50 96.2 160 3 × 70 / 35
93.75 235.3 400 2 × 3 × 95 / 50 135.3 200 3 × 95 / 50 103.1 160 3 × 70 / 35
100.00 251.0 400 2 × 3 × 95 / 50 144.3 200 3 × 95 / 50 110.0 160 3 × 70 / 35
112.50 282.4 400 2 × 3 × 95 / 50 162.4 250 3 × 120 / 70 123.7 200 3 × 95 / 50
120.00 301.2 500 2 × 3 × 120 / 70 173.2 250 3 × 120 / 70 132.0 200 3 × 95 / 50
125.00 313.8 500 2 × 3 × 120 / 70 180.4 250 3 × 120 / 70 137.5 200 3 × 95 / 50
150.00 376.5 630 2 × 3 × 185 / 95 216.5 315 3 × 185 / 95 165.0 250 3 × 120 / 70
175.00 439.3 630 2 × 3 × 185 / 95 252.6 400 2x 3 × 95 / 50 192.5 315 3 × 185 / 95
200.00 502.0 800 2 × 3 × 240 / 120 288.7 400 2 × 3 × 95 / 50 219.9 315 3 × 185 / 95
225.00 – – – 324.8 500 2 × 3 × 120 / 70 247.4 400 2 × 3 × 95 / 50
250.00 – – – 360.8 500 2 × 3 × 120 / 70 274.9 400 2 × 3 × 95 / 50
275.00 – – – 396.9 630 2 × 3 × 185 / 95 302.4 500 2 × 3 × 120 / 70
300.00 – – – 433.0 630 2 × 3 × 185 / 95 329.9 500 2 × 3 × 120 / 70
350.00 – – – 505.2 800 2 × 3 × 240 / 120 384.9 630 2 × 3 × 185 / 95
375.00 – – – 541.3 800 2 × 3 × 240 / 120 412.4 630 2 × 3 × 185 / 95
400.00 – – – 577.4 800 2 × 3 × 240 / 120 439.9 630 2 × 3 × 185 / 95
Cross section Losses per metre of
in mm2two-core cable in VA
2.5 0.36
4.0 0.22
6.0 0.15
10.0 0.09