Franklin Electric SubDrive Connect Plus SDCP-SUB0723 User manual

SubDrive Connect Plus
QUICKSTART GUIDE
English
EN
QUICKSTART GUIDE
Physical Installation
Environmental Requirements
The drive is intended for operation in ambient temperatures from -13 °F to 122 °F (-25 °C to 50 °C).
• Allow at least 6 inches (15.24 cm) of clearance on all sides of the unit for air flow.
The drive is suitable for outdoor use with a NEMA 3R rating, provided:
• Mount the drive on a back plate 6” (15 cm) larger than the outer dimensions of the
enclosure in order to maintain the NEMA 3R rating.
• The unit must be mounted vertically with the wiring end oriented downward, and the
cover must be properly secured (also applies to indoor installations).
• NEMA 3R enclosures are capable of withstanding downward-directed rain only.
Protect from hose-directed or sprayed water as well as blowing rain.
Mounting the Drive
1. Mount the drive using all three keyhole slots on the top side of the enclosure.
2. At least two keyhole screws at the top must attach to a solid structure such as a stud or
brace.
3. Secure the three additional mounting holes on the bottom.
4. All six screw hole locations should be used to ensure the drive is securely mounted.
IMPORTANT: Do not drill holes in the drive.
Risk of damage to drive, or malfunction can occur due to improper handling,
installation, or environment.
• Install in a location where temperature is within the range of product rating.
• Mount VFD vertically (top up) for proper heat dissipation.
• Do not mount VFD in direct sunlight or near other heat sources.
• Do not install in corrosive environments.
• Install away from direct sunlight and extreme temperatures or humidity.
• Installation of non-approved screening may damage the drive and/or reduce output.
Cold Air
6 in mín.
(15.25 cm)
Warm Air
6 in mín.
(15.25 cm)
6 in mín.
(15.25 cm)
6 in mín.
(15.25 cm)
Risk of bodily injury or damage to drive or other equipment.
• The drive should be mounted on a structure such as a wall or post capable of supporting the weight
of the unit, at least 18” (45.7 cm) above the ground.
• The drive must be mounted on a heat-resistant back plate.
• Ensure suitable mounting hardware is used when installing the drive.
• Do not install the drive on unreinforced drywall.
• Use two persons when lifting the drive for transport or installation. If using lifting equipment, it must
be in good condition and rated for at least 5 times the weight of the drive.
• Wear protective gloves while installing the drive to guard against sharp edges.
This QuickStart Guide
includes basic installa-
tion, setup, and opera-
tion information.
For additional important
safety and operation
information, please refer
to the
SubDrive Connect Plus
Owner’s Manual
and the AIM Manual
available at:
www.franklinwater.com.

QUICKSTART GUIDE
Electrical Installation
2
Electrical Installation
Wiring Guidelines
1. Wire directly to the service entrance. Do not connect to a sub-panel.
2. Use a dedicated branch circuit for the drive.
3. Route motor wiring out of the building as soon as possible. Separate input power and motor wiring by
at least 8 in. (20.3 cm).
4. Cross over other branch circuits and facility wiring at a 90 angle. If it is necessary to run wiring in par-
allel, separate by at least 8 in. (20.3 cm).
5. All control wiring—sensors, switches, transducers, etc.—should be in a separate conduit routed individu-
ally, not parallel, from high voltage wiring. In addition, any shielded cables should be properly grounded.
Branch Circuit Protection
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protec-
tion must be provided in accordance with the National Electrical Code and any additional local codes, or the
equivalent. Drive shall be protected by fast-acting Class T fuses only.
Terminal Block Wire Size
Maximum Torque
Do not use power tools to tighten terminal block screws, use hand tools only. Tighten terminal block screws
to a maximum torque of:
AWG 20 to AWG 6 - 15 in-lbs (1.7 Nm)
AWG 20 to AWG 2 - 31 in-lbs (3.5 Nm)
AWG 16 to AWG 2/0 - 50 in-lbs (5.5 Nm)
Risk of damage to VFD, or malfunction can occur.
Follow all wire routing and grounding instructions carefully. Inductive currents caused by parallel wiring, or close
proximity between high voltage and control wiring can cause unexpected behaviors.
• Do not run input power and motor wires in the same conduit.
• Do not run motor wires from multiple VFDs in common conduit.
• Do not run any wiring through the airflow channel in the back of the drive.
• Do not run control wiring parallel with high voltage wiring.
• Do not install a magnetic contactor or disconnect in the motor circuit.
• Do not run VFD wiring parallel with house or out-building wiring.
• Do not use aluminum wires for VFD connections.
• Do not use with a Ground Fault Circuit Interrupter (GFCI).
• All wiring must comply with the National Electrical Code and local codes.
• Improper splicing or damage to motor cable insulation may expose the conductor(s) to moisture and can pro-
duce motor cable failure.
• For retrofit application, make sure to check the integrity of power and motor leads. This requires measuring the
insulation resistance with a suitable megohm-meter.
Frame Size Input Terminal Block
SDC Plus All Models Output Terminal Block
SDC Plus SUB Models Output Terminal Block
SDC Plus CEN Models
Min AWG Max AWG Min AWG Max AWG Min AWG Max AWG
Frame 2 20 6 20 2 20 6
Frame 3 20 2 16 2/0 20 2

QUICKSTART GUIDE
Electrical Installation
3
Power Wiring Connections
Incoming Power Supply
Before connecting power to drive, test incoming voltages as follows:
•230V Models: The line to line and line to ground voltage must be 190-253V (208-230V ±10%). The line
to ground voltage must be less than or equal to 253 V.
•460V Models: The line to line and line to ground voltage must be 414-506V (460V ±10%). The line to
ground voltage must be less than or equal to 506 V.
If line to line voltage exceeds these ratings, the drive cannot be used on the incoming power supply. An
additional suitably sized transformer will be required to bring the voltages within limits.
IMPORTANT: If line to ground voltage exceeds these ratings, remove Power Board EMC jumpers from J10
and J11 (four total). This is common in applications supplied by a Corner-Grounded Delta transformer. Refer
to the NOTICE above.
1. Incoming Power terminal block.
2. Power Out to Motor terminal block. If the drive is equipped with a dV/dt
(EMI) filter, this terminal block is pre-wired to the dV/dt filter. The motor
is wired to the terminal block on the dV/dt filter.
3. J10 Jumper location (two jumpers here).
4. J11 Jumper location (two jumpers here).
Ground Connections
1. Make sure a service entrance ground rod is properly installed and connected.
2. An input power ground wire from the supply panel must be connected to the drive.
3. A dedicated output ground wire from the drive must be connected to the motor. Motor and ground
wires must be bundled together.
Contact with hazardous voltage could result in death or serious injury.
• Disconnect and lock out all power before installing or servicing equipment.
• Connect the motor, the drive, metal plumbing, and all other metal near the motor or cable to the
power supply ground terminal using wire no smaller than motor cable wires.
• Close any open conduit holes before finishing installation.
Risk of damage to drive, or malfunction can occur.
• Power source line to line, and line to ground voltages must be measured before connecting the
drive. If line to ground voltage exceeds specification, both pins of EMC jumper J10 must be removed
to prevent damage to the drive. Refer to “Incoming Power Supply” below.
• Ensure that the system is properly grounded all the way to the service entrance panel. Improper
grounding may result in loss of voltage surge protection and interference filtering.
12
3 4

QUICKSTART GUIDE
Electrical Installation
4
Power Circuit and Motor Connections
NOTE: Do not use power tools to tighten these screws, use hand tools only. Refer to “Maximum Torque” on
page 2 for wire size and torque information.
1. Power Input Connector: Remove one of the knockouts on the bottom left side of the drive. Route the
incoming power leads through the opening on the bottom left side of the drive and connect them to
the Power Board terminal block (#1 above).
• Use positions marked L1, L2, and (Ground) for 230 VAC single-phase incoming power.
• Use positions marked L1, L2, L3, and (Ground) for three-phase incoming power.
2. J10, J11 EMC Jumper: If any line to ground measurements exceed specification, these jumpers must be
removed (four jumpers total). Refer to “Incoming Power Supply” on page 3.
3.
Output to Motor:
Route the motor leads through the opening on the bottom center of
the drive (large opening) and connect them to the terminal block (#3 above) positions
marked
(Ground), Red (W), Yellow (V), and Black (U).
For drives that include a dV/dt filter, motor connections are made at the terminal block on
the left side of the dV/dt filter (#3 at right). In this case, the terminals are marked
(Ground), Red (U), Yellow (V), and Black (W).
NOTE: Relay terminals accept wire sizes from 12 to 26 AWG and should be tightened
to a torque of 3 in-lbs (0.35 Nm). Do not use power tools to tighten these screws, use
hand tools only.
4. System Run Relay: This connection activates whenever the system is actively pump-
ing. Both normally-open (NO) and normally-closed (NC) contacts are provided. The
contacts are rated 5 A at 250 VAC/30 VDC for general purpose loads, or 2A at 250
VAC/30 VDC for inductive loads (i.e. relay).
5. System Alarm Relay: This connection activates whenever the system is faulted. Both
normally-open (NO) and normally-closed (NC) contacts are provided. The contacts
are rated 5A at 250VAC/30VDC for general purpose loads, or 2A at 250VAC/30VDC for inductive loads
(i.e. relay).
NOTE: These relays are not suitable for use on low voltage isolated circuits, and not recommended to
control critical systems (chemical dosing, etc.).
1
2
3
4 5
2
3

QUICKSTART GUIDE
Electrical Installation
5
Control Circuit Connections
NOTE: All control terminals accept wire sizes from 12 to 26 AWG and should be tightened to a torque of
3 in-lbs (0.35 Nm) maximum. Do not use power tools to tighten these screws.
1. Pressure Transducer – When using a pressure transducer:
• Connect the red cable lead to the TRANSDUCER +24 terminal.
• Connect the black cable lead to the – terminal.
• Connect the shield wire (when applicable) to the S terminal.
NOTE: An included 200 PSI transducer is included with the drive.
2. Pressure Sensor – When using a standard pressure sensor:
• Connect the sensor leads (interchangeable) to the Pressure Sensor terminals.
3. Hand/Auto Switch – Connect a dry contact switch to this terminal to select Hand or Auto modes. In
Auto mode (this terminal is open), the drive will regulate pressure. In Hand mode (terminal is
closed), the drive will run at a fixed frequency. The frequency can be selected via the up/down but-
tons.
4. Run/Stop Switch – Connect a dry contact switch to this terminal to select Run or Stop modes. The
drive will operate regularly when this terminal is open. The drive will stop the motor if this terminal
is closed.
NOTE: When Stop is selected, the drive motor will stop even if the drive is in Auto mode.
5. PT100/1000 – Connector for external RTD temperature sensor.
• I+ Positive connection for excitation current circuit for two, three, and four wire PT100/PT1000
RTD sensors.
• V+ Positive connection for voltage sensing circuit for two, three, and four wire PT100/PT1000
RTD sensors.
• I-/V- Negative connections for the excitation and voltage sensing circuits for two, three, and
four wire PT100/PT1000 RTD sensors.
6. Moisture Sensor – The WET SENSOR terminal supports the Franklin Electric Moisture Sensor.
• Connect the red cable lead to the +24 terminal.
• Connect the black cable lead to the terminal.
• Connect the white cable lead to the I+ terminal.
• Connect the green cable lead to the I– terminal.
7. Dual Setpoint – The drive will regulate to Pressure Setpoint 1 when this terminal is open. Pressure
Setpoint 2 is active when this terminal is closed.
8.
Analog (4-20mA) Output
– The 4-20mA Analog Output allows the user to repeat the incoming
Pressure Transducer 4-20mA signal. Additionally, DIP SW1 Position 4 can be toggled to output a 4-
20mA signal of the motor speed.
9. MultiDrive – Setup in the mobile app only. Connections should be from each terminal to the corre-
sponding terminal on the next drive(s) in series.
• Shield wires should be connected together and grounded on one end only.
• DIP Switch SW7 - Position 2 (to the left of the connector) should be in the Up (On) position for
the first and last drives in the series.
10. Digital Input – This feature will be used in the future.

QUICKSTART GUIDE
Drive Configuration
6
Drive Configuration
To adjust system settings, make sure power is off for five minutes, and remove the cover. Then, power the drive to make menu and
DIP switch changes. When changes are complete, power off the drive before replacing the cover.
DIP Switch Settings
DIP switch changes can be made with the drive powered and
will take effect immediately.
Basic Setup (DIP SW1 – Position 1)
DIP SW1 Position 1 (FE Connect mobile app switch) must be in
the OFF (down) position for DIP switch settings to be recognized. If the switch is in the ON (up) position, the drive can be pro-
grammed using the SubDrive Connect Plus mobile app. This setting disables DIP switch control and app programming overrides
any manual DIP switch settings. Refer to “FE Connect Mobile App for SubDrive Connect Plus” on page 10 for more information.
NOTE: The menu-based settings can be changed regardless of the position of this DIP switch.
Carrier Frequency Switch (DIP SW1 – Position 2)
In CEN applications where audible electrical noise can be heard from the motor, increasing the carrier frequency (CF) can help
reduce or eliminate audible electrical noise.
• Carrier frequency setting is 2.5 kHz when the switch is in the off (down) position.
• Carrier frequency setting is 8 kHz when the switch is in the on (up) position.
NOTE: SUB drive models (filtered drives) do not allow 8 kHz.
Pipe Fill Switch (DIP SW1 – Position 3)
When enabled, the Pipe Fill (PF) feature will run the motor at reduced speed while the pipes fill with water. This can reduce water
hammer in some systems, building up pressure in a controlled manner.
• The Pipe Fill feature is disabled when the switch is in the off (down) position.
• The Pipe Fill feature is enabled when the switch is in the on (up) position.
NOTE: Additional configuration of the Pipe Fill feature is available in the SubDrive Connect Plus mobile app.
Analog Output Selection (DIP SW1 – Position 4)
Use this switch (AO) to select the signal to be repeated on the 4-20mA Output terminal.
• The analog output is proportional to the motor speed value when the switch is in the off (down) position.
• The analog output repeats the 4-20mA transducer reading when the switch is in the on (up) position.
Bump Mode Configuration (DIP SW1 – Position 5)
Bump mode controls how hard the drive will pump just before stopping the motor when the pressure setpoint is reached. For
applications with a large pressure tank, or if the system takes too long to stop, place the switch in the ON (up) position for a more
aggressive bump.
• Test system behavior to ensure proper operation.
NOTE:
Additional configuration of the Bump Mode feature is available in the SubDrive Connect Plus mobile app.
Broken Pipe Protection (DIP SW1 – Position 6)
When enabled (in Auto mode only), this feature stops the system and displays a Fault condition if the drive runs at full speed for 10
minutes without reaching the pressure setpoint.
If the system is used with a sprinkler system or is being used to fill a pool or cistern, the feature should be disabled.
• The Broken Pipe fault is disabled when the switch is in the off (down) position.
• The Broken Pipe fault is enabled when the switch is in the on (up) position.
NOTE:
Additional configuration of the Broken Pipe feature is available in the SubDrive Connect Plus mobile app.
ON
AO AB BPCF PF
SW1
12345678

QUICKSTART GUIDE
Drive Configuration
7
Menu Settings
To adjust system settings, make sure power is off, and remove the
cover. Then, power the drive to make menu changes. When changes
are complete, power off the drive before replacing the cover.
Use the arrow keys to the right of the Display to navigate through the
setup menus.
• The right arrow moves from screen to screen, and also functions
as an Enter key.
• The up and down arrows scroll through the available options on
each screen.
• When a selection has been made, you must press the Enter key
(right arrow) for the setting to take effect.
NOTE: If DIP SW1 – Position 1 is ON, settings can be made either through the manual display, or through the mobile app. Changes in
either tool are reflected in the other. Power cycling the drive is not required for menu based or DIP switch settings to take effect.
Menu Navigation
Home Screen: In normal operation, this screen displays the current system status. During setup, pressing the Enter key (right
arrow) changes the display to the Motor Type screen.
Motor Type: Configures the drive for the type of motor being used. Selecting SUB configures the drive for use with a submersible
motor. Selecting CEN configures the drive for an above-ground, centrifugal motor.
NOTE: SUB drive models can be configured for either type. CEN drive models can only be configured for CEN pump/motor type.
Max Amps: The Max Amps value is used to configure various protection features (pump underload, motor overload, etc.). This
value should match the Service Factor Amps or Maximum Amps rating listed on the motor nameplate.
Sensor Type: Configures the drive for the type of pressure transducer or sensor being used. Selecting Transducer displays the Sensor
Range screen. If a standard Pressure Sensor is selected, the target pressure is set using the adjusting screw on the sensor itself. The Sys-
tem Response screen is displayed next for Pressure Sensor use.
Sensor Range: This is only configurable when the sensor type is transducer. This setting scales system operation to the installed
transducer. The range is 100 to 300, with a default setting of 200 PSI. When changing, the setting changes in 10 PSI increments.
Setpoints: Drive speed control is based on the difference between the setpoint and the transducer feedback value. As user
demand (flow) causes pressure changes, the drive varies the output frequency (motor speed) to maintain pressure at or near the
target setpoint. There are two user configurable setpoints in the system—Setpoint 1 and Setpoint 2. If an application has different
pressure requirements for specific uses, the dual setpoint feature can be used by connecting a switch to the Dual Setpoint terminal
block on the control board. Refer to “Control Circuit Connections” on page 5. When the dual setpoint input is open, Setpoint 1 is
used for pressure control. When the input is closed, Setpoint 2 is used.
•Setpoint 1: When using a Pressure Transducer, use this screen to set the desired target pressure the system will maintain
during normal operation. Recommended maximum value is 5% less than sensor max for proper operation.
•Setpoint 2: Set an alternate setpoint here.
NOTE: Factory defaults for the Setpoints are 0 PSI. This puts the drive in the Sleep/Stop state, keeping the drive from running while
programming takes place. The Drive will run 5 seconds after SETPOINT 1 is adjusted above 0 PSI and NEXT button is pressed.
IMPORTANT: Monitor pressure gauge during initial startup to ensure system does not over-pressurize.
Home Motor
Type
Max Amps Sensor
Type
Sensor
Range
Setpoint 1 Setpoint 2 Drawdown System
Response
Underload
Sensitivity
Underload
Off Time
Submersible
Centrifugal
Transducer
Pres. Sensor
Pressure Sensor Only
Transducer Only
QR Code
Press
Down
button to
view Fault
Logs 1-5

QUICKSTART GUIDE
Drive Configuration
8
Drawdown: When using a pressure transducer, a pressure offset can be set to allow for more water to be drawn from the pressure
tank before a sleeping drive will start. This will reduce sleep/wakeup cycles.
For example, a system setpoint pressure of 50 PSI and a drawdown value of 20 PSI would cause the drive to maintain system pres-
sure at 50 PSI when running; however when the system is idle, the drive will not start the motor until the system pressure drops
below 30 PSI.
System Response: System response time affects how the drive reacts to the pressure transducer/sensor feedback. Faster response
times can improve pressure stability in some systems. However, if the response is too fast, the system could overshoot, leading to
overpressure, rapid cycling, or hydraulic noise. Selections include SLOW, MEDIUM, FAST, and Custom. These control the following
configuration items:
• Proportional Gain, default = 500
• Integral Time, default = 25 (2.5 seconds)
• Ramp Time, default = 10 (1.0 seconds)
• Acceleration Time, default = 2s for SUB, 20s for CEN
• Deceleration Time, default = 2s for SUB, 20s for CEN
Underload Sensitivity: The drive is configured to ensure detection of Underload faults in a wide variety of pumping applications. In
rare cases (as with certain pumps in shallow wells), this trip level may result in unnecessary faults. If the pump is installed in a shal-
low well, activate the drive and observe system behavior. Once the system begins to regulate pressure, check operation at several
flow rates to make sure the default sensitivity does not cause false Underload trips.
•Shallow Set: If the pump is installed in an extremely shallow well and the system continues to trip, then adjust to a lower sen-
sitivity setting. Check the Underload trip level and repeat as necessary.
•Deep Set: In cases where the pump is set very deep, run the system at open discharge to pump the well down and observe
carefully that an Underload is detected properly. If the system does not trip as it should, adjust to a higher sensitivity setting.
Underload Off Time: This setting determines how long the drive will wait before attempting to run after an Underload event. The
default is Smart Reset, but is user-adjustable from 5 minutes to 24 hours.
• Smart reset will set the underload off time to 5 minutes for the first fault. If the drive faults again immediately following the 5
minute off time, the next off time is doubled.
QR Code: This screen displays a code identifying the drive for connection to the mobile app. This screen also displays the software
version and the drive/motor voltage.
Fault Codes: While the QR code is displayed, pressing the DOWN button causes the display to scroll through the last five fault
codes beginning with the most recent one. The display shows the Fault Log Number (1-5), Fault Code, Fault Description, Date/Time
(shown as mm/dd/yy hh:mm:ss).
Special Functions
Reset to Factory Settings: From the HOME screen, press and hold the UP/DOWN/NEXT buttons at the same time for 3 seconds. A con-
firmation screen (Are you sure?) appears in the display. Choosing YES restores all programmable parameters to factory default set-
tings (fault history is NOT cleared). Choosing NO reverts back to the HOME SCREEN.
MANUAL STOP Mode: From the HOME screen, press and hold UP/DOWN buttons together for 2 seconds to manually place the
drive in STOP mode. The display shows STOP in the upper right corner of the HOME screen where RUN/STOP status is shown (same
as placing a jumper on the RUN/STOP input terminal).
When activated, MANUAL STOP displays centered at bottom of HOME screen where the motor speed (HZ) and output current (A)
readouts were displayed.
Pressing the UP/DOWN buttons again for 2 seconds removes the drive from manual stop mode.

QUICKSTART GUIDE
Operation
9
Operation
Hand/Auto Mode
When powered up, the drive reads the signal on Control Board J10 (Hand/Auto). If a Hand/Auto switch is not
used, the absence of a connection here appears as an open switch, and puts the drive in Auto mode. When a
Hand/Auto switch is used, an open switch puts the drive in Auto mode. In Auto mode, the drive controls the
pump to maintain a constant pressure.
If a Hand/Auto switch is connected to Control Board J10 (Hand/Auto), closing the switch puts the drive in
Hand mode. Hand mode runs the pump at a constant speed (default is 60 Hz, shown in the display). Hand
mode allows the drive to be run at full speed without a pressure transducer for longer periods of time as in
the case of new well development or system start up. Moving the switch back to Auto mode resumes the
automatic pressure tracking and control by the VFD.
System Status
When the drive is controlling the motor and pump, the display is illuminated
and the following information is shown:
1. Whether the system is in HAND or AUTO mode.
2. Whether the motor is running (RUN) or stopped (STOP).
3. When using a pressure transducer, the system displays the current sys-
tem pressure in PSI.
When using a standard pressure sensor, the system displays the current motor speed (in Hz).
When running in HAND mode, the system displays the keypad frequency setpoint.
4. When using a pressure transducer in AUTO mode, the motor speed is displayed at the lower left of the
screen. In HAND mode, current system pressure is displayed.
When using a standard pressure sensor, this field is not displayed.
5. The lower right of the screen displays output current in Amps.
6. The Bluetooth icon indicates that the VFD is connected to a mobile device running the FE Connect -
SubDrive Connect Plus mobile app. A thermometer icon displayed at the left side of the screen indi-
cates the drive is in Over Temperature Foldback
Fault Detected
If a fault condition occurs, the drive displays the Fault Code and Fault Description.
Several faults reset automatically, displaying a countdown timer until the reset occurs.
Pressing the DOWN button while the countdown timer is active resets the fault immedi-
ately. For faults that require a manual reset, turn off power to the drive (power cycle) and
restart after five minutes.
Refer to “Diagnostic Fault Codes” on page 11 for details.

QUICKSTART GUIDE
FE Connect Mobile App for SubDrive Connect Plus
10
FE Connect Mobile App for SubDrive Connect Plus
The SubDrive Connect Plus companion app is an intuitive way to wirelessly configure and control your VFD.
It provides features such as:
• Simple, application-based setup for quick and easy startup
• Create templates for fast configuration of multiple drives
• MultiDrive set up and control
• Informational dashboard for visual monitoring of system performance
• Mobile control mode for easy Hand mode operation
• In-app troubleshooting with fault time and date logging
• Email system logs directly to FE support
• Wireless drive firmware updates from your phone
Search for FE Connect in your mobile device’s app store. In the search results, locate the FE Connect Sub-
Drive Connect + app and install it. Once installed, the app icon is named SubDrive Plus.
Setup Bluetooth Connection
After installing the SubDrive Plus app, use the following procedure to connect to the drive:
1. From the Home screen, tap “Connect New Product.”
2. On the New Product Wizard screen, tap either Scan QR Code or Enter the Bluetooth Key.
3. If using the scanning tool, center the QR code on the drive in the screen. The code is displayed on the
VFD display and on a sticker to the right of the display. Refer to “Menu Navigation” on page 7.
4. If using the Bluetooth key, (also available onscreen) enter it in the box provided.
5. Enter a Name and Location to identify the drive within the app.
6. Tap Finish & Connect to complete the connection.
Using the Mobile App
To communicate with a SubDrive Connect Plus that has been paired with the app:
1. On the My Products screen, tap the name of the drive to connect to the device and enter the Dashboard.
2. Tap the MENU button to for a list of options.
3. Tap Setup to change VFD settings.
IMPORTANT: We recommend that the app be updated before going to installation site. Open the app when
connected to the internet to get the latest update.

QUICKSTART GUIDE
Troubleshooting
11
Troubleshooting
Diagnostic Fault Codes
Code Reset Fault Possible Cause Corrective Action
F1 Auto Motor Underload • Over-pumped well
• Broken shaft or coupling
• Blocked screen, worn pump
• Air/gas locked pump
• Underload Sensitivity setting
incorrect
• Frequency near maximum with load less than configured ULD
sensitivity
• System is drawing down to pump inlet (out of water)
• High static, light loading pump - reset for less sensitivity if not out of
water
• Check pump rotation, reconnect if necessary for proper rotation
• Air/gas locked pump - if possible, set deeper in well to reduce
F2 Auto Undervoltage • Low line voltage
• Misconnected input leads
• Loose connection at breaker or panel
• Line voltage low,
• Check incoming power connections and correct or tighten if necessary
• Correct incoming voltage - check breaker or fuses, contact power
company
F3 Auto Overcurrent or
Locked Pump • Motor and/or pump locked
• Abrasives in pump
• Excess motor cable length
• Amperage above SFL at 30 Hz
• Remove and repair or replace as required
• Reduce motor cable length. Adhere to Maximum Motor Cable Length
table.
F5 Manual Open Phase • Loose connection
• Defective motor or drop cable
• Wrong motor
• Open reading on DC test at start.
• Check drop cable and motor resistance, tighten output connections.
• Use dry motor to check drive functions.
F6 Manual Short Circuit • When fault is indicated immediately
after power-up, short circuit caused
by a shorted connection, defective
cable, splice or motor
• Amperage exceeded 25 amps on DC test at start or SF amps during
running
• Incorrect output wiring, phase to phase short, phase to ground
• If fault is present after resetting and removing motor leads, replace
drive
F7 Auto Overheated Drive • High ambient temperature
• Direct sunlight
• Obstruction of airflow
• Fan blocked or inoperable, ambient above 122 °F (50 °C), direct
sunlight
• Replace fan or relocate drive as necessary
• Remove debris from fan intake/exhaust
F9 Manual Internal PCB Fault • A fault was found internal to drive • Contact Technical Service
F12 Auto Overvoltage • High line voltage
• Internal voltage too high
• Check incoming power connections and correct or tighten if necessary
• If line voltage is stable and within range, contact Technical Service
F14 Manual Broken Pipe • Broken pipe or large leak is detected
• Drive runs at full power for 10
minutes without reaching pressure
setpoint
• Large water draw does not allow
system to reach pressure setpoint
• Check system for large leak or broken pipe
• If the system contains a sprinkler system or is being used to fill a pool
or cistern, disable the Broken Pipe Detection
F15 Manual Phase Imbalance • Motor phase currents differ by >20%
• Motor is worn internally
• Motor cable resistance is not equal
• Incorrect motor phase setting
• Check resistance of motor cable and motor windings
• Verify motor type matched drive settings (single- or three-phase)
F16 Manual Ground Fault • Motor cable is damaged
• Phase to ground short
• Check motor cable insulation resistance with megger (while not
connected to drive). Replace motor cable if needed.
F25 Manual Moisture Sensor
Fault • Moisture or water detected
• Input is incorrectly configured
• Check Moisture Sensor location for moisture or presence of water.
• Ensure Moisture Sensor input is configured correctly
F27 Auto Pressure Trans-
ducer Error • Transducer has failed
• Transducer is incorrectly wired
• Transducer signal is out of range
• Transducer is disconnected
• Incorrect sensor type setting
• Check pressure transducer wiring connections
• Ensure sensor type setting is correct
• Replace pressure transducer

800.348.2420 | franklinwater.com
For technical assistance, parts, or repair, please contact:
Form 226203202 Rev. 000 09/20 Copyright © 2020, Franklin Electric, Co., Inc. All rights reserved.
Safety Information
This equipment should be installed and serviced by technically
qualified personnel who are familiar with the correct selection
and use of appropriate tools, equipment, and procedures. Failure
to comply with national and local electrical and plumbing codes
and within Franklin Electric recommendations may result in elec-
trical shock or fire hazard, unsatisfactory performance, or equip-
ment failure.
Read and follow instructions carefully to avoid injury and prop-
erty damage. Do not disassemble or repair unit unless described
in this manual.
Failure to follow installation or operation procedures and all
applicable codes may result in the following hazards:
Product Specific Precautions
High voltages capable of causing severe
injury or death by electrical shock are
present in this unit.
• To reduce risk of electrical shock, disconnect power before work-
ing on or around the system. More than one disconnect switch
may be required to de-energize the equipment before servicing.
• Make sure the ground terminal is connected to the motor, con-
trol enclosures, metal plumbing, and other metal near the motor
or cable using wire no smaller than motor cable wires.
Risk of bodily injury, electric shock,
or property damage.
• This equipment must not be used by children or persons with
reduced physical, sensory or mental abilities, or lacking in expe-
rience and expertise, unless supervised or instructed. Children
may not use the equipment, nor may they play with the unit or
in the immediate vicinity.
• Equipment can start automatically. Lockout-Tagout before ser-
vicing equipment.
• This equipment produces high temperatures during normal
operation. Use caution when contacting surfaces.
• Operation of this equipment requires detailed installation and
operation instructions provided in this manual for use with this
product. Read entire manual before starting installation and
operation. End User should receive and retain manual for future
use.
• Keep safety labels clean and in good condition.
High voltages capable of causing severe
injury or death by electrical shock are
present in this unit.
• To minimize risk of electrical shock, disconnect power before
working on or around the system.
• Serious or fatal electrical shock may result from failure to con-
nect the ground terminal to the motor, drive, metal plumbing, or
other metal near the motor or cable, using wire no smaller than
motor cable wires.
• Do not remove or install VFD cover for wiring, periodic inspec-
tions, or adjustments while power is applied, or the unit is in
operation.
• Capacitors inside the drive can still hold lethal voltage even after
power has been disconnected—ALLOW 5 MINUTES FOR DAN-
GEROUS INTERNAL VOLTAGE TO DISCHARGE BEFORE REMOV-
ING COVER.
• Operate VFD and control devices with dry hands.
• Do not use VFD if power or motor cable is damaged.
• Do not apply power to a damaged VFD or to VFD with missing
parts.
• Perform wiring after VFD has been mounted. Otherwise, electric
shock or bodily injury can occur.
• Do not handle the VFD with wet hands or when standing on a
wet or damp surface, or in water.
Risk of damage to drive or other equipment.
• Install and wire VFD according to the instructions in this manual.
• Take protective measures against ESD (Electrostatic Discharge)
before touching control boards during inspection, installation or
repair.
• This product is recommended for use with Franklin Electric 4-
inch and 6-inch submersible motors or above-ground centrifu-
gal motors. Use of this unit with any other Franklin Electric
motor or with motors from other manufacturers may result in
damage to both motor and electronics.
• In applications where water delivery is critical, a replacement
pressure sensor and/or back-up system should be readily avail-
able if the drive fails to operate as intended.
This manual suits for next models
15
Table of contents
Other Franklin Electric DC Drive manuals

Franklin Electric
Franklin Electric SubDrive Utility UT2W User manual

Franklin Electric
Franklin Electric Cerus X-Drive User manual

Franklin Electric
Franklin Electric SUBDRIVE UTILITY UT3P User manual

Franklin Electric
Franklin Electric SubDrive Connect Plus SDCP-SUB2043 User manual

Franklin Electric
Franklin Electric Cerus X-Drive User manual

Franklin Electric
Franklin Electric Fhoton 2 User manual

Franklin Electric
Franklin Electric MONODRIVE UTILITY UT3W User manual

Franklin Electric
Franklin Electric SUBDRIVE CONNECT PLUS User manual

Franklin Electric
Franklin Electric Cerus X-Drive User manual

Franklin Electric
Franklin Electric SUBDRIVE CONNECT PLUS User manual