Franklin Electric Cerus X-Drive User manual

SAFETY INFORMATION
1
Cerus X-Drive Firmware Version 1.2
QUICKSTART GUIDE
English
EN
This QuickStart Guide includes basic setup and operation information.
For detailed instructions and safety information, please refer to the
Cerus X-Drive Installation and Operation Manual
www.franklin-controls.com.
Safety Information
This equipment should be installed and serviced by technically quali-
fied personnel who are familiar with the correct selection and use of
appropriate tools, equipment, and procedures. Failure to comply with
national and local electrical and plumbing codes and within Franklin
Electric recommendations may result in electrical shock or fire hazard,
unsatisfactory performance, or equipment failure.
Read and follow instructions carefully to avoid injury and property
damage. Do not disassemble or repair unit unless described in this
manual.
Failure to follow installation or operation procedures and all applicable
codes may result in the following hazards:
High voltages capable of causing severe
injury or death by electrical shock are
present in this unit.
• To reduce risk of electrical shock, disconnect power before
working on or around the system. More than one discon-
nect switch may be required to de-energize the equipment
before servicing.
• Serious or fatal electrical shock may result from failure to
connect the ground terminal to the motor, drive, metal
plumbing, or other metal near the motor or cable, using
wire no smaller than motor cable wires.
• Do not remove or install VFD cover for wiring, periodic
inspections, or adjustments while power is applied, or the
unit is in operation.
• Capacitors inside the drive can still hold lethal voltage
even after power has been disconnected—ALLOW 10 MIN-
UTES FOR DANGEROUS INTERNAL VOLTAGE TO DIS-
CHARGE BEFORE REMOVING COVER.
• Operate VFD and control devices with dry hands.
• Do not use VFD if power or motor cable is damaged.
• Do not apply power to a damaged VFD or to VFD with
missing parts.
• Perform wiring after VFD has been mounted. Otherwise,
electric shock or bodily injury can occur.
Risk of bodily injury, electric shock,
or property damage.
• This equipment must not be used by children or persons
with reduced physical, sensory or mental abilities, or lack-
ing in experience and expertise, unless supervised or
instructed. Children may not use the equipment, nor may
they play with the unit or in the immediate vicinity.
• Equipment can start automatically. Lockout-Tagout before
servicing equipment.
• This equipment produces high temperatures during nor-
mal operation. Use caution when contacting surfaces.
• Do not allow lint, paper, wood chips, dust, metallic chips
or other foreign material into the drive.
• Some VFD parameters are set as default to automatically
start VFD in some applications. Disable these parameters
if automatic start is not safe for personnel or equipment.
Risk of damage to drive or other equipment.
• Take protective measures against ESD (Electrostatic Dis-
charge) before touching control boards during inspection,
installation or repair.
• Set correct motor data from the motor nameplate and
overload protection parameters for proper motor overload
protection.
• Use, if possible, an inverter rated or motor with insulation
Class F or higher. For submersible pump motors, use Class
B or higher. The VFD generates high frequency output
pulses with spikes, which can deteriorate motor winding
insulation and eventually damage the motor. The longer
distance to the motor the higher amplitude of these volt-
age spikes will be applied to motor winding. Any cables
with paralleled wires will increase the amplitude of these
spikes at motor terminals.
• The VFD can operate a motor at frequencies higher than
50HZ or 60Hz. Verify the maximum allowed speed with
motor and machinery manufacturers prior to increasing
output frequency because it can overheat the motor or
damage machinery.

PHYSICAL INSTALLATION
Environmental Requirements
2
Physical Installation
Environmental Requirements
The VFD must be installed and used in a controlled environment that meets the following requirements:
The drive electronics are air-cooled. Provide
enough clearance for an airflow around the VFD.
Mount VFD vertically (top up) for proper heat dis-
sipation.
Do not mount VFD in direct sunlight or near other
heat sources.
Do not block cooling vents or airflow with any
panel components or wires.
See minimum mounting clearance table below for
different VFD frame sizes.
* For frames sizes D, E, & F, install a metal separator between side-by-side drives. Barrier depth must match the VFD depth.
Risk of damage to VFD, or malfunction can occur due to improper handling,
installation, or environment.
• Do not mount VFD on equipment with excessive vibration.
• Install in a location where temperature is within the range of product rating.
• Install VFD on a non-combustible surface. The VFD generates heat during normal operation.
• The VFD should be mounted in a Pollution Degree 2 environment. If VFD will be installed in an environment
with a high probability of dust, metallic particles, mists, corrosive gas or other contaminants, the VFD must be
mounted inside the appropriate electrical enclosure with proper NEMA, UL or IP rating and adequate cooling.
• When two or more VFDs are installed in a ventilated enclosure, the cooling system should provide adequate
airflow for all the VFDs. Do not install VFD above another heat source (another VFD, inductive reactors, etc.).
Ambient Temperature 50 °C (122 °F) for UL Open Type/IP20 (top cover must be removed)
40 °C (104 °F) for NEMA 1 / UL Type 1 / IP20 enclosure
Location Pollution Degree 2 Environment
Altitude 1000 m (3281 ft) above sea level. De-rate current 1% per 100 m (328 ft) from 1000 to 2000 m (3281-
6562 ft). Consult Technical Support for installations above 2000 m.
Relative Humidity 95% Maximum relative humidity (non-condensing)
Vibration 1.0 mm, peak to peak value range from 2 Hz to 13.2 Hz
0.7G-1.0G range from 13.2 Hz to 55 Hz
1.0G range from 55 Hz to 512 Hz
Frame Size A B C D
A, B, & C 60 mm/2.4 in. 30 mm/1.2 in. 10 mm/0.4 in. 12 mm/0.5 in.
D, E, & F 100 mm/3.9 in. 50 mm/2.0 in. 10 mm/0.4 in. 25 mm/1.0 in.
G 200 mm/7.9 in. 100 mm/3.9 in. 10 mm/0.4 in. 25 mm/1.0 in.
H 350 mm/ 13.8 in. 150 mm/6.0 in. 10 mm/0.4 in. 50 mm/2.0 in.
A
A
BBCD

ELECTRICAL INSTALLATION
Mounting the Drive
3
Mounting the Drive
The mounting location should have nearby access to the electrical supply and to the motor wiring.
Use lag screws or bolts appropriate for supporting the weight of the drive.
1. Mount the drive using the mounting holes on the back side of the enclosure.
2. Screws at the top must attach to a solid structure such as a stud or brace.
3. All screw hole locations should be used to ensure the drive is securely mounted.
IMPORTANT: Do not drill holes in the drive.
Electrical Installation
Wiring Guidelines
Risk of bodily injury or damage to drive or other equipment.
• The drive should be mounted on a structure such as a wall or post capable of supporting the weight of the unit.
• Install VFD on a non-combustible surface.
• Ensure suitable mounting hardware is used when installing the drive.
• Do not install the drive on unreinforced drywall.
• Use suitable lifting equipment, in good condition, rated for at least 5 times the weight of the drive.
Contact with hazardous voltage could result in death or serious injury.
• Disconnect and lock out all power before installing or servicing equipment.
• Always check if DC bus charge LED is off and DC voltage on the terminals DC (+1) and DC (-) is less than 30 VDC
before working on VFD wiring. The DC bus capacitors may hold high-voltage charge for several minutes after
the VFD power is disconnected.
• Connect the motor, the drive, metal plumbing, and all other metal near the motor or cable to the power supply
ground terminal using wire no smaller than motor cable wires.
• All wiring must comply with the National Electrical Code and local codes.
Risk of damage to VFD, or malfunction can occur.
Follow all wire routing and grounding instructions carefully. Inductive currents caused by parallel wiring, or close
proximity between high voltage and control wiring can cause unexpected behaviors.
• Do not run input power and motor wires in the same conduit.
• Do not run motor wires from multiple VFDs in common conduit.
• Do not run control wiring parallel with high voltage wiring.
• Do not run VFD wiring parallel with building or facility wiring.
• Do not install power factor correction capacitors, surge suppressors, or RFI filters to the VFD output.
• The use of any disconnecting device (contactor, disconnect etc.) in motor circuit during VFD run can cause
damage to VFD power components. Stop VFD before opening the motor circuit with disconnect or contactor.
• Do not use aluminum wires for VFD connections.
• Do not leave wire fragments, metal shavings or other metal objects inside the VFD.
• Improper splicing or damage to motor cable insulation may expose the conductor(s) to moisture and can pro-
duce tripping on faults or VFD damage.
• For retrofit application, check the integrity of power and motor leads. This requires measuring the insulation
resistance with a suitable megohm-meter.

ELECTRICAL INSTALLATION
Branch Circuit Protection
4
1. Mount the drive as close as possible to the service entrance panel. Connect directly to the service entrance, not to a sub-panel.
2. Use a dedicated branch circuit for the drive. Verify that the circuit is equipped with a properly-sized circuit breaker or fuse.
3. Separate input power and motor wiring by at least 8 in. (20.3 cm).
4. Cross over other branch circuits and facility wiring at a 90 angle. If necessary to run wires in parallel, separate by at least 8 in.
(20.3 cm).
5. All control wiring—sensors, switches, transducers, etc.—should be in a separate conduit routed individually, not parallel, from
high voltage wiring. In addition, any shielded cables should be properly grounded.
6. Treat Open-Delta power configuration (two-transformer utility bank) as single-phase power and size wiring accordingly.
7. Install a line reactor for VFDs in pump systems with dedicated service transformer to protect VFD from transient power surges
and provide some degree of harmonics distortion mitigation.
Branch Circuit Protection
Integral solid-state short circuit protection does not provide branch circuit protection. Branch Circuit Protection must be provided in
accordance with the National Electrical Code (NEC) and applicable local codes; or equivalent as determined by Authorities Having
Jurisdiction (AHJ). The Drive shall be protected by Listed Class J fuses, Listed inverse-time circuit breakers, or Franklin Electric Man-
ual Motor Starters.
Short-circuit current rating (SCCR): The drive is suitable for use on a circuit capable of delivering not more than 100,000 symmetri-
cal amperes (rms) when protected by suitable Class J fuses. Rated fuse current shall be maximum 3 times the motor output full-
load current (FLA) rating. Rated circuit breaker current shall be maximum 2.5 times the motor output FLA rating when using single
phase or polyphase AC motors. For all other motors, refer to NEC Sec 430 and the Franklin Electric Aim Manual. When protected by
a circuit breaker and placed in a panel, drive SCCR is as follows:
Wire Sizing
Size power wire to maintain a voltage drop less than 2% at VFD or motor terminals. For submersible pumping applications, refer to
the Franklin Electric AIM Manual for wire gauge and distance information.
Frame A: Use only copper conductors rated for at least 75 C and 600 V. Use cable with a 90 C rating if ambient environment is
greater than 50 C.
Frame B and above: Use only copper conductors rated for at least 75 C and 600 V. Use cable with a 90 C rating if ambient envi-
ronment is greater than 40C (30 C for models CX-061A-2V, CX-105A-2V, CX-370A-4V, or CX-930A-4V).
460 and 575 V applications: Install a load (output) reactor to protect motor windings if distance from VFD to a motor is in the
range 45-100 ft (13.7-30.5 m). Install output dV/dt filter for a range 100-1000 ft (13.7-304.8 m) or a sine wave filter.
Power Wires Motor Wires
ضضض ض ض
VFD Output Rating Test Current
Up to 50 HP (0 to 37.3 kW) 5,000 Amperes (rms)
51 to 200 HP (39 to 149 kW) 10,000 Amperes (rms)
201 to 400 HP (150 to 298 kW) 18,000 Amperes (rms)
401 to 600 HP (299 to 447 kW) 30,000 Amperes (rms)
601 to 900 HP (448 to 671 kW) 42,000 Amperes (rms)

ELECTRICAL INSTALLATION
Power Wiring Connections
5
Suggested Maximum Motor Cable Lengths for Non-Submersible Applications
• Without output reactor: 13.7 m (45 ft)
• With output reactor: 30.5 m (100 ft)
• With dV/dt filter: 305 m (1000 ft)
Power Wiring Connections
Power Wiring Diagram
1. Main Connection, Power
2. VFD
3. Motor
4. Ground Terminals
5. Power input terminals
6. Output to Motor terminals
7. Jumper (optional DC reactor, dynamic
brake or DC choke unit)
8. Optional brake resistor terminals
Use ring type terminals for the VFD power wiring.
Power line ground and motor ground wires should be connected to designated ground terminals.
Three-phase power, including Open-Delta must be connected to the R(L1), S(L2), and T(L3) terminals. Proper phase sequencing is
not required.
• For single-phase power, connect L1 to R and L2 to S terminals.
• G and H frame VFDs have double-pole power terminals or lugs to accommodate two smaller gauge wires.
Connect three-phase motor wires to the U(T1), V(T2), and W(T3) terminals. When in forward rotation, the motor shaft should turn
clockwise when viewed from the motor to the load. If rotation is not correct, reverse any two motor leads.
Risk of damage to drive, or malfunction can occur.
• Do not connect input power to VFD output terminals U, V, and W otherwise VFD can be damaged.
• Ensure that the system is properly grounded all the way to the service entrance panel. Improper
grounding may result in loss of voltage surge protection and interference filtering.
• Do not connect any wires except dynamic braking resistor to (B1) and (B2) terminals.
• Do not remove the jumper between terminals (+2) and (+1) except for dynamic braking unit or DC
link choke, otherwise the VFD can be damaged.
• When using a general GFCI (Ground Fault Circuit Interrupter), select a current sensor with sensitivity
of 200mA or above and not less than 0.1-second operation time to avoid nuisance tripping.
+2
(DC+)
R
–
(DC–) +1 B1 B2
L1
L2
L3
S
T
U
V
W
T1
T2
T3
2
1
3
6
5
78
44
GND
Frame Maximum Terminal Wire Size Torque
Frame A 8 AWG 17.4 in-lbs (1.96 Nm)
Frame B 4 AWG 30.4 in-lbs (3.43 Nm)
Frame C 1/0 AWG 69.4 in-lbs (7.84 Nm)
Frame D0 2/0 AWG 69.4 in-lbs (7.84 Nm)
Frame D 300 MCM or 4/0 AWG 156 in-lbs (18 Nm)
Frame E 4/0 AWG*2 174 in-lbs (20 Nm)
Frame F 300 MCM*2 or 4/0 AWG*2 156 in-lbs (18 Nm)
Frame G: Terminals R, S, & T 250 MCM*4 156 in-lbs (18 Nm)
Frame G: Terminals U, V, & T 500 MCM*2 354 in-lbs (40 Nm)
Frame H 350 MCM*4 156 in-lbs (18 Nm)

ELECTRICAL INSTALLATION
Control Circuit Connections
6
Control Circuit Connections
Terminal Identification
The control board is divided into 5 groups of terminals and connectors, plus a group of micro switches that control individual termi-
nal configurations.
• Always insulate bare control or shield wires with shrink tubing or electrical tape to prevent short circuit.
• The ideal length of stripped wire for control terminals is 5 mm.
1. Analog Inputs/Outputs – These connections are used for transducers, sensors, and control systems such as a BAS, BMS, or
PLC. Use shielded cable with shield connected to the ground terminal. Terminals accept 26~16 AWG (0.13~1.3mm2) wires,
and should be tightened to a torque of 1.73 lb-in (0.19 Nm).
•ACI is a 0-10 VDC or 4-20 mA input, adjustable by micro switch. Set ACI Input Sel [IO–00] to match the switch setting. Default
= 4-20 mA.
•AVI1 is a 0-10 VDC or 4-20 mA input, adjustable by micro switch. Set AVI1 Input Sel [IO–05] to match the switch setting.
Default = 0-10 V.
•AVI2 is a 0-10VDC input.
When an input source has been connected, select the appropriate terminal in either Auto Speed Ref [SET–07], Hand Speed Ref
[SET–09], or PID F/B Source [SET–18].
•AFM1 & AFM2 are programmable, multi-function analog outputs. Refer to AFMI Out Select [IO–59] and AFM2 Out Select [IO–61] for
options. Each output can be set by micro switch to 0-10V (min load 5k Ω at 2 mA) or 0/4-20 mA (max load 500 Ω).
•+10V terminal (with common ACM) provides a +10 VDC 50 mA power supply for input devices.
•ACM terminals are the common for analog inputs, outputs, and +10 VDC power supply. All ACM terminals are connected
internally.
IMPORTANT: DCM and ACM terminals are isolated from each other and from the ground. Do not connect these terminals
to earth ground, which can cause electrical noise in control circuits and unstable VFD operation.
0-10V
0 - 10 V
Open
120
AFM1
AFM2 AVI 1 ACI
0/4-20mA
0/4-20mA 4-20mA
4-20mA
485
RC3 RA3 RC2 RA2 RC1 RB1 RA1
AFM1 +10V AVI1 ACI STO1 STO2 +24
AFM2 ACM AVI2 ACM SCM1 SCM2 DCM
+24V COM FWD MI1 MI3 MI5 MI7
0-10V 0-10V
SGND
DCM REV MI2 MI4 MI6 MI8 SG+ SG–
12
3
5
4
81 81

ELECTRICAL INSTALLATION
Example Configurations
7
2. Digital Inputs & RS-485 Communication – These connections provide input for a wide selection of switches or programmable
controls. Use shielded cable or twisted wires for 24 VDC digital control circuits wiring and separate these wires from the main
power and motor wiring and other high voltage circuits. Terminals accept wire sizes from 26~16 AWG (0.2~1.5mm2), and should
be tightened to a torque of 6.9 lb-in (0.78 Nm).
• Digital inputs are configured for NPN (Sink) mode by default, with a jumper across +24 and COM terminals. Refer to the
owner’s manual for more details.
• All digital inputs can be re-programmed from Normally Open to Normally Closed.
• Digital inputs are activated by voltage 11 VDC or greater. Maximum input voltage rating is 27 VDC at 3.5 mA.
•MI1-MI8 are programmable, multi-function digital inputs that can be used for a variety of switching features with com-
mon terminal DCM. Refer to MI1 Define [IO–21] through MI8 Define [IO–28] for options.
NOTE: MI1 FWD and REV behave as “No Function”
•FWD & REV are dedicated Forward and Reverse run commands. If any digital input is programmed for FWD or REV, corre-
sponding dedicated FWD or REV input will be disabled automatically.
•SG+, SG–, & SGND are RS485 communication terminals for PLC, Modbus, or BACnet. Use PLC Com Type [PLC–23] to set the
com type. Termination resistance is controlled by micro switch. Set the 485 switch to the Down position to connect 120 Ω
termination resistance for long distance or for an electrically noisy environment.
•+24 terminal provides 24 VDC (with DCM common) 50 mA power for digital control circuits and 150 mA for external trans-
ducers.
•COM terminal is a digital inputs common. By default, it is connected by jumper to +24 to configure NPN (Sink) mode.
•DCM is the internal 24 VDC power supply common.
• Earth ground. Use this terminal to connect shield wires.
IMPORTANT: DCM and ACM terminals are isolated from each other and from the ground. Do not connect these terminals
to earth ground, which can cause electrical noise in control circuits and unstable VFD operation.
3. Relay Outputs – These are configurable, multi-function, dry contact relays. Refer to Relay RA1 [IO–47] through Relay RA3 [IO–49] for
options. Terminals accept wire sizes from 26~16 AWG (0.2~1.5mm2), and should be tightened to a torque of 4.3 lb-in (0.49 Nm).
• Relays ratings are 1.25A at 250 VAC, or 3A at 30 VDC.
• RA1-RB1-RC1 is a single-pole, double throw relay. RA1-RC1 is N.O. (normally open), and RB1-RC1 is N.C. (normally closed).
• RA2-RC2 and RA3-RC3 are independent single pole, single throw, normally open relays.
4. Safety Torque Off (STO) Inputs – These connections provide emergency stop control from an external system. By default, the
inputs are closed through jumper wires, allowing the drive to run.
5. RJ-45 Sockets – These connections are communication terminals for PLC, Modbus, or BACnet. Use PLC Com Type [PLC–23] to set
the Com Type. Then set both Speed Reference and Run Command to RS485. Both RJ-45 sockets and terminals (SG+, SG-, &
SGND) are connected internally.
Example Configurations
4-20mA Speed Control Signal from an External BMS or PLC:
• Connect the BMS or PLC output signal to the ACI or AVI1 terminal. The ACI micro
switch should be in the UP position. If using the AVI1 terminal, the AVI1 micro
switch should be DOWN.
• Connect the BMS Com wire to the ACM terminal (signal ground).
• Any shield wire should be connected to Earth ground.
•ACI Input Sel [IO–00] or AVI1 Input Sel [IO–05] should be set to the correct signal type.
•Auto Speed Ref [SET–07] should be set to the chosen input.
ACM
VFD
ACI
BMS
Out
4-20 mA
Com
Shield
ACI

ELECTRICAL INSTALLATION
Example Configurations
8
0-10V Speed Control Signal from an External BMS or PLC:
• Connect the BMS or PLC output signal to the AVI1, AVI2, or ACI terminal. The
AVI1 micro switch should be in the UP position. If using the ACI terminal, the ACI
micro switch should be DOWN.
• Connect the BMS Com wire to the ACM terminal (signal ground).
• Any shield wire should be connected to Earth ground.
•ACI Input Sel [IO–00] or AVI1 Input Sel [IO–05] should be set to 0-10V.
•Auto Speed Ref [SET–07] should be set to the chosen input.
4-20mA Transducer with VFD 10 VDC Power:
• Connect the transducer positive (Power) wire to the VFD +10V terminal.
• Connect the transducer output (Out) wire to the ACI or AVI1 terminal. The ACI
micro switch should be in the UP position. If using the AVI1 terminal, the AVI1
micro switch should be DOWN.
• Any shield wire should be connected to Earth ground.
•ACI Input Sel [IO–00] or AVI1 Input Sel [IO–05] should be set to the correct signal type.
•Auto Speed Ref [SET–07] should be set to PID Output, PID F/B Source
[SET–18] should be set to the chosen input, and PID F/B Unit [SET–19] should be set to
the appropriate scale (psi, temp, flow, etc.).
4-20mA Transducer with VFD 24 VDC Power:
• Connect the transducer positive (Power) wire to the VFD +24V terminal.
• Connect the transducer output (Out) wire to the ACI or AVI1 terminal. The ACI
micro switch should be in the UP position. If using the AVI1 terminal, the AVI1
micro switch should be DOWN.
• Use a jumper wire to connect the ACM and DCM terminals.
• Any shield wire should be connected to Earth ground.
•ACI Input Sel [IO–00] or AVI1 Input Sel [IO–05] should be set to the correct signal type.
•Auto Speed Ref [SET–07] should be set to PID Output, PID F/B Source [SET–18] should be set to the chosen input, and PID F/B Unit [SET–19]
should be set to the appropriate scale (psi, temp, flow, etc.).
4-20mA Transducer with External 24 VDC Power:
• Connect the transducer positive (Power) wire to the external source positive
[+24V]. Connect the external source negative to the VFD ACM terminal.
• Connect the transducer output (Out) wire to the ACI or AVI1 terminal. The ACI
micro switch should be in the UP position. If using the AVI1 terminal, the AVI1
micro switch should be DOWN.
• Any shield wire should be connected to Earth ground.
•ACI Input Sel [IO–00] or AVI1 Input Sel [IO–05] should be set to the correct signal type.
•Auto Speed Ref [SET–07] should be set to PID Output, PID F/B Source [SET–18] should be set to the chosen input, and PID F/B Unit [SET–19]
should be set to the appropriate scale (psi, temp, flow, etc.).
0-10VDC Transducer with VFD 10 VDC Power:
• Connect the transducer positive (Power) wire to the VFD +10V terminal.
• Connect the transducer output (Out) wire to the AVI1, AVI2, or ACI terminal. The
AVI1 micro switch should be in the UP position. If using the ACI terminal, the ACI
micro switch should be DOWN.
• Connect the transducer Com wire to the ACM terminal (signal ground).
• Any shield wire should be connected to Earth ground.
•ACI Input Sel [IO–00] or AVI1 Input Sel [IO–05] should be set to 0-10V.
•Auto Speed Ref [SET–07] should be set to PID Output, PID F/B Source [SET–18] should be set to the chosen input, and PID F/B Unit [SET–19]
should be set to the appropriate scale (psi, temp, flow, etc.).
VFD
AVI1
AVI1
ACM
Shield
Com
0-10V
Out
BMS
Power (+)
Transducer VFD
ACI
+10V
ACI
Shield
Out
ACI
DCM
ACM
ACI
+24V
Shield
Out
Power (+)
VFD
Transducer
Transducer
Power (+)
Out
Power Supply
+ -
VFD
ACM
Shield
ACI
ACI
Transducer
Power (+)
Out
Com
Shield
VFD
AVI1
AVI1
ACM
+10V

ELECTRICAL INSTALLATION
Example Configurations
9
0-10VDC Transducer with VFD 24 VDC Power:
• Connect the transducer positive (Power) wire to the VFD +24V terminal.
• Connect the transducer output (Out) wire to the AVI1, AVI2, or ACI terminal. The
AVI1 micro switch should be in the UP position. If using the ACI terminal, the ACI
micro switch should be DOWN.
• Connect the transducer Com wire to the ACM terminal (signal ground).
• Use a jumper wire to connect the ACM and DCM terminals.
• Any shield wire should be connected to Earth ground.
•ACI Input Sel [IO–00] or AVI1 Input Sel [IO–05] should be set to 0-10V.
•Auto Speed Ref [SET–07] should be set to PID Output, PID F/B Source [SET–18] should be set to the chosen input, and PID F/B Unit [SET–19]
should be set to the appropriate scale (psi, temp, flow, etc.).
0-10VDC Transducer with External 24 VDC Power:
• Connect the transducer positive (Power) wire to the external source positive
[+24V].
• Connect the transducer Com wire to the external source negative.
• Connect the transducer output (Out) wire to the AVI1, AVI2, or ACI terminal. The
AVI1 micro switch should be in the UP position. If using the ACI terminal, the ACI
micro switch should be DOWN.
• Any shield wire should be connected to Earth ground.
•ACI Input Sel [IO–00] or AVI1 Input Sel [IO–05] should be set to 0-10V.
•Auto Speed Ref [SET–07] should be set to PID Output, PID F/B Source [SET–18] should be set to the chosen input, and PID F/B Unit [SET–19]
should be set to the appropriate scale (psi, temp, flow, etc.).
Temperature Protection or PID Control with PT-100 or PTC Sensor:
• Connect the sensor Positive wire to the AFM2 terminal. Place the AFM2 micro
switch in the DOWN position.
• Connect the sensor Negative wire to the ACM terminal.
• Use a jumper wire to connect the AFM2 and AVI1 terminals. The AVI1 micro
switch should be in the UP position.
• Any shield wire should be connected to Earth ground.
• For PT100, AVI1 Input Sel [IO-05] should be set to PT100 & AFM2.
• If using PT100 for PID Feedback, Spare Sensor, or Aux Sensor, set the max value to 200 °C.
Speed Control using 0-10 VDC Potentiometer:
• Connect the potentiometer Positive wire to the VFD +10V terminal.
• Connect the potentiometer Output wire to the AVI1, AVI2, or ACI terminal. The
AVI1 micro switch should be in the UP position. If using the ACI terminal, the ACI
micro switch should be DOWN.
• Connect the potentiometer Com wire to the ACM terminal (signal ground).
• Any shield wire should be connected to Earth ground.
•ACI Input Sel [IO–00] or AVI1 Input Sel [IO–05] should be set to 0-10V.
•Auto Speed Ref [SET–07] or Hand Speed Ref [SET–09] should be set to the chosen input.
Relay switching to control an external starter, contactor, or other system:
• Connect the incoming power to the RC terminal.
• Wire the corresponding RA terminal to the external application.
• Set the relay control, Relay RA1, -2, -3 [IO-47, -48, 49].
NOTE: Illustration example uses 120 V, relay 1, and a run light application.
Transducer VFD
+24V
AVI1
ACM
DCM
Shield
Power (+)
Out
Com
AVI1
Transducer
Power (+)
Com
Out
Power Supply
+ -
VFD
AVI1
ACM
Shield
AVI1
+
–
Sensor
Shield
VFD
AFM2
AVI1
ACM
AVI1
AFM2
Potentiometer
VFD
+10V
AVI1
ACM
AVI1
Shield
Run Light
120 V
VFD
RA1
RC1

DRIVE CONFIGURATION
Using the Keypad
10
External HOA switch:
• Connect two MI terminals to DCM and the HOA switch.
• Wire a normally open run contact to DCM and FWD terminals.
•MI_ Define [IO-21, -22,...-28] of the two terminals should be set to 1) HOA-HAND, and
2) HOA-AUTO.
• Put HOA Mode Source [SET_60] to Digital Input.
NOTE: Factory-installed drives use MI7 for Hand and MI8 for Auto.
Drive Configuration
Using the Keypad
VFD
MI7
MI8
DCM
FWD
HOA
The ESC key returns to the Home
Screen from any menu.
The RUN LED indicates that power
is being sent to the motor.
Up and Down Arrow keys allow
navigation within a parameter
group.
The MENU key provides access for
editing all parameter groups.
Pressing BACK from this screen
displays a basic drive menu.
The ENTER key places the VFD in
programming mode and confirms
changes to parameters.
The AUTO key places the VFD in
Auto mode when keypad control
is enabled.
The STOP/RESET key stops the
motor when keypad control is
enabled, or if enabled in remote
mode. The LED indicates that the
VFD is stopped. RESET can be
used to clear some faults.
LCD Display Screen
Function Keys provide access to
(F1) Jog Function, (F2) View
Mode, and (F3) Fault history.
The HAND LED indicates when the
VFD is in Hand mode.
The Back key returns display to
the previous screen. From the first
MENU screen, this key displays a
basic drive menu.
Left and Right Arrow keys allow
navigation between parameter
groups, cursor movement when
setting a value, and for increment
of numeric values.
The HAND key places the VFD in
Hand mode when keypad control
is enabled.
The START key starts the motor
when keypad control is enabled.
The LED indicates that a Start
command is present.
The FWD/REV key selects motor direc-
tion when enabled. The LED lights either
green or red to indicate selection.

DRIVE CONFIGURATION
Home Screen Display Options
11
Home Screen Display Options
Enter Required Parameters Before Starting VFD
1. Application Sel [SET–00]: Use the keypad to select the type of application the drive will control. When a selec-
tion has been made, application related parameters will be automatically updated to proper defaults. Enter the
following parameters to ensure best performance for the specific installation.
NOTE: the BASIC application provides standard VFD control with start/stop command from digital inputs and
speed reference from a remote analog signal. For systems using a transducer or other control sensors, choose
the relevant application type to ensure that correct defaults are set.
NOTE: When using a FE MagForce or other permanent magnet motor application, refer to the owner’s manual.
2. Input Phase [SET–01]: Verify that the setting matches the type of power supply— 3-phase (default).
3. Motor HP [SET–02]: Enter the rated horsepower from the motor nameplate.
4. Motor FLA (SFA) [SET–03]: Enter the FLA (Full Load Amps) rating from the motor nameplate, or enter SFA (Ser-
vice Factor Amps) if using a submersible pump motor.
5. Motor RPM [SET–04]: Enter the rated motor RPM from the motor nameplate.
6. Motor Voltage [SET–05]: Enter the rated voltage from the motor nameplate.
7. Motor Freq Sel [SET-06]: Select the standard motor frequency (either 50 or 60 Hz).
1. Operating Status
Run/Stop
Limit by PID 2
Ctrl by PID 2
Stopped by AI
Backspin Timer
Lubrication
Limit by Level
Limit by Temp
Stall
2. Command Source
K = Keypad
T = Terminal control
R = RS485
O = Option board
3. Frequency Source
K = Keypad/PID
V1 = from AV1
V2 = from AV2
C = from ACI
R = RS485
O = Option board
1-15 = Step speed
J = Jog frequency
b
Run
H
A
58.7 PSI
60.00 Hz
K/K
2.22 Amp
JOG View . Faults
1 2 3
4
5
6
BT
4. Display Line 1 [SET-57] Use Arrow and Enter keys to step through selections and to change setpoints.
H = Output speed when running (Hz).
P = PID Set-point [SET–21] in application based units (PSI, inWC, etc.). This is adjustable using the keypad.
F = Keypad Speed Reference (Hz) when Auto Speed Ref [SET–07] or Hand Speed Ref [SET–09] is set to Keypad. This is adjustable using the
keypad.
5. Display Line 2 Displays motor current.
6. Display Line 3 [SET-58] Use Arrow keys to step through choices. This display corresponds to choices in [SET–57].

DRIVE CONFIGURATION
Verify Default Settings
12
Verify Default Settings
After the initial parameters have been entered, the following default settings should be checked and adjusted to ensure expected
operation. Refer to the “Default Settings Tables” on page 16 for a list of automatically populated settings per application.
1. VFD Max Freq [VFD–00]: The highest frequency (speed) allowable. If running a FE MagForce pump, this should be set to the
calculated electrical frequency corresponding to the target pump RPM. Refer to the Owner’s Manual to set up FE Magforce
motors if needed.
2. VFD Base Freq [VFD–02]: This should be set to the motor nameplate frequency rating.
3. Auto Speed Ref [SET–07]: This is the source of frequency (speed) setpoint the drive will use when in Auto mode.
• When using one of the analog inputs with an automated BAS, BMS, or PLC system, be sure to configure the terminal for
the correct signal type. Refer to “Terminal Identification” on page 43.
• When using feedback from a sensor or transducer, select PID Output. When PID mode is selected, additional parameters
must be verified for setpoints, inputs, and limits.
• When set to Keypad, the drive will run at the Keypad Speed Reference (F on display).
4. Auto Run Cmd [SET–08]: The source of RUN command when VFD is in Auto Mode—Keypad or external.
5. Hand Speed Ref [SET–09]: The source of frequency (speed) setpoint the drive will use when in Hand mode. PID is disabled in
Hand mode. Be sure to configure any selected input terminals for the correct signal type.
• When set to Keypad, the drive will run at the Keypad Speed Reference (F on display).
6. Hand Run Cmd [SET–10]: The source of RUN command when VFD is in Hand Mode—Keypad or external.
7. Accel Time [SET–11]: The time in seconds for drive to ramp up from stop to maximum frequency. Recommended defaults are 2
seconds for submersible pump motors and 20 seconds for most other applications. Additional acceleration curves can be
added for more precise control through selected frequency ranges. Refer to “Acceleration/Deceleration Control” on page 82.
8. Decel Time [SET–12]: The time in seconds to slow down from maximum frequency to stop. Recommended defaults are 2 sec-
onds for submersibles and 30 seconds for surface/booster pumps. This setting is only effective when Stop Mode [SET–16] is set to
Decel to Stop. Additional deceleration curves can be added for more precise control through selected frequency ranges. Refer to
“Acceleration/Deceleration Control” on page 82.
9. Low Freq Limit [SET–13]: The lowest frequency (speed in Hz) allowed by the VFD in any mode.
10. High Freq Limit [SET–14]: The highest frequency (speed in Hz) allowed by the VFD in any mode.
11. PID Mode [SET–17]: Enables or disables PID control, either direct or inverse.
12. PID F/B Source [SET–18]: The input terminal for PID Feedback source. Be sure to configure the terminal for the correct signal
type.
13. PID F/B Unit [SET–19]: Selects a measurement unit for PID feedback.
14. PID F/B Max [SET–20]: The maximum reading of the feedback source. This is used to scale the analog signal to transducer. For
example: if using a 0–200 psi transducer, the value should be 200.
15. PID Set-point [SET–21]: The desired value for the drive to maintain in PID mode while running in Auto. This parameter can
also be changed through keypad on Line-1 of the display (value P).
16. PID Low Hz Limit [SET–22]: Minimum PID frequency output will be limited to this value.
17. PID High Hz Limit [SET–23]: Maximum PID frequency output will be limited to this value.
18. Language: Select a desired language for the display. Press the Menu button and then press the Back button. Use the Down key to
scroll to 5_Set Language.
19. Clock: Current time and date. This setting is used to record real-time data for faults, parameter changes, etc. To adjust, press
the Menu button and then press the Back button. Use the Down key to scroll to 6_Set Time.
Enter or Verify Optional Settings
There are many optional features available for customizing system operation. Some examples are included in “Example Configura-
tions” on page 7. For more information, refer to the Cerus X-Drive Installation and Operation Manual. Features include:
• Automation features
• Protection features
• Maintenance features
• Communications features
• Multi-Drive/Motor applications

OPERATION
Basic Operation
13
Operation
Basic Operation
The drive can be operated in either HAND or AUTO mode as follows:
•HOA Mode Source [SET–60]: This setting selects whether Hand/Auto control will come from the Keypad, a Digital Input, or
Communications.
•HAND mode runs the motor based on Hand Speed Ref [SET–09] (frequency source) and Hand Run Cmd [SET–10] (command source).
Defaults for both settings are Keypad, which runs the motor at a fixed speed (Keypad Setpoint) set on the Home Screen. Both set-
tings can be reprogrammed for external control. PID control is disabled in Hand mode.
•AUTO mode runs the motor based on AUTO Speed Ref [SET–07] (frequency source) and AUTO Run Cmd [SET–08] (command source). The
speed reference default is set per application. The run command default is Keypad. Both settings can be reprogrammed as
required.
Standard Operation with an Automated Control System
In many VFD applications, including ventilation, water supply, or irrigation, motor speed is often determined by an automated sys-
tem such as a BAS, BMS, or PLC. These systems provide control information to the VFD either through a communications protocol
such as Modbus or BACnet, or through direct electrical connection to one of the analog input terminals.
When the drive is in AUTO mode, it runs the motor at a variable frequency based on information from the automation system
through the input selected in Auto Speed Ref [SET–07].
Standard Operation with PID Feedback Control
A PID controlled application, such as a fan system or a constant pressure pump system, uses feedback from a transducer to measure
system performance against a user defined Setpoint (target) to control motor speed. The VFD can use several types of measure-
ment, including pressure, flow, level, temperature, etc.
For example:
• In a pumping application, the default measurement unit is PSI. As user demand (flow) causes pressure changes, the drive varies
the output frequency (motor speed) to maintain pressure at the target setpoint. When the drive determines a no-demand con-
dition, it enters Sleep mode and stops the motor.
• In a fan application, the default measurement unit is inWC (air pressure).
When the drive is in AUTO mode, it runs the motor at a variable frequency based on a comparison between the PID Setpoint [SET–21]
and feedback from the PID transducer, up to the PID Hi Hz Limit [SET–23]. PID operation is disabled in HAND mode.
When basic setup is complete, including motor specifications, verify or set the following parameters for PID operation:
Auto Speed Ref [SET–07]: This should be set to PID Output.
Auto Run Command [SET–08]: Select source of Run Command, either Keypad or external. If using a Digital Input (M1-8) with a
switch, set the terminal to FWD (or REV) [IO–21 ~ 28].
PID Mode [SET–17]: Set to PID Direct for most PID operations (exceptions are noted in the tables).
Feedback Source [SET–18]: Set to the terminal used for transducer connection. Make sure impedance is set correctly.
PID Feedback Units [SET–19]: Set to the appropriate measurement unit for the transducer type.
PID Feedback Max [SET–20]: Set to the maximum rating of the transducer.
PID Setpoint [SET–21]: Set to the desired measurement target.
PID P-Gain [SET–24]: Proportional Gain controls motor speed adjustments based on the proportional difference between the PID
setpoint and PID feedback. Higher settings result in a faster response. However, if the value is too high, it may cause system oscilla-
tion and instability. Used along with PID I-TIme [SET-25] to smooth and balance system response.
PID I Time [SET–25]: Integral Time determines PID response time. Lower values increase system response to the feedback signal,
which reduces overshoot, but may cause system oscillation if set too low. Greater values provide slower response, which may cause
overshoot of the setpoint and oscillation of output frequency.
Sleep Mode [SET–26]: This should be enabled for most pump applications, and Disabled for most HVAC applications.

OPERATION
Sleep Mode with Pressure Boost (Pump Applications)
14
Sleep Mode with Pressure Boost (Pump Applications)
The Sleep feature monitors pressure and frequency to detect a no-demand condition, at which point it stops the motor. The Sleep
Feature also has the option to boost system pressure by a set amount before stopping.
The Sleep feature works only in Auto mode using PID Direct (Sleep is disabled when PID mode is set to Inverse). PID2 operation
does not have Sleep function.
The following parameters control Sleep functions:
Sleep Mode [SET–26]: This setting disables or enables sleep mode or the sleep plus boost option. The default value for submers-
ibles and surface/boost pump applications is Sleep Only. If a pressure boost is desired while the system is at rest, select Sleep + Boost
and set a Sleep Boost Value [SET–29].
Sleep Check Time [SET–27]: Time delay (sleep check cycle time) before each Sleep Check procedure. Default = 10 sec.
Sleep Delay [SET–28]: Delay before VFD triggers Sleep Mode when all other conditions are met. Default = 6 sec.
Sleep Boost Value [SET–29]: Value added to original setpoint to provide pressure boost—0.0 to 10.0% of Feedback Max Value
[SET–20]. Default = 3%.
Sleep-Boost Timer [SET–30]: Timer that limits sleep boost duration if Sleep Boost setpoint is not reached—5 to 120 seconds.
Default = 10 sec.
Wakeup Level [SET–31]: Sets a wakeup level for VFD to quit Sleep mode and start running—0.0 to [SET-21]. Default = 55 PSI.
Sleep Bump Timer [SET–32]: Sets a duration time for pressure bump to increase system pressure as part of the no-demand calcu-
lation. Default = 5 sec.
All default settings related to Sleep mode have been calculated for best system performance for most applications. However, some
well conditions may require a slight adjustment.
During system setup it is recommended to test the Sleep feature by closing a main valve to simulate a no-demand condition. The
system should be running at normal demand, maintaining pressure setpoint, then flow should be decreased slowly until stopped.
• If the system does not enter Sleep mode, it may be necessary to increase the PID Lo Hz Limit [SET–22] to ensure that system pres-
sure reaches PID Setpoint [SET–21] (plus boost, if enabled).
• If, during normal operation, the system enters Sleep mode, but cycles on and off rapidly as it nears the Setpoint, it may be nec-
essary to slightly lower the PID Lo Hz Limit [SET–22] to prevent Sleep mode problems.
Damper Control (HVAC Applications)
The VFD can provide a relay output to open a damper actuator before starting a fan motor. When enabled, the damper relay output
is activated when the system receives a RUN command and the motor will start based on the following configurations:
•With Damper Limit Switch: If any Digital Input [IO–21 through 28] is set to Damper Limit Sw and the VFD receives a RUN command,
the damper relay is activated and when the damper limit switch is closed (damper is fully open and DI is activated), the VFD
will start the motor.
If the limit switch is not closed within the Damper Time Delay [IO–37], the VFD will trip on Damper Fault. If at any point during run
mode damper limit switch is open for more than 2 seconds, the VFD will trip on Damper Fault. VFD will try to restart based on
retry number setting [PROT–10].
•Without Damper Limit Switch. If no Digital Input is configured for a damper limit switch and the VFD receives a RUN command,
the damper relay is activated and when Damper Time Delay [IO–37] is complete, the VFD will start the motor. There is no damper
fault detection because there is no damper limit switch feedback.
NOTE: If any other delay timer is set and the VFD receives a RUN command, the damper relay will start after the first timer expires.
During run mode the damper relay stays activated. When a STOP command is received, the damper relay will be deactivated only in
VFD stop state. If stop mode is set to deceleration, the relay will be deactivated after VFD reaches zero speed (0.00Hz).
Set the following parameters to use the Damper Control function:
Damper Mode [IO–36]: This setting enables or disables damper mode.
Damper T-Delay [IO–37]: This setting provides a run time delay without a damper limit switch; or, provides a Damper Fault delay
for systems that include a damper limit switch. The delay time should be greater than damper opening time.

OPERATION
Fireman’s Override
15
Damper Output Terminal [IO–47 through 49]: Connect the damper actuator to one of the Relay Outputs (RA1–3), and set the cor-
responding parameter to 38_Damper Output.
Damper Limit SW Terminal [IO–21 through 28]: If the system includes a damper limit switch, connect the switch to one of the Dig-
ital Inputs (MI1–8) and set the corresponding parameter to 34_Damper Limit SW.
Auto Restarts [PROT-10]: The number of times the VFD will try to restart after a fault.
Auto Retry Delay [PROT-11]: The time delay before the VFD attempts to restart after a fault.
Fireman’s Override
Fireman’s Override (FO) provides the ability to force the drive to run exhaust fan to purge smoke from fire in the building by activat-
ing FO digital input. This mode is available for Basic and Exhaust fan applications.
In FO mode, if Damper Mode is enabled [IO–36], the damper relay output will be activated, but damper time delay [IO–37] will reduce
by half before VFD starts. The VFD will not monitor a Damper Switch, if present, and no damper faults will be available. Set the fol-
lowing parameters to use the FO function:
FO Input Terminal [IO–21 through 28]: Connect the FO switch to one of the Digital Inputs (MI1–8) and set the corresponding
parameter to either 32 FO with RUN Cmd or 33_FO w/o RUN Cmd.
FO Enable [IO–29]: Enables FO in either Forward or Reverse.
FO Frequency [IO–30]: Setpoint for non-PID operation during FO.
FO Fault Retry [IO–31]: Number of fault resets allowed during FO.
FO Retry Delay [IO–32]: Delay until restart during FO.
FO Mode & Reset [IO–33]: Sets control method and reset method during FO (PID Off Manual, PID Off Auto, PID On Manual, or PID
On Auto).
NOTE: FO Mode overrides all non-critical faults. When FO is activated, the Auto Retry Delay (PROT-11) is ignored and the current
fault, Prot-11 Delay timer, and Auto Restart counter will be reset.
FO PID S-Point [IO–34]: Setpoint for PID operation during FO.
FO Bypass [IO–72]: Enables Bypass for FO.
FO Bypass Delay [IO–73]: Time delay between FO becoming active and enabling relay output.

DEFAULT SETTINGS TABLES
Set Menu
16
Default Settings Tables
Set Menu
Parameters in highlighted rows are reset when the application is changed [SET–00].
CODE Display Basic Supply Fan Exhaust
Fan Cooling
Tower Centrifugal
Pump Submersible
Pump Vacuum
Pump Constant
Torque FE
MagForce PM Motor
SET-01 Input Phase 3-Phase 3-Phase 3-Phase 3-Phase 3-Phase 3-Phase 3-Phase 3-Phase 3-Phase 3-Phase
SET-02 Motor HP By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
SET-03 Motor FLA (SFA) By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
SET-04 Motor RPM 1750 1750 1750 1750 1750 3450 1750 1750 3600 3450
SET-05 Motor Voltage By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
SET-06 Motor Freq Sel *60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz
SET-07 Auto Speed Ref ACI Analog PID Output PID Output PID Output PID Output PID Output PID Output ACI Analog PID Output ACI Analog
SET-08 Auto Run Cmd Digital
Input Keypad Keypad Keypad Keypad Keypad Keypad Keypad Keypad Keypad
SET-09 Hand Speed Ref Keypad Keypad Keypad Keypad Keypad Keypad Keypad Keypad Keypad Keypad
SET-10 Hand Run Cmd Keypad Keypad Keypad Keypad Keypad Keypad Keypad Keypad Keypad Keypad
SET-11 Accel Time 20 Sec 20 Sec 20 Sec 20 Sec 20 Sec 2 Sec 20 Sec 20 Sec 2 Sec 20 Sec
SET-12 Decel Time 30 Sec 30 Sec 30 Sec 30 Sec 30 Sec 2 Sec 30 Sec 30 Sec 2 Sec 30 Sec
SET-13 Low Freq Limit 20 Hz 20 Hz 20 Hz 20 Hz 20 Hz 30 Hz 20 Hz 0 Hz 60 Hz 40 Hz
SET-14 High Freq Limit 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 120 Hz 120 Hz
SET-15 Load Rotation FWD Only FWD Only FWD Only FWD Only FWD Only FWD Only FWD Only FWD Only FWD & REV FWD Only
SET-16 Stop Mode Coast Coast Coast Coast Decel Coast Coast Decel Coast Coast
SET-17 PID Mode Disable PID Direct PID Inverse PID Inverse PID Direct PID Direct PID Direct PID Direct PID Direct PID Direct
SET-18 PID F/B Source ACI ACI ACI ACI ACI ACI ACI ACI ACI ACI
SET-19 PID F/B Unit inWC inWC inWC °F PSI PSI inWC PSI PSI inWC
SET-20 PID F/B Max 1 inWC 1 inWC 1 inWC 150 °F 100 PSI 100 PSI 406.9 inWC 100 PSI 100 PSI 1 inWC
SET-21 PID Set-point 0.5 inWC 0.5 inWC 0.5 inWC 76 °F 60 PSI 60 PSI 60 inWC 60 PSI 60 PSI 0.5 inWC
SET-22 PID Lo Hz Limit 20 Hz 20 Hz 20 Hz 20 Hz 20 Hz 30 Hz 20 Hz 20 Hz 60 Hz 40 Hz
SET-23 PID Hi Hz Limit 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 120 Hz 120 Hz
SET-24 PID P-Gain 1% 1% 1% 1% 2% 2% 1% 1% 2% 1%
SET-25 PID I-Time 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 0.5 Sec 0.5 Sec 1 Sec
SET-26 Sleep Mode Disabled Disabled Disabled Disabled Sleep Only Sleep Only Disabled Disabled Sleep Only Disabled
SET-27 Sleep Chk Time 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec
SET-28 Sleep Delay Time 6 Sec 6 Sec 6 Sec 6 Sec 6 Sec 6 Sec 6 Sec 6 Sec 6 Sec 6 Sec
SET-29 S-Boost Value 3% 3% 3% 3% 3% 3% 3% 3% 3% 3%
SET-30 Sleep Boost Timer 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec
SET-31 Wake-Up Level 0.45 inWC 0.5 inWC 0.5 inWC 75 °F 55 PSI 55 PSI 55 inWC 55 PSI 55 PSI 0.5 inWC
SET-32 S-Bump Timer 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec
SET-33 Pipe Fill Timer 0 Min 0 Min 0 Min 0 Min 0 Min 0 Min 0 Min 0 Min 3 Min 0 Min
SET-34 Pipe Fill Exit Level 0.4 inWC 0.4 inWC 0.4 inWC 74 °F 25 PSI 25 PSI 25 inWC 25 PSI 25 PSI 0.4 inWC
SET-35 Pipe Fill Freq 47 Hz 47 Hz 47 Hz 47 Hz 47 Hz 47 Hz 47 Hz 47 Hz 95 Hz 95 Hz
SET-36 Broken Pipe Lvl 0 inWC 0 inWC 0inWC 0 °F 15 PSI 15 PSI 0 inWC 0 PSI 15 PSI 0.4 inWC
SET-37 Broken Pipe Freq 59.5 Hz 59.5 Hz 59.5 Hz 59.5 Hz 59.5 Hz 59.5 Hz 59.5 Hz 59.5 Hz 114 Hz 114 Hz
SET-38 Broken Pipe Dly 180 Sec 180 Sec 180 Sec 180 Sec 180 Sec 180 Sec 180 Sec 180 Sec 180 Sec 180 Sec
SET-39 OverPress Set Disabled Disabled Disabled Disabled OP Auto
Reset
OP Auto
Reset Disabled OP Auto
Reset
OP Auto
Reset Disabled
SET-40 OverPress Lvl 1 inWC 1 inWC 1 inWC 80 °F 80 PSI 80 PSI 80 inWC 80 PSI 80 PSI 1 inWC
SET-41 ULD Select By Current By Current By Current By Current By Current By Current By Current By Current By Torque By Torque
SET-42 ULD Level 45% 45% 45% 45% 45% 70% 45% 45% 60% 45%
SET-43 ULD Frequency 30 Hz 30 Hz 30 Hz 30 Hz 30 Hz 59 Hz 30 Hz 20 Hz 60 Hz 40 Hz
SET-44 ULD Delay 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec

DEFAULT SETTINGS TABLES
I/O Menu
17
* If Motor Freq Sel [SET-06] is changed to 50 Hz, all output frequency related parameters are adjusted. Refer to the owner’s manual.
I/O Menu
Parameters in highlighted rows are reset when the application is changed [SET–00].
SET-45 ULD Recovery T 0 Min 0 Min 0 Min 0 Min 30 Min 30 Min 0 Min 0 Min 30 Min 0 Min
SET-46 ULD Recover Cnt Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only
SET-47 HLD Select By Current By Current By Current By Current By Current By Current By Current By Current By Torque By Torque
SET-48 HLD Level 110% 110% 110% 110% 110% 110% 110% 150% 110% 110%
SET-49 HLD Frequency 20 Hz 20 Hz 20 Hz 20 Hz 20 Hz 30 Hz 20 Hz 20 Hz 60 Hz 40 Hz
SET-50 HLD Delay 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 5 Sec 2 Sec
SET-51 HLD Recovery T 0 Min 0 Min 0 Min 0 Min 0 Min 0 Min 0 Min 0 Min 0 Min 0 Min
SET-52 HLD Recover Cnt Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only
SET-53 ACC Change Freq 0 Hz 0 Hz 0 Hz 0 Hz 0 Hz 0 Hz 0 Hz 0 Hz 60 Hz 0 Hz
SET-54 Second ACC 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 5 Sec 60 Sec
SET-55 Second DEC 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 5 Sec 60 Sec
SET-56 ACC/DEC Hyster 0 Hz 0 Hz 0 Hz 0 Hz 0 Hz 1 Hz 0 Hz 0 Hz 1 Hz 0 Hz
SET-57 Display Line 1 Freq
Command
Freq
Command
Freq
Command
Freq
Command
Freq
Command
Freq
Command
Freq
Command
Freq
Command
Freq
Command
Freq
Command
SET-58 Display Line 3 PID
Feedback %
PID
Feedback %
PID
Feedback %
PID
Feedback %
PID
Feedback %
PID
Feedback %
PID
Feedback %
PID
Feedback %
PID
Feedback %
PID
Feedback %
SET-59 Keypad Freq 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 10 Hz 115 Hz 115 Hz
SET-60 HOA Mode Source Keypad Keypad Keypad Keypad Keypad Keypad Keypad Keypad Keypad Keypad
SET-61 KPD STOP as OFF Disable Disable Disable Disable Disable Disable Disable Disable Disable Disable
SET-62 Carrier Freq 2 kHz 2 kHz 2 kHz 2 kHz 2 kHz 2 kHz 2 kHz 2 kHz 2 kHz 2 kHz
SET-63 2/3-Wire Select 2-Wire
Fwd/Rev
2-Wire
Fwd/Rev
2-Wire
Fwd/Rev
2-Wire
Fwd/Rev
2-Wire
Fwd/Rev
2-Wire Fwd/
Rev
2-Wire
Fwd/Rev
2-Wire
Fwd/Rev
2-Wire
Fwd/Rev
2-Wire
Fwd/Rev
CODE Display Basic Supply Fan Exhaust
Fan Cooling
Tower Centrifugal
Pump Submersible
Pump Vacuum
Pump Constant
Torque FE
MagForce PM Motor
CODE Display Basic Supply Fan Exhaust
Fan Cooling
Tower Centrifugal
Pump Submersible
Pump Vacuum
Pump Constant
Torque FE MagForce PM Motor
IO-00 ACI Input Sel 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA
IO-01 ACI Loss Trip Disable Stop/Start Stop/Start Stop/Start Trip Stop Trip Stop Trip Stop Stop/Start Stop/Start Trip Stop
IO-02 ACI Loss Level Below
Minimum
Below
Minimum
Below
Minimum
Below
Minimum
Below
0.5xMin
Below
0.5xMin
Below
Minimum
Below
Minimum
Below
0.5xMin
Below
0.5xMin
IO-03 ACI Loss Delay 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec
IO-04 ACI Filter T 0.1 Sec 0.1 Sec 0.1 Sec 0.1 Sec 0.1 Sec 0.1 Sec 0.1 Sec 0.1 Sec 0.1 Sec 0.1 Sec
IO-05 AVI1 Input Sel 0-10V 0-10V 0-10V 0-10V 0-10V 0-10V 0-10V 0-10V 0-10V 0-10V
IO-06 AVI1 Loss Trip Disable Disable Disable Disable Disable Disable Disable Disable Disable Disable
IO-07 AVI1 Loss Lvl Below
Minimum
Below
Minimum
Below
Minimum
Below
Minimum
Below
0.5xMin
Below
0.5xMin
Below
Minimum
Below
Minimum
Below
0.5xMin
Below
0.5xMin
IO-08 AVI1 Loss Delay 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec
IO-09 AVI1 Filter T 0.2 Sec 0.2 Sec 0.2 Sec 0.2 Sec 0.2 Sec 0.2 Sec 0.2 Sec 0.2 Sec 0.2 Sec 0.2 Sec
IO-10 AVI2 Filter T 0.2 Sec 0.2 Sec 0.2 Sec 0.2 Sec 0.2 Sec 0.2 Sec 0.2 Sec 0.2 Sec 0.2 Sec 0.2 Sec
IO-11 Spare Max Value 1 inWC 1 inWC 1 inWC 150 °F 200 PSI 200 PSI 200 inWC 200 PSI 200 PSI 200 inWC
IO-12 Spare AI Select AVI1 AVI1 AVI1 AVI1 AVI1 AVI1 AVI1 AVI1 AVI1 AVI1
IO-13 F/B PT Status Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only
IO-14 PID Filter Time 0.5 Sec 0.5 Sec 0.5 Sec 0.5 Sec 0.5 Sec 0.5 Sec 0.5 Sec 0.5 Sec 0.5 Sec 0.5 Sec
IO-15 PID Delay Time 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec
IO-16 Limit by Level Disable Disable Disable Disable Disable Disable Disable Disable Disable Disable
IO-17 Max Limit Level 6 Feet 0.9 inWC 0.9 inWC 140 °F 50 PSI 6 Feet 50 PSI 50 PSI 6 Feet 6 Feet
IO-18 Min Limit Level 3 Feet 0.8 inWC 0.8 inWC 130 °F 40 PSI 3 Feet 40 PSI 40 PSI 3 Feet 3 Feet
IO-19 Min Freq Limit 40 Hz 40 Hz 40 Hz 40 Hz 40 Hz 40 Hz 40 Hz 40 Hz 80 Hz 80 Hz
IO-20 DI Filter 0.005 Sec 0.005 Sec 0.005 Sec 0.005 Sec 0.005 Sec 0.005 Sec 0.005 Sec 0.005 Sec 0.005 Sec 0.005 Sec
IO-21 MI1 Define Speed-L None None None None None None None None None

DEFAULT SETTINGS TABLES
I/O Menu
18
IO-22 MI2 Define Speed-M None None None None None None None None None
IO-23 MI3 Define Speed-H None None None None None None None None None
IO-24 MI4 Define Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset
IO-25 MI5 Define E-Stop E-Stop E-Stop E-Stop E-Stop E-Stop E-Stop E-Stop E-Stop E-Stop
IO-26 MI6 Define XCEL-L XCEL-L XCEL-L XCEL-L XCEL-L XCEL-L XCEL-L XCEL-L XCEL-L XCEL-L
IO-27 MI7 Define None None None None None None None None None None
IO-28 MI8 Define None None None None None None None None None None
IO-29 FO Enable Disable Disable Disable Disable Disable Disable Disable Disable Disable Disable
IO-30 FO Frequency 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 115 Hz 115 Hz
IO-31 FO Fault Retry 10 10 10 10 10 10 10 10 10 10
IO-32 FO Retry Delay 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec
IO-33 FO Mode & Reset PID Off
Auto
PID On
Auto
PID On
Auto
PID On
Auto
PID On
Auto PID On Auto PID On
Auto
PID Off
Auto PID On Auto PID Off
Auto
IO-34 FO PID S-Point 0 inWC 0 inWC 0 inWC 0 °F 0 PSI 0 PSI 0 inWC 0 PSI 0 PSI 0 inWC
IO-35 Ext Trip Mode Coast Coast Coast Coast Coast Coast Coast Coast Coast Coast
IO-36 Damper Mode Disable Enable Enable Disable Disable Disable Disable Disable Disable Disable
IO-37 Damper T-Delay 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec 60 Sec
IO-38 No-Flow Mode Disable Disable Disable Disable Disable Disable Disable Disable Disable Disable
IO-39 Prime Time 20 Sec 20 Sec 20 Sec 20 Sec 20 Sec 20 Sec 20 Sec 20 Sec 20 Sec 20 Sec
IO-40 No-Flow Freq 20 Hz 20 Hz 20 Hz 20 Hz 20 Hz 30 Hz 20 Hz 20 Hz 60 Hz 40 Hz
IO-41 Lube/S-Clean Disable Disable Disable Disable Disable Disable Disable Disable Disable Disable
IO-42 S-Clean Timer 60 Min 60 Min 60 Min 60 Min 60 Min 60 Min 60 Min 60 Min 60 Min 60 Min
IO-43 Pre-Lube Timer 30 Sec 30 Sec 30 Sec 30 Sec 30 Sec 30 Sec 30 Sec 30 Sec 30 Sec 30 Sec
IO-44 Run-Lube Timer 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec
IO-45 Post-Lube Timer 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec
IO-46 DI NO/NC N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O.
IO-47 Relay RA1 Fault Fault Fault Fault Fault Fault Fault Fault Fault Fault
IO-48 Relay RA2 Run Run Run Run Run Run Run Run Run Run
IO-49 Relay RA3 FDT-4 FDT-4 FDT-4 FDT-4 FDT-4 FDT-4 FDT-4 FDT-4 FDT-4 FDT-4
IO-50 CNT Attained 0 0 0 0 0 0 0 0 0 0 0
IO-51 CNT Attained 1 0 0 0 0 0 0 0 0 0 0
IO-52 FDT-2 Freq 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 115 Hz 115 Hz
IO-53 FDT-2 Bandwdth 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz
IO-54 FDT-3 Freq 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 115 Hz 115 Hz
IO-55 FDT-3 Bandwdth 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz
IO-56 I Hi/Lo Setting 0% 0% 0% 0% 0% 0% 0% 0% 0% 0%
IO-57 FDT-4/5 Setting 3.0 Hz 3.0 Hz 3.0 Hz 3.0 Hz 3.0 Hz 3.0 Hz 3.0 Hz 3.0 Hz 3.0 Hz 3.0 Hz
IO-58 Relay NO/NC N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O.
IO-59 AFM1 Out Select Output
FREQ
Output
FREQ
Output
FREQ
Output
FREQ
Output
FREQ Output FREQ Output
FREQ
Output
FREQ Output FREQ Output
FREQ
IO-60 AFM1 Gain 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
IO-61 AFM2 Out Select ACI % ACI % ACI % ACI % ACI % ACI % ACI % ACI % ACI % ACI %
IO-62 AFM2 Gain 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
IO-63 AFM1 mA Select 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA
IO-64 AFM2 mA Select 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA 4-20mA
IO-65 AFM1 Filter Time 0.01 Sec 0.01 Sec 0.01 Sec 0.01 Sec 0.01 Sec 0.01 Sec 0.01 Sec 0.01 Sec 0.01 Sec 0.01 Sec
IO-66 AFM2 Filter Time 0.01 Sec 0.01 Sec 0.01 Sec 0.01 Sec 0.01 Sec 0.01 Sec 0.01 Sec 0.01 Sec 0.01 Sec 0.01 Sec
IO-72 FO Bypass Disable Disable Disable Disable Disable Disable Disable Disable Disable Disable
IO-73 FO Bypass Delay 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec
IO-74 D-Inputs Status Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only
IO-75 D-Relays Status Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only
IO-76 AI Loss Freq 40 Hz 40 Hz 40 Hz 40 Hz 40 Hz 40 Hz 40 Hz 40 Hz 80 Hz 80 Hz
CODE Display Basic Supply Fan Exhaust
Fan Cooling
Tower Centrifugal
Pump Submersible
Pump Vacuum
Pump Constant
Torque FE MagForce PM Motor

DEFAULT SETTINGS TABLES
ADV Menu
19
ADV Menu
Parameters in highlighted rows are reset when the application is changed [SET–00].
CODE Display Basic Supply Fan Exhaust
Fan Cooling
Tower Centrifugal
Pump Submersible
Pump Vacuum
Pump Constant
Torque FE MagForce PM Motor
ADV-00 Upper Bound Int 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
ADV-01 PID Out Limit 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
ADV-02 Password Input 0 0 0 0 0 0 0 0 0 0
ADV-03 Parameter Reset None None None None None None None None None None
ADV-05 Password Lock Unlocked Unlocked Unlocked Unlocked Unlocked Unlocked Unlocked Unlocked Unlocked Unlocked
ADV-06 Acc/Dec Type Linear Acc/
Dec
Linear Acc/
Dec
Linear Acc/
Dec
Linear Acc/
Dec
Linear Acc/
Dec
Linear Acc/
Dec
Linear Acc/
Dec
Linear Acc/
Dec
Linear Acc/
Dec
Linear Acc/
Dec
ADV-07 Acc/Dec Format Unit 0.1 sec Unit 0.1 sec Unit 0.1 sec Unit 0.1 sec Unit 0.1 sec Unit 0.1 sec Unit 0.1 sec Unit 0.1 sec Unit 0.1 sec Unit 0.1 sec
ADV-08 Energy Saving Disable Disable Disable Disable Disable Disable Disable Disable Disable Disable
ADV-09 E-Saving Gain 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
ADV-10 MMC Mode Disable Disable Disable Disable Disable Disable Disable Disable Disable Disable
ADV-11 Motor Quantity 1 1 1 1 1 1 1 1 1 1
ADV-12 Aux Motor Stop
Hz 0 Hz 0 Hz 0 Hz 0 Hz 0 Hz 0 Hz 0 Hz 0 Hz 0 Hz 0 Hz
ADV-13 Alt Run Time 720 Min 720 Min 720 Min 720 Min 720 Min 720 Min 720 Min 720 Min 720 Min 720 Min
ADV-14 S-Start ON Delay 1 sec 1 sec 1 sec 1 sec 1 sec 1 sec 1 sec 1 sec 1 sec 1 sec
ADV-15 S-Start Off Delay 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec 1 Sec
ADV-16 Motor Switch
Tmr 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec
ADV-17 Motor Switch Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 115 Hz 115 Mz
ADV-18 Lag Start Freq 59.5 Hz 59.5 Hz 59.5 Hz 59.5 Hz 59.5 Hz 59.5 Hz 59.5 Hz 59.5 Hz 114 Hz 114 Hz
ADV-19 Lag Start Delay 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec
ADV-20 Lag Start Level 2% 2% 2% 2% 2% 2% 2% 2% 2% 2%
ADV-21 Lead Freq Drop 10 Hz 10 Hz 10 Hz 10 Hz 10 Hz 10 Hz 10 Hz 10 Hz 10 Hz 10 Hz
ADV-22 MMC Decel Time 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec
ADV-23 Lag Stop Freq 35 Hz 35 Hz 35 Hz 35 Hz 35 Hz 35 Hz 35 Hz 35 Hz 70 Hz 50 Hz
ADV-24 Lag Stop Delay 4 Sec 4 Sec 4 Sec 4 Sec 4 Sec 4 Sec 4 Sec 4 Sec 4 Sec 4 Sec
ADV-25 Lag Stop Level 0.3% 0.3% 0.3% 0.3% 0.3% 0.3% 0.3% 0.3% 0.3% 0.3%
ADV-26 Lead Freq Bump 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz
ADV-27 MMC Accel Time 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec
ADV-28 Power-On Delay 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec
ADV-29 Run Delay Timer 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec
ADV-30 Backspin Timer 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec
ADV-31 Aux Timer Type On-Delay On-Delay On-Delay On-Delay On-Delay On-Delay On-Delay On-Delay On-Delay On-Delay
ADV-32 Aux Timer Time 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec
ADV-33 Aux Timer Input FWD DI FWD DI FWD DI FWD DI FWD DI FWD DI FWD DI FWD DI FWD DI FWD DI
ADV-34 Min Run Timer 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec 0 Sec
ADV-35 Multi-VFD Set Single VFD Single VFD Single VFD Single VFD Single VFD Single VFD Single VFD Single VFD Single VFD Single VFD
ADV-36 Standby Pumps 0 0 0 0 0 0 0 0 0 0
ADV-37 Multi-VFD ID VFD-1 VFD-1 VFD-1 VFD-1 VFD-1 VFD-1 VFD-1 VFD-1 VFD-1 VFD-1
ADV-38 VLag Start Freq 59.5 Hz 59.5 Hz 59.5 Hz 59.5 Hz 59.5 Hz 59.5 Hz 59.5 Hz 59.5 Hz 114 Hz 114 Hz
ADV-39 VLag Start Delay 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec 10 Sec
ADV-40 VLag Stop Freq 35 Hz 35 Hz 35 Hz 35 Hz 35 Hz 35 Hz 35 Hz 35 Hz 70 Hz 50 Hz
ADV-41 VLag Stop Delay 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec
ADV-42 VLead/Lag ID Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only
ADV-43 VLag Spd Source PID PID PID PID PID PID PID PID PID PID
ADV-44 VLag Set Freq 55 Hz 55 Hz 55 Hz 55 Hz 55 Hz 55 Hz 55 Hz 55 Hz 110 Hz 110 Hz
ADV-45 Alternation Disable Disable Disable Disable Disable Disable Disable Disable Disable Disable
ADV-46 Alternate TMR 24 Hour 24 Hour 24 Hour 24 Hour 24 Hour 24 Hour 24 Hour 24 Hour 24 Hour 24 Hour
ADV-47 Set VFD Ready Ready Ready Ready Ready Ready Ready Ready Ready Ready Ready
ADV-48 Jockey Mode Disable Disable Disable Disable Disable Disable Disable Disable Disable Disable
ADV-49 J-Start Press 0.5 inWC 0.5 inWC 0.5 inWC 75 °F 54 PSI 54 PSI 54 inWC 54 PSI 54 PSI 0.5 inWC
ADV-50 J-Start Freq 50 Hz 50 Hz 50 Hz 50 Hz 50 Hz 50 Hz 50 Hz 50 Hz 100 Hz 100 Hz
ADV-51 Main Stop Freq 40 Hz 40 Hz 40 Hz 40 Hz 40 Hz 40 Hz 40 Hz 40 Hz 80 Hz 80 Hz
ADV-52 J-Start Delay 20 Sec 20 Sec 20 Sec 20 Sec 20 Sec 20 Sec 20 Sec 20 Sec 20 Sec 20 Sec

DEFAULT SETTINGS TABLES
ADV Menu
800.348.2420 |franklin-electric.com
For technical assistance, parts, or repair, please contact:
Form 10000005066 Rev. 002 03/22 Copyright © 2022, Franklin Electric, Co., Inc. All rights reserved.
ADV-53 Main Stop Delay 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec 5 Sec
ADV-55 AVR Select Enable Enable Enable Enable Enable Enable Enable Enable Enable Enable
ADV-56 Prog-1 Setting None None None None None None None None None None
ADV-57 Prog-1 On Time 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01
ADV-58 Prog-1 Off Time 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01
ADV-59 Prog-1 Week Day None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
ADV-60 Prog-2 Setting None None None None None None None None None None
ADV-61 Prog-2 On Time 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01
ADV-62 Prog-2 Off Time 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01
ADV-63 Prog-2 Week
Day None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
ADV-64 Prog-3 Setting None None None None None None None None None None
ADV-65 Prog-3 On Time 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01
ADV-66 Prog-3 Off Time 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01
ADV-67 Prog-3 Week
Day None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
ADV-68 Prog-4 Setting None None None None None None None None None None
ADV-69 Prog-4 On Time 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01
ADV-70 Prog-4 Off Time 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01 00:01
ADV-71 Prog-4 Week
Day None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
None
Selected
ADV-74 Set-Point-A 0.5 inWC 0.5 inWC 0.5 inWC 76 °F 60 PSI 60 PSI 60 inWC 60 PSI 60 PSI 0.5 inWC
ADV-75 Set-Point-B 0.5 inWC 0.5 inWC 0.5 inWC 76 °F 60 PSI 60 PSI 60 inWC 60 PSI 60 PSI 0.5 inWC
ADV-76 Set-Point-AB 0.5 inWC 0.5 inWC 0.5 inWC 76 °F 60 PSI 60 PSI 60 inWC 60 PSI 60 PSI 0.5 inWC
CODE Display Basic Supply Fan Exhaust
Fan Cooling
Tower Centrifugal
Pump Submersible
Pump Vacuum
Pump Constant
Torque FE MagForce PM Motor
Other manuals for Cerus X-Drive
2
Table of contents
Other Franklin Electric DC Drive manuals

Franklin Electric
Franklin Electric SubDrive Connect Plus SDCP-SUB0723 User manual

Franklin Electric
Franklin Electric Fhoton 2 User manual

Franklin Electric
Franklin Electric Cerus X-Drive User manual

Franklin Electric
Franklin Electric Cerus X-Drive User manual

Franklin Electric
Franklin Electric SUBDRIVE UTILITY UT3P User manual

Franklin Electric
Franklin Electric FHOTON User manual

Franklin Electric
Franklin Electric SubDrive Inline 1100 User manual

Franklin Electric
Franklin Electric SUBDRIVE CONNECT PLUS User manual

Franklin Electric
Franklin Electric SubDrive 50 User manual

Franklin Electric
Franklin Electric SubDrive Connect Plus SDCP-SUB2043 User manual