Page 5 REV 0999 RTU1-IS
A) ISB and ISC Engines ...
In order for the RTU to operate on the Cummins ISC and
ISB engines,it is important that the ECM be programmed
properly and some of the inputs are enabled.
1) Program setting:
a) The remote throttle option in the ECM has to be turned on. This cannot be done using
the diagnostic tool. An authorized dealer with the 'INSIGHT' service tool is needed to turn
the remote throttle option on.
b) The ECM has 2 operating modes: 'Automotive' governor mode and the 'All-speed' gov-
ernor mode. For the ISB/ISC engines, the user must ensure that the default governor is
selected appropriately when programming the user features. Under normal operating situa-
tion, the cab foot throttle is set up as 'Automotive'(min/max) governor.
2) Enabling the 'All-speed' governor when the pump is engaged
For the RTU to work properly, the 'All-speed' governor mode has to be selected in the
ECM. Note: Select the 'All-speed' governor only when the RTU governor is active,
e.g: the pump is engaged.To select the 'All-speed' governor mode, the 'Selected Throttle
Control Switch' ( pin B6 ) has to be grounded. This is assuming that the cab foot throttle is
set up as min/max (Automotive ) governor. (The 'Selected Throttle Control Switch' toggles
the operating modes, ie: if the default mode is 'All-speed' governor, grounding the switch
will change the control mode to the 'Automotive governor.)
3) Enabling the 'Remote Throttle ON/OFF' input
In order for the remote throttle to be active, the 'Remote Throttle ON/OFF' input (ECM B
connector pin B45) has to be grounded. Since the 'All-speed' governor and the 'Remote
Throttle ON/OFF' inputs are enabled by grounding pin B6 and pin B45, both of these
signals can be activated together.
4) Remote Throttle input
Connect the Remote Throttle cable to the ECM B connector pin B9, B10, and B20. Refer
to Figure 1 for details.
Interface to the ECM
"A" Connector
"B" Connector