CAUSE
No power
Poor plug contact at cutlet.
Bucket is full.
Humidity control is at Off position
Wire disconnect or loose
CONDITION
1. Dehumidifier does net start. (Both
compressor and fan motor do not
operate.)
Capacitor
(Discharge capacitor beforetesting.)
2. Motorrunsbutcompressordoesnot
run. Voltage (115V _+10%)
Wiring
REMEDY
Check powersupply at outlet.
Correct if none.
Installplug properly or replace it.
If Auto Shut Offlights, empty the bucket
and replace properly.
Turn the humidity control switch toward
Max.
Connect wire. Refer to wiring diagram for
terminal identification. Repairor replace
loose terminal.
Testcapacitor,
Replace if not within ±10% of
manufacturer's rating. Replace if shorted,
open, or damaged.
Itmust be between 103.5V and 126,5V, If
not within limits, call an electrician
Check the wire connections: If loose,
repair or replace the terminal. If the wires
are disconnected, referto wiring diagram
tar identification, and replace the wires.
Check the wire connections; If not
according to the wiring diagram, correct
the connections.
Rotary switch Check for continuity, refer to the wiring
diagram for terminal identification. Replace
the switch if the circuit is open.
Defrost control
Capacitor
(Discharge capacitor before servicing.)
The Defrost Control senses frost build-up
on the evaporator coil and automatically
shuts off the compressor, The fan .
continues to ran,drawing air across the
coil, and meltingthe frost. When the coil is
defrosted, the compressor automatically
restarts, anddehumidifying resumes.
Check the capacitor,
Replace if not within _+10%of
manufacturer's rating. Replace if shorted,
open, or damaged.
Compressor Check the compressor for open circuit or
ground. If openor grounded, replace the
compressor.
Overload protector (O.L.P.) Check the compressor O.L.P. if exlernally
mounted. Replace if open. (If the
compressor temperature is high, remove
O.L,P., cool, and retest.)
I Defrost control is defective.
Low relativehumidity
Poor air circulation
3. Does not defrost control. Check defrost control, replace it.
4. Insufficient dehumidificalion Turn dehumidifier oft.
Movedehumidifier toobtain free and
unobstructed aircirculation.
Coils clogged with dust and dirt. Cleanevaporatorand!orcondenserassemb(y
Air filter is dirty. Clean it,
Motor is not operating. CheckMotor,repairor replace it.
15