The 2nd Generation DC Series VRF Indoor Units
Kaysun 2nd Generation DC Series Duct VRF Indoor Units Engineering Data Book
201805 3
KPDHF-112 DN4.0 / KPDHF-140 DN4.0 / KPDHF-160 DN4.0
Table 1.2: KPDHF-112(140,160)DN4.0 specifications
Model name KPDHF-112 DN4.0 KPDHF-140 DN4.0 KPDHF-160 DN4.0
Power supply 1-phase, 220-240V, 50Hz
Cooling1Capacity kW 11.2 14 16
kBut/h 38.2 47.8 54.6
Input W 380 420 700
Heating2Capacity kW 12.5 16 17
kBut/h 42.7 54.6 58
Input W 380 420 700
Fan motor
Model WZDK750-38G-W WZDK750-38GS-W WZDK750-38GS-W
Type DC
Brand Pansonic/ Welling
Speed (H/M/L) r/min 1113/1066/1012/971/
925/876/840
1019/981/941/902/
855/808/765
1080/1046/996/954/
910/869/825
Coil
Number of rows 925/876/840 1019/981/941/902/ 4
Tube pitch ×row pitch mm 855/808/765 1080/1046/996/954/ 25.4×22
Fin spacing mm 910/869/825 1.6 1.6
Fin type Hydrophilic aluminum
Tube OD and type mm Ф9.53 Inner groove
Dimensions (L×H ×W) mm 700×356×66 996×356×88 996×356×88
Number of circuits 7 7 7
Airflow rate3m3/h 1870/1783/1697/1610/
1523/1437/1350
2240/2133/2027/1920/
1813/1707/1600
2660/2530/2400/2270/
2140/2010/1880
External static pressure4Pa 100 (30~ 200)
Sound pressure level5dB(A) 48/47/46/45/43/42/41 45/44/43/42/41/40/40 46/45/44/43/42/41/40
Sound power level dB(A) 66/65/64/63/61/60/59 63/62/61/60/59/58/58 64/63/62/61/60/59/58
Unit
Net dimensions6
(W×H×D) mm 952×420×690 1300×420×690 1300×420×690
Packed dimensions
(W×H×D) mm 1090×440×768 1436×450×768 1436×450×768
Net/Gross weight kg 51/57 63/70 63/70
Refrigerant type R410A
Throttle Type Electronic expansion valve
Model BD20FKS(L)
Design pressure (H/L) MPa 4.4/2.6
Pipe
connections
Liquid/Gas pipe mm Ф9.53/Ф19.1
Drain pipe mm OD Ф25
Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Fan motor speed and air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.
4. Stable operation external static pressure range. (Note: setting external static pressure outside the unit’s optimal static pressure range may lead to higher
noise levels and lower airflow rate. For the optimal external static pressure range refer to the unit’s installation manual.)
5. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.4m below the unit in a semi-
anechoic chamber.
6. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.