FSP Technology LightUp L8000 User manual

Version: 1.1
User Manual
LightUp L8000
Off-grid Solar Inverter

0
Table of Contents
ABOUT THIS MANUAL.................................................................................................................................1
Purpose.....................................................................................................................................................1
Scope ........................................................................................................................................................1
SAFETY INSTRUCTIONS.............................................................................................................................1
INTRODUCTION...........................................................................................................................................2
Features.....................................................................................................................................................2
Basic System Architecture..........................................................................................................................2
Product Overview.......................................................................................................................................3
INSTALLATION.............................................................................................................................................4
Unpacking and Inspection..........................................................................................................................4
Preparation................................................................................................................................................4
Mounting the Unit.......................................................................................................................................4
Battery Connection.....................................................................................................................................5
AC Input/Output Connection.......................................................................................................................6
PV Connection...........................................................................................................................................7
FinalAssembly...........................................................................................................................................9
Remote Display Panel Installation............................................................................................................10
DC Output Connectors (Optional)............................................................................................................. 11
Communication Connection...................................................................................................................... 11
Dry Contact Signal ...................................................................................................................................12
BMS Communication................................................................................................................................12
OPERATION ...............................................................................................................................................13
Power ON/OFF........................................................................................................................................13
Inverter Turn-on........................................................................................................................................13
Operation and Display Panel....................................................................................................................13
LCD Display Icons....................................................................................................................................14
LCD Setting .............................................................................................................................................16
LCD Display.............................................................................................................................................29
Operating Mode Description.....................................................................................................................36
Faults Reference Code.............................................................................................................................38
Warning Indicator.....................................................................................................................................39
BATTERY EQUALIZATION.........................................................................................................................40
SPECIFICATIONS.......................................................................................................................................41
Table 1 Line Mode Specifications...............................................................................................................41
Table 2 Inverter Mode Specifications.........................................................................................................42
Table 3 Charge Mode Specifications..........................................................................................................43
Table 4 General Specifications...................................................................................................................44
TROUBLE SHOOTING................................................................................................................................45
Appendix I: Parallel function.....................................................................................................................46
Appendix II: BMS Communication Installation.........................................................................................58
Appendix III: The Wi-Fi Operation Guide in Remote Panel ......................................................................64

1
ABOUT THIS MANUAL
Purpose
This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read
this manual carefully before installations and operations. Keep this manual for future reference.
Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.
SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions. Read and keep
this manual for future reference.
1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all
appropriate sections of this manual.
2. CAUTION --To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries.
Other types of batteries may burst, causing personal injury and damage.
3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required.
Incorrect re-assembly may result in a risk of electric shock or fire.
4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning.
Turning off the unit will not reduce this risk.
5. CAUTION – Only qualified personnel can install this device with battery.
6. NEVER charge a frozen battery.
7. For optimum operation of this inverter/charger, please follow required spec to select appropriate cable
size. It’s very important to correctly operate this inverter/charger.
8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop
a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please
refer to INSTALLATION section of this manual for the details.
10. Fuses are provided as over-current protection for the battery supply.
11. GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded
wiring system. Be sure to comply with local requirements and regulation to install this inverter.
12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input
short circuits.
13. Warning!! Only qualified service persons are able to service this device. If errors still persist after
following troubleshooting table, please send this inverter/charger back to local dealer or service
center for maintenance.
14. WARNING: Because this inverter is non-isolated, only three types of PV modules are acceptable:
single crystalline, poly crystalline with class A-rated and CIGS modules. To avoid any malfunction, do
not connect any PV modules with possible current leakage to the inverter. For example, grounded PV
modules will cause current leakage to the inverter. When using CIGS modules, please be sure NO
grounding.
15. CAUTION: It’s required to use PV junction box with surge protection. Otherwise, it will cause
damage on inverter when lightning occurs on PV modules.

2
INTRODUCTION
This is a multi-function inverter, combining functions of inverter, solar charger and battery charger to offer
uninterruptible power support in a single package. The comprehensive LCD display offers user-configurable
and easy-accessible button operations such as battery charging current, AC or solar charging priority, and
acceptable input voltage based on different applications.
Features
Pure sine wave inverter
Configurable color with the built-in RGB LED bar
Built-in Wi-Fi for mobile monitoring (APP is required)
Supports USB On-the-Go function
Optional 12V DC output
Built-in anti-dusk kit
Detachable LCD control module with multiple communication ports for BMS (RS485, CAN-BUS, RS232)
Configurable input voltage ranges for home appliances and personal computers via LCD control panel
Configurable AC/PV output usage timer and prioritization
Configurable AC/Solar charger priority via LCD control panel
Configurable battery charging current based on applications via LCD control panel
Compatible to utility mains or generator power
Auto restart while AC is recovering
Overload / Over temperature / short circuit protection
Smart battery charger design for optimized battery performance
Cold start function
Basic System Architecture
The following illustration shows basic application for this unit. It also required the following devices to have a
complete running system:
Generator or Utility mains.
PV modules
Consult with your system integrator for other possible system architectures depending on your requirements.
This inverter can power various appliances in home or office environment, including motor-type appliances
such as tube light, fan, refrigerator and air conditioners.
Figure 1 Basic hybrid PV System Overview

3
Product Overview
NOTE: For parallel installation and operation, please check
Appendix I.
1. LCD display 13. Parallel communication port
2. Status indicator 14. Dry contact
3. Charging indicator 15. USB port as USB communication port and USB function
4. Fault indicator port
5. Function buttons 16. BMS communication port: CAN, RS-485 or RS-232
6. Power on/off switch 17. Output source indicators (refer to OPERATION/Operation
7. AC input connectors and Display Panel section for details) and USB function
8. AC output connectors (Load connection) setting reminder (refer to OPERATION/Function Setting for
9. PV connectors the details)
10. Battery connectors 18. RS-232 communication port
11. Remote LCD module communication 19. RGB LED bar (refer to LCD Setting section for the details)
Port 20. 12V DC output connectors (optional)
12. Current sharing port 21. Power switch for DC output (optional)

4
INSTALLATION
Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should
have received the following items inside of package:
Inverter unit Manual software CD RS-232 cable Parallel communication cable Current sharing cable
DC Fuse Cable gland x 5 pcs PV connectors x 2 sets
Preparation
Before connecting all wirings, please take off bottom cover by removing five screws. When removing the
bottom cover, be carefully to remove three cables as shown below.
Mounting the Unit
Consider the following points before selecting where to install:
lDo not mount the inverter on flammable construction materials.
lMount on a solid surface
lInstall this inverter at eye level in order to allow the LCD display to be
read at all times.
lThe ambient temperature should be between 0°C and 55°C to ensure
optimal operation.
lThe recommended installation position is to be adhered to the wall
vertically.
lBe sure to keep other objects and surfaces as shown in the right diagram
to guarantee sufficient heat dissipation and to have enough space for
removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

5
Install the unit by screwing four screws. It’s recommended to use M4 or M5 screws.
Battery Connection
CAUTION: For safety operation and regulation compliance, it’s requested to install a separate DC over-current
protector or disconnect device between battery and inverter. It may not be requested to have a disconnect
device in some applications, however, it’s still requested to have over-current protection installed. Please refer
to typical amperage in below table as required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use
appropriate cable for battery connection. To reduce risk of injury, please use the
proper recommended cable and terminal size as below.
Recommended battery cable and terminal size:
Model Typical
Amperage Battery
capacity Wire Size Cable
mm2
Ring Terminal
Torque
value
Dimensions
D (mm) L (mm)
8KW 182.2A 250AH 1*2/0AWG 67.4 8.4 51 5 Nm
Please follow below steps to implement battery connection:
1. Assemble battery ring terminal based on recommended battery cable and terminal size.
2. Fix two cable glands into positive and negative terminals.
3. Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the nuts are
tightened with torque of 5 Nm. Make sure polarity at both the battery and the inverter/charge is correctly
connected and ring terminals are tightly screwed to the battery terminals.
Ring terminal:

6
WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in series.
CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring
terminal. Otherwise, overheating may occur.
CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected
tightly.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure
positive (+) must be connected to positive (+) and negative (-) must be connected to negative
(-).
AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between
inverter and AC input power source. This will ensure the inverter can be securely disconnected during
maintenance and fully protected from over current of AC input.
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input
and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC
input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires
Model Gauge Torque Value
8KW 8 AWG 1.4~ 1.6Nm
Please follow below steps to implement AC input/output connection:
1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
3. Fix two cable glands into input and output sides.
4. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws.
Be sure to connect PE protective conductor ( )first.
→Ground (yellow-green)
L→LINE (brown or black)
N→Neutral (blue)
WARNING:
Be sure that AC power source is disconnected before attempting to hardwire it to the unit.

7
5. This inverter is equipped with dual-output. There are four terminals (L1/N1, L2/N2) available on output
port. It is to set up through LCD program or monitoring software to turn on and off the second output.
Refer to “LCD setting” section for the details.
Before making wiring of second output, please remove knockout and install the cable gland first.
Insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. Be
sure to connect PE protective conductor ( )first.
→Ground (yellow-green)
L1→LINE (brown or black)
N1→Neutral (blue)
L2→LINE (brown or black)
N2→Neutral (blue)
6. Make sure the wires are securely connected.
PV Connection
CAUTION: Before connecting to PV modules, please install separately DC circuit breakers between inverter
and PV modules.
NOTE1: Please use 600VDC/30A circuit breaker.
NOTE2: The overvoltage category of the PV input is II.
Please follow the steps below to implement PV module connection:
Step 1: Check the input voltage of PV array modules. This system is applied with two strings of PV array.
Please make sure that the maximum current load of each PV input connector is 18A.
Step 2: Disconnect the circuit breaker and switch off the DC switch.
CAUTION: Important
Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause
utility short-circuited when these inverters are worked in parallel operation.
CAUTION: Appliances such as air conditioner requires at least 2~3 minutes to restart because it’s required
to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers
in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please
check manufacturer of air conditioner if it’s equipped with time-delay function before installation. Otherwise,
this inverter/charger will be trigger overload fault and cut off output to protect your appliance but sometimes
it still causes internal damage to the air conditioner.
CAUTION: Exceeding the maximum input voltage can destroy the unit!! Check the system before wire connection.
WARNING: Because this inverter is non-isolated, only three types of PV modules are acceptable: single
crystalline and poly crystalline with class A-rated and CIGS modules.
To avoid any malfunction, do not connect any PV modules with possible current leakage to the inverter. For
example, grounded PV modules will cause current leakage to the inverter. When using CIGS modules, please
be sure NO grounding.
CAUTION: It’s required to use PV junction box with surge protection. Otherwise, it will cause damage on
inverter when lightning occurs on PV modules.

8
Step 3: Assemble provided PV connectors with PV modules by the following steps.
Components for PV connectors and Tools:
Female connector housing
Female terminal
Male connector housing
Male terminal
Crimping tool and spanner
Prepare the cable and follow the connector assembly process:
Insert striped cable into female terminal and crimp female terminal as shown below.
Insert assembled cable into female connector housing as shown below.
Insert striped cable into male terminal and crimp male terminal as shown below.
Insert assembled cable into male connector housing as shown below.
Then, use spanner to screw pressure dome tightly to female connector and male connector as shown below.
Step 4: Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect
positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of
connection cable to negative pole (-) of PV input connector.
WARNING! For safety and efficiency, it's very important to use appropriate cables for PV module connection.
To reduce risk of injury, please use the proper cable size as recommended below.
Conductor cross
-
section
(mm
2
)
AWG no.
4~6 10~12
CAUTION: Never directly touch the terminals of inverter. It might cause lethal electric shock.
Strip one cable 8 mm on both end sides and be careful NOT to nick
conductors.

9
Recommended Panel Configuration
When selecting proper PV modules, please be sure to consider the following parameters:
1. Open circuit Voltage (Voc) of PV modules not to exceed maximum PV array open circuit voltage of the
inverter.
2. Open circuit Voltage (Voc) of PV modules should be higher than the start-up voltage.
INVERTER MODEL 8KW
Max. PV Array Power 8000W
Max. PV Array Open Circuit Voltage 500Vdc
PV Array MPPT Voltage Range 90Vdc~450Vdc
Start-up Voltage (Voc) 80Vdc
Recommended solar panel configuration:
Solar Panel Spec.
(reference)
- 250Wp
- Vmp: 30.7Vdc
- Imp: 8.3A
- Voc: 37.7Vdc
- Isc: 8.4A
- Cells: 60
SOLAR INPUT 1 SOLAR INPUT 2 Q'ty of
panels Total Input
Power
Min in series: 4pcs, per input
Max. in series: 12pcs, per input
4pcs in series x 4pcs 1000W
x 4pcs in series 4pcs 1000W
12pcs in series x 12pcs 3000W
x 12pcs in series 12pcs 3000W
6pcs in series 6pcs in series 12pcs 3000W
6pcs in series, 2 strings x 12pcs 3000W
x 6pcs in series, 2 strings 12pcs 3000W
8pcs in series, 2 strings x 16pcs 4000W
x 8pcs in series, 2 strings 16pcs 4000W
9pcs in series, 1 string 9pcs in series, 1 string 18pcs 4500W
10pcs in series, 1 string 10pcs in series, 1 string 20pcs 5000W
12pcs in series, 1 string 12pcs in series, 1 string 24pcs 6000W
6pcs in series, 2 strings 6pcs in series, 2 strings 24pcs 6000W
7pcs in series, 2 strings 7pcs in series, 2 strings 28pcs 7000W
8pcs in series, 2 strings 8pcs in series, 2 strings 32pcs 8000W
Take the 555Wp PV module as an example. After considering above two parameters, the recommended module
configurations are listed in the table below.
Solar Panel Spec.
(reference)
- 555Wp
- Imp: 17.32A
- Voc: 38.46Vdc
- Isc: 18.33A
- Cells: 110
SOLAR INPUT 1 SOLAR INPUT 2 Q'ty of
panels Total Input
Power
Min in series: 3pcs, per input
Max. in series: 10pcs, per input
3pcs in series x 3pcs 1665W
x 3pcs in series 3pcs 1665W
7pcs in series x 7pcs 3885W
x 7pcs in series 7pcs 3885W
7pcs in series 7pcs in series 14pcs 7770W

10
Final Assembly
After connecting all wirings, re-connect three cables and then put bottom cover back by screwing five screws
as shown below.
Remote Display Panel Installation
The LCD module can be removable and installed in a remote location with an optional communication cable.
Please take the follow steps to implement this remote panel installation.
Step 1. Remove the screw on the bottom of LCD module and pull down the module from the case. Detach
the cable from the original communication port. Be sure to replace the retention plate back to the inverter.

11
Step 2. Prepare your mounting holes in the marked locations as shown in the illustration below. The LCD
module then can be securely mounted to your desired location.
Note: Wall installation should be implemented with the proper screws to the right.
Step 3. After LCD module is installed, connect LCD module to the inverter with an optional RJ45
communication cable as shown below.
DC Output Connectors (optional)
These DC output connectors are used to provide emergency power backup to all kinds of DC-powered
equipment such as routers, modems, set-top box, VOIP phone systems, surveillance system, alarm system,
access control system and many critical telecom equipment. There are 4 channels (current limit at 3A for
each channel), which could be activated/disabled manually either through LCD operation or power switch
beside the DC jacks.
Supplied dimension of DC jack (male) is OD 5.5mm, ID 2.5mm.
Communication Connection
Serial Connection
Please use the supplied serial cable to connect between the inverter and your PC. Install the monitoring
software from the bundled CD and follow the on-screen instructions to complete your installation. For detailed
software operation, refer to the software user manual on the bundled CD.
RS-232 communication
to PC
USB communication to
PC
BMS
communication
Remote
communication

12
Wi-Fi Connection
This unit is equipped with a Wi-Fi transmitter. Wi-Fi transmitter can enable wireless communication between
off-grid inverters and monitoring platform. Users can access and control the monitored inverter with
downloaded APP. You may find “WatchPower” app from the Apple®Store or “WatchPower Wi-Fi” in Google®
Play Store. All data loggers and parameters are saved in iCloud. For quick installation and operation, please
check Appendix III.
Dry Contact Signal
There is one dry contact (3A/250VAC) available on the rear panel. It could be used to deliver signal to external
device when battery voltage reaches warning level.
Unit Status Condition Dry contact port:
NC & C NO & C
Power Off Unit is off and no output is powered. Close Open
Power On
Output is
powered
from Battery
power or
Solar energy.
Program 01
set as USB
(utility first)
or SUB (solar
first)
Battery voltage < Low DC
warning voltage Open Close
Battery voltage > Setting
value in Program 13 or
battery charging reaches
floating stage
Close Open
Program 01
is set as SBU
(SBU priority)
Battery voltage < Setting
value in Program 12 Open Close
Battery voltage > Setting
value in Program 13 or
battery charging reaches
floating stage
Close Open
BMS Communication
It is recommended to purchase a special communication cable if you are connecting to Lithium-Ion battery
banks. Please refer to
Appendix II- BMS Communication Installation
for details.

13
OPERATION
Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch
(located on the display panel) to turn on the unit.
Inverter Turn-on
After this inverter is turned on, WELCOME light show will be started with RGB LED BAR. It will slowly cycle
through entire spectrum of nine colors (Green, Sky blue, Royal blue, Violet, Pink, Red, Honey, Yellow, Lime
yellow) about 10-15 seconds. After initialization, it will light up with default color.
RGB LED BAR can light up in different color and light effects based on the setting of energy priority to
display the operation mode, energy source, battery capacity and load level. These parameters such as
color, effects, brightness, speed and so on can be configured through the LCD panel. Please refer to LCD
settings for the details.
Operation and Display Panel
The operation and the LCD module, shown in the chart below, includes six indicators, six function keys, on/off
switch and a LCD display to indicate the operating status and input/output power information.
Indicators
LED Indicator Color Solid/Flashing Messages
Setting LED 1 Green Solid On Output powered by utility
Setting LED 2 Green Solid On Output powered by PV
Setting LED 3 Green Solid On Output powered by battery
Status
indicators
Green Solid On Output is available in line mode
Flashing Output is powered by battery in battery mode
Green Solid On Battery is fully charged
Flashing Battery is charging.
Red Solid On Fault mode
Flashing Warning mode
Status indicators
Function keys
On/off switch
Function keys
Setting LED 3
Setting LED 1 Setting LED 2
LCD display

14
Function Keys
Function Key Description
ESC Exit the setting
USB function setting Select USB OTG functions
Timer setting for the Output source
priority Setup the timer for prioritizing the output source
Timer setting for the Charger source
priority Setup the timer for prioritizing the charger source
+
Press these two keys at the time to switch RGB LED bar
for output source priority and battery discharge/charge
status
Up To last selection
Down To next selection
Enter To confirm/enter the selection in setting mode
LCD Display Icons
Icon Function description
Input Source Information
Indicates the AC input.
Indicates the PV input
Indicate input voltage, input frequency, PV voltage, charger current,
charger power, battery voltage.
Configuration Program and Fault Information
Indicates the setting programs.
Indicates the warning and fault codes.
Warning: flashing with warning code.
Fault: lighting with fault code
Output Information
Indicate output voltage, output frequency, load percent, load in VA,
load in Watt and discharging current.
The ICON flashing that indicate the unit with AC output and setting
Programs 60,61 or 62 different to default setting.
Battery Information

15
Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100% in
battery mode and charging status in line mode.
When battery is charging, it will present battery charging status.
Status Battery voltage LCD Display
Constant
Current mode /
Constant
Voltage mode
<2V/cell
4 bars will flash in turns.
2 ~ 2.083V/cell Bottom bar will be on and the other three bars
will flash in turns.
2.083 ~ 2.167V/cell Bottom two bars will be on and the other two
bars will flash in turns.
> 2.167 V/cell Bottom three bars will be on and the top bar
will flash.
Floating mode. Batteries are fully charged. 4 bars will be on.
In battery mode, it will present battery capacity.
Load Percentage Battery Voltage LCD Display
Load >50%
< 1.85V/cell
1.85V/cell ~ 1.933V/cell
1.933V/cell ~ 2.017V/cell
> 2.017V/cell
Load < 50%
< 1.892V/cell
1.892V/cell ~ 1.975V/cell
1.975V/cell ~ 2.058V/cell
> 2.058V/cell
Load Information
Indicates overload.
Indicates the load level by 0-24%, 25-49%, 50-74% and 75-100%.
0%~24% 25%~49%
50%~74% 75%~100%
Mode Operation Information
Indicates unit connects to the mains.
Indicates unit connects to the PV panel.
Indicates load is supplied by utility power.
Indicates the utility charger circuit is working.
Indicates the solar charger circuit is working.
Indicates the DC/AC inverter circuit is working.
Indicates unit alarm is disabled.
Indicates USB disk is connected.
Indicates timer setting or time display

16
LCD Setting
General Setting
After pressing and holding “ ”button for 3 seconds, the unit will enter the Setup Mode. Press “ ” or “ ”
button to select setting programs. Press “ ” button to confirm you selection or “ ” button to exit.
Setting Programs:
Program Description Selectable option
00 Exit setting mode
Escape
01 Output source priority:
To configure load power
source priority
Utility first (default) Utility will provide power to the
loads as first priority.
Solar and battery energy will
provide power to the loads only
when utility power is not
available.
Solar first Solar energy provides power to the
loads as first priority.
If solar energy is not sufficient to
power all connected loads, Utility
energy will supply power to the
loads at the same time.
SBU priority
Solar energy provides power to
the loads as first priority.
If solar energy is not sufficient to
power all connected loads, battery
energy will supply power to the
loads at the same time.
Utility provides power to the loads
only when battery voltage drops
to either low-level warning
voltage or the setting point in
program 12.
02
Maximum charging current:
To configure total charging
current for solar and utility
chargers.
(Max. charging current =
utility charging current +
solar charging current)
60A (default)
Setting range is from 10A to
120A . Increment of each click is
10A.

17
03 AC input voltage range
Appliances (default) If selected, acceptable AC input
voltage range will be within 90-
280VAC.
UPS If selected, acceptable AC input
voltage range will be within 170-
280VAC.
05 Battery type
AGM (default) Flooded
User-Defined If “User-Defined” is selected,
battery charge voltage and low
DC cut-off voltage can be set up
in program 26, 27 and 29.
Pylontech battery If selected, programs of 02, 26,
27 and 29 will be automatically
set up. No need for further
setting.
WECO battery If selected, programs of 02, 12,
26, 27 and 29 will be auto-
configured per battery supplier
recommended. No need for
further adjustment.
Soltaro battery If selected, programs of 02, 26,
27 and 29 will be automatically
set up. No need for further
setting.
LIb-protocol compatible
battery Select “ LIb” if using Lithium
battery compatible to Lib
protocol. If selected, programs of
02, 26, 27 and 29 will be
automatically set up. No need for
further setting.

18
3rd party Lithium battery Select “LIC” if using Lithium
battery not listed above. If
selected, programs of 02, 26, 27
and 29 will be automatically set
up. No need for further setting.
Please contact the battery
supplier for installation
procedure.
06 Auto restart when overload
occurs
Restart disable (default) Restart enable
07 Auto restart when over
temperature occurs
Restart disable (default) Restart enable
09 Output frequency
50Hz (default) 60Hz
10 Output voltage
220V 230V (default)
240V
11
Maximum utility charging
current
Note: If setting value in
program 02 is smaller than
that in program in 11, the
inverter will apply charging
current from program 02
for utility charger.
2A 30A (default)
Setting range is 2A, then from 10A to 120A. Increment of each
click is 10A.
Table of contents
Other FSP Technology Inverter manuals
Popular Inverter manuals by other brands

Omnik New Energy
Omnik New Energy Omniksol-5k-TL2-3P user manual

LS
LS SV0008iS7-2 manual

Targus
Targus 200W AC AUTOMOTIVE POWER INVERTER user guide

Kodak
Kodak OG-Plus3.24RM Installation & user manual

BELTTT
BELTTT BEU350L manual

Portable Power Technology
Portable Power Technology SN-BT Series instruction manual